Installation, use and maintenance manual
MANUAL CODE: 6328407
Page 47 / 148
5
INSTALLATION AND HOOK-UPS
WARNING: the product must be installed,
commissioned and maintained by
authorised, qualified personnel. Do not
attempt to install the product by
yourself.
5.1
Preparing the installation site
The product must be installed in a suitable place,
where the normal use and adjustment operations
can be performed, as well as routine and non-
scheduled maintenance.
The necessary operating space must be prepared,
making reference to the measurements shown in
Fig. Fig. 2.
Fig. 6 – Clearances
Model
X1
X2
X3
Y1
mm
mm
mm
mm
ECOMAXI 160 ErP
650
650
200
300
The space must also be:
equipped with suitable water mains and
electricity supply lines;
equipped with a connector for the
condensate outlet;
equipped with suitable water outlets in case of
damage to the boiler, the safety valve being
tripped or breakages in the pipework or
connectors;
equipped with any containment systems in
case of serious water leakages;
sufficiently lit (as required);
20 m
3
in volume, as a minimum;
dry and sheltered from frost.
WARNING: To prevent mechanical
vibrations from spreading, do not install
the appliance on structures with
wooden beams (e.g. in the attic).
5.2
Air ventilation connections
The heat pump requires adequate air ventilation,
in addition to the clearance spaces specified
under 5.1.
Create a specific air duct as shown in figure 3 and
4.
Fig. 7 – Example of air ducting for the model with upper
outlets (standard)
X3
Y1
X2
X1
Fig. 8 – Example of air ducting for the model with additional
rear outlets (optional)
Outsi
de
≥500 kg
Outsi
de