2.8 

COAXIAL DUCT

“25/60 BF -30/60 BF”

The coaxial inlet and outlet duct ø 60/100

is supplied in a kit code 8084805 complete

with mounting instructions.

2.8.1 

Diaphragm installation

The diaphragm is supplied together with the

“30/60 BF”

boiler version. 

See figure 9 for the positioning.

ATTENTION: 

Install  the  diaphragm  only  when  the

length  of  the  ø  60/100  coaxial  duct  is

less than 1 m.

2.8.2 

Coaxial duct 

accessories

The  accessories  necessary  for  the  realisa-

tion  of  this  type  of  discharge  and  some  of

the  connecting  systems  that  can  be  used

are shown in fig. 10.

With  the  elbow  supplied  in  the  kit  the

maximum length of the duct should not be

greater than 3 metres. 

2.8.3 

Positioning the 

outlet terminals

The  outlet  terminals  for  forced-draught

appliances  may  be  located  in  the  external

perimeter walls of the building. 

To provide some indications of possible solu-

tions, 

Table 1

gives the minimum distances

to  be  observed,  with  reference  to  the  type

of building shown in fig. 11.

2.8.4 

Roof outlet 

coaxial duct

The  roof  outlet  terminal  L.1284  cannot  be

shortened  and  the  positioning  of  the  tile

distances  must  be  no  less  than  600  mm

from the discharge terminal outlet (fig. 12).

The fittings required for this type of dischar-

ge  and  some  of  the  connecting  systems

that can be used are shown in fig. 13. 

Up to a maximum of three extensions can

be  added  to  reach  a  rectilinear  length  of

3.7 m. If it proves necessary to provide for

78

KEY

1a-b

Coaxial duct kit code 8084802

Extension L.815 code 8084800

Vertical extension L.584 code 8086900

Supplementary 90° elbow code 8085600

TABLE1

Siting of terminal

Appliances from 7 to 35 kW

(distances in mm)

A - below openable window

600

B - below ventilation opening

600

C - below eaves

300

D - below balcony (1)

300

E - from adjacent window

400

F - from adjacent ventilation opening

600

G - from horizontal or vertical soil or drain pipes (2)

300

H - from corner of building

300

I

- from recess in building

300

L - from ground level or other treadable surface

2500

M - between two terminals set vertically

1500

N - between two terminals set horizontally

1000

O - from a surface facing without openings or terminals

2000

P - as above but with openings and terminals

3000

Fig. 11

Fig. 10

1) Terminals  below  a  practicable  balcony  must  be  located  in  such  a  way  that  the  total

path of the smoke from its outlet point from the terminal to its outlet point from the

external perimeter of the balcony, including the height of possible railings, is not less

than 2000 mm.

2) When  siting  terminals,  where  materials  that  may  be  subject  to  the  action  of  the  combu-

stion products  are present in the vicinity, e.g., eaves, gutters and downspouts painted or

made of plastic material, projecting timberwork, etc., distances of not less than 1500 mm

must be adopted, unless adequate shielding is provided to guard these materials.

Fig. 9

IMPORTANT: 
Each  additional  90° curve  installed  reduces  the
available length by 0.90 metres.
Each  additional  45° curve  installed  reduces  the
available length by 0.45 metres.

Summary of Contents for Format 25/60 BF

Page 1: ...e for the outlet of the products of the combustion is unobstructed and has been pro perly installed Make sure that any shutoff valves are open Make sure that the system is charged with water and is thoroughly vented Check that the circulating pump is not locked CAUTION Remember to release the pump coupled with the control panel if necessary to protect the electronic control card Purge the system b...

Page 2: ...ber natural draught FORMAT 25 60 BF 30 60 BF with electronic ignition and modulation room sealed forced draught Follow the instructions given in this manual for the correct installation and perfect func tioning of the appliance 73 1 DESCRIPTION OF THE BOILER 1 2 DIMENSIONS 1 2 1 25 60 OF model 600 135 D 865 225 110 495 782 460 25 125 80 70 70 70 107 E U C M R G 63 Fig 1 600 105 865 235 110 495 782...

