Installation, use and maintenance manual
MANUAL CODE: 6328407
Page 65 / 148
7.2.1.1
Complete list of appliance parameters
Description of parameter
Abbre
viation
Unit
Min.
Max.
Default Notes
Password
PA
0
Specialist technical
personnel only
Setpoint HOT H2O economy cycle
SP1
°C/°F
r3
r4
55.0
Setpoint HOT H2O automatic cycle
SP2
°C/°F
r1
r2
55.0
Setpoint COLD H2O
SP3
°C/°F
10.0
r2
45.0
Setpoint H2O stop heat pump
SP5
°C/°F
r1
SP2
62.0
Setpoint H2O activate digital input, solar
panel supplement
SP6
°C/°F
40.0
100.0
62.0
Setpoint H2O ANTIFREEZE
SP7
°C/°F
0
40
10
Setpoint solar thermal cycle
SP8
°C/°F
0
100.0
40
Setpoint cold evaporator
SP9
°C/°F
-25.0
25.0
4.0
Setpoint faulty evaporator
SP10
°C/°F
-50.0
25.0
-25.0
Calibrate upper probe
CA1
°C/°F
-25.0
25.0
2.0
Calibrate lower probe
CA2
°C/°F
-25.0
25.0
-4.5
Calibrate evaporator probe
CA3
°C/°F
-25.0
25.0
0.0
Type of probe
P0
----
0
1
1
0 = PTC
1 = NTC
2 = PT1000
Decimal point
P1
----
0
1
1
1 = decimal point for
display temperature
Unit of measurement
P2
----
0
1
0
0 = °C
1 = °F
Function associated with evaporator
probe
P4
----
0
2
2
0 = disabled
1 = defrosting start-stop
2 = start defrosting
Local display data
P5
----
0
3
0
0 = upper probe
1 = operating setpoint
2 = lower probe
3 = evaporator probe
Remote display data
P6
----
0
3
0
0 = upper probe
1 = operating setpoint
2 = lower probe
3 = evaporator probe
Cooling down time on display in tenths of
a second
P8
1/10
sec
0
250
5
Operating setpoint differential
r0
°C/°F
0.1
30.0
11.5
Minimum setpoint, auto cycle
r1
°C/°F
10.0
r2
40.0
Maximum setpoint, auto cycle
r2
°C/°F
r1
100.0
70.0
Minimum setpoint, economy cycle
r3
°C/°F
10.0
r4
40.0
Maximum setpoint, economy cycle
r4
°C/°F
r3
100.0
56.0
Lock changes to operating setpoint
r5
----
0
1
0
1 = the setpoint cannot