Page 3: ...pansion vessel Water content Preloading pressure l bar 8 1 8 1 8 1 C H setting range C 40 80 40 80 40 80 D H W setting range C 10 60 10 60 10 60 D H W production Tank capacity l 60 60 60 Continuous D H W flow rate at t 30 C l h 684 684 774 Specific D H W flow rate EN 625 1 l min 14 5 14 5 16 1 D H W maximum water head bar 7 7 7 Recovery time from 25 C to 55 C min 4 30 4 30 4 D H W expansion vessel...

Page 4: ...onal 20 C H flow cock optional 21 D H W cock optional 22 D H W drain cock 23 D H W sensor SB 24 Limit stat 80 C 25 Magnesium anode 26 Fixing jig optional 27 Filling cock 28 Non return valve 1 5 MAIN COMPONENTS 17 16 15 14 13 12 11 1 2 3 4 5 6 7 8 9 10 Fig 3 KEY 1 Control panel 2 Gas valve 3 C H pump 4 Non return valve 5 Burner 6 Water pressure switch 7 Water gas exchanger 8 Limit stat 80 C 9 Fan B...

Page 5: ...l The kit code 8093900 is supplied comple te with mounting instructions 2 3 CONNECTING UP SYSTEM Before proceeding to connect up the boiler you are recommended to make the air cir culating in the piping in order to eliminate any foreign bodies that might be detrimen tal to the operating efficiency of the applian ce When making the hydraulic connections make sure that the dimensions indicated in fi...

Page 6: ...ro ducts and their possible condensates Follow a vertical path and not present any throttling throughout its entire length Be adequately insulated to prevent phe nomena of condensation or smokes coo ling in particular if located outside the building or in unheated ambiences Be set at an adequate distance from combustible or easily inflammable mate rial by means of an air gap or suitable insulating...

Page 7: ...ves necessary to provide for 78 KEY 1a b Coaxial duct kit code 8084802 2 Extension L 815 code 8084800 3 Vertical extension L 584 code 8086900 4 Supplementary 90 elbow code 8085600 TABLE1 Siting of terminal Appliances from 7 to 35 kW distances in mm A below openable window 600 B below ventilation opening 600 C below eaves 300 D below balcony 1 300 E from adjacent window 400 F from adjacent ventilat...

Page 8: ...is type of discharge The sector diaphragm that comes with the kit must be used as indicated in fig 15 according to the maximum load loss allowed in both ducts The complete range of the fittings neces sary for each type of installation is given in fig 16 79 KEY 1 Tile with articulated joint 2 Lead panel 3 Collar 4 Locking screw Fig 12 Fig 13 KEY 1 Vertical extension L 194 with take off point code 8...

Page 9: ... extension L 1000 code 8077306 4 Outlet terminal code 8089501 5 Int est ring kit code 8091500 6 Intake terminal code 8089500 7 45 elbow MF code 8077406 8 Condensation outlet L 135 code 8092800 9 Locking junction n 5 code 8092700 Sectors of diaphragm Total head loss to remove mm H2O Pa 0 0 2 0 19 6 2 2 3 19 6 29 4 4 3 4 29 4 39 2 6 4 5 39 2 49 0 Remove diaphragm 5 8 49 0 78 4 Sectors of diaphragm T...

Page 10: ...ling to earth the boiler 2 10 1 Control board fig 19 To access the electrical panel turn off the power supply and then remove the front panel and the two screws that anchor the control panel to the sides see point 4 6 The panel will move towards the bottom at an angle that will allow access to the com ponents To remove the protection 6 unscrew the fixing screws and with a screw driver press on the...

Page 11: ...AR Ignition detection electrode TRA Ignition transformer TS Safety stat 100 C Note The room stat or the chronothermostat must be connected to terminals 10 11 of the TA connector after having removed the bridge 1 2 6 7 5 8 3 4 Fig 19 KEY 1 Thermometer 2 Time programmer 3 Rotary switch 4 Electronic board 5 Earth faston 6 Instrument protection 7 Room stat cover 8 Room stat connector TA CONNECTOR SPAR...

Page 12: ...ulator PA Water pressure switch C Rotary switch SM Heating sensor blue SB D H W sensor TA Room stat EAR Ignition detection electrode TRA Ignition transformer TS Safety stat 100 C Note The room stat or the chro nothermostat must be connected to terminals 10 11 of the TA con nector after having removed the bridge CONNECTOR SPARE PART CODES J2 cod 6278622 J3 cod 6278621 J5 cod 6278625 J6 cod 6278620 ...

Page 13: ...immer in an anti clockwise direction The level of pressure of slow starting is able to be set during the first 3 seconds from the starting of the burner After having established the level of pressure at starting STEP according to the type of gas check that the heating gas pressure is still on the value previou sly set Connector METANO GPL 4 With the connector disconnected the boiler is ready to fu...

Page 14: ... that the cable of the electrode is interrupted or is not well fixed to the terminal of the ignition tran sformer The electrode is earthed or very worn and needs to be substituted The electronic board is faulty Due to a sudden fall in electricity the burner is immediately arrested once the electricity is restored the boiler will automatically restart 3 4 SMOKE SAFETY DEVICE 25 60 OF It is a safety...

Page 15: ...CUITO CON VALVOLE DI ZONA NOTA I relé vengono impiegati solo nel caso le valvole di zona siano prive di micro CIRCUITO CON POMPE DI ZONA CR1 CR Connettore TA 10 11 RL Cavo pompa impianto NOTA Sostituire la pompa impianto della caldaia con il tronchetto optional cod 8094001 Collegare il cavo della pompa impianto ad un relè di potenza RL L N TA1 CRL R1 P TA R P1 CR CR1 LEYENDA TA TA1 Zone room stat ...

Page 16: ...UM 4 2 1 Maximum and minimum pressure adjustment SIT 845 SIGMA fig 29 In order to carry out the setting of the maxi mum pressure proceed in the following way Connect the manometer to the down stream pressure plug of the gas valve In the BF versions instead connect the manometer as shown in fig 28 Remove the plastic cap of the modulator 1 Place the heating potentiometer knob on the maximum value St...

Page 17: ...nob set to the maximum the hot water tap turned on and the burner lit hold nut 3 locked in place and simulta neously turn nut 2 using a fixed ø 7 wrench to identify the minimum pres sure value shown in Table 4 turn the nut anti clockwise to reduce pressure or clockwise to increase it Turn the boiler on and off repeatedly while keeping the hot water tap turned on checking that pressure corresponds ...

Page 18: ...bracket Before refilling the system make sure that the expansion vessel is pre loaded to a pres sure of 0 8 1 bar 4 6 REMOVAL THE OUTER CASING For easy maintenance of the boiler it is pos sible to completely dismantle the casing fol lowing these simple instructions fig 33 Pull the front panel 5 fixed with pin clut ches forward Unscrew the two screws that fix the con trol panel to the shell Remove ...

Page 19: ...at 80 C and restarting at 70 C Before activating the chimney sweep func tion make sure that the radiator valves or eventual zone valves are open The test may be carried out also during hot water service functioning To do so it is enough after having activated the chimney sweep function to take some hot water from one or more cocks Even in this condition the boiler functions at the maximum temperat...

Page 20: ...y of water of the system Check the pre loading pressure of the expansion vessel Replace the expansion vessel if faulty The radiators do not heat up in winter The rotary switch is in the summer posi tion put it on the winter position The room stat is regulated too low or needs to be replaced as it is faulty The electrical connections of the room stat are not correct The principal burner burns badly...

Page 21: ...e system The operation of the boiler will be stop ped through the intervention of the ther mostat or timer TEMPERATURES ADJUSTMENT fig 2 The D H W temperature can be adju sted by turning the knob of the D H W potentiometer which has a range of between 40 to 60 C fig 2 The C H temperature can be adjusted by turning the knob of the C H potentiome ter which has a range of between 40 to 80 C To ensure...

Page 22: ... filling tap The blue coloured scale 1 shows the working field with heating system functioning Other faults fig 5 In the 25 60 BF 30 60 BF versions in case the green bicolour detector fan pressure switch deactive the boi ler and call the authorised technical staff for assistance In case the orange bico lour detector lights upt heating sensor SM failure deactive the boiler and call the authorised t...

Page 23: ...n memorized by pressing button P The display then changes to the further programme Repeat the same opera tions to set the successive programmes At the end of the programming Move the selector to the RUN position Cancelling one or more programmes fig 9 The programmed switch on time and switch off time must be cancelled for each individual programme by moving selector 2 to the P position Select the ...

Reviews: