6.15 System solutions
6.15.1 Quick boiler system type configuration
Parameter
“TSP 02 = Hydraulic configuration”
is used to quickly configure the type of system installed after the boiler. According to the
value set for this parameter, one of the following system solutions is selected:
–
Solution 1
= System with instant boiler with two direct multi-zone circuits
–
Solution 2
= System with instant boiler with a mixed multi-zone circuit
–
Solution 3
= System with instant boiler with a direct multi-zone circuit and a mixed multi-zone circuit
–
Solution 5
= System with instant boiler with a mixed multi-zone circuit and a remote hot water tank for preheating domestic hot water
–
Solution 6
= System with instant boiler with two direct multi-zone circuits and a remote hot water tank for preheating domestic hot
water
–
Solution 8
= System with instant boiler with one direct multi-zone circuit and a remote solar hot water tank for preheating domestic
hot water
–
Solution 9
= System with instant boiler with a mixed multi-zone circuit and a remote solar hot water tank for preheating domestic
hot water
–
Solution 10
= System with instant boiler with one direct multi-zone circuit, a mixed multi-zone circuit and a remote solar hot water
tank for preheating domestic hot water
–
Solution 12
= System with instant boiler with one direct multi-zone circuit and a hot/cold mode system
–
Solution 14
= System with instant boiler with one mixed multi-zone circuit, a fan coil and a hot/cold mode system
–
Solution 15
= System with instant boiler with one direct multi-zone circuit, a remote solar hot water tank for preheating domestic
hot water, and a hot/cold mode system
To set parameter
“TSP 02”
, follow the procedure described in the section “
Parameter setting and display
”.
m
CAUTION
In relation to the value set under parameter
“TSP 02”
, the following parameters take on the values shown in the table.
CHOOSEN HYDRUALIC SETUP
1
2
3
5
6
8
9
10
12
14
15
TSP
Description
Range
Parameter values
04
System connected to circuit 1
0 = high temperature
1 = low temperature
0
1
1
1
0
0
1
1
0
1
0
26
Configuring the DHW
0 = rapid
2 = hot water tank with sensor
0
0
0
0
0
0
0
0
0
0
0
30
Relay 1 function
2 = direct zone 1
2
2
2
2
2
2
2
2
12
12
12
31
Relay 2 function
1 = solar pump
7 = direct zone 2
8 = mix valve (position A)
7
8
8
8
7
1
8
8
8
8
1
32
Relay 3 function
0 = not used
1 = solar pump
8 = mix valve (position A)
9 = mix valve (position B)
0
9
9
9
0
0
9
9
9
9
17
33
Relay 4 function
0 = not used
1 = solar pump
7 = direct zone 2
9 = mix valve (position B)
0
0
7
0
0
0
1
1
11
11
11
34
Relay 5 function
0 = not used
7 = direct zone 2
0
0
0
0
0
0
0
7
7
2
0
36
Configuring SC input (PT1000)
0 = not used
1 = solar sensor
2 = system safety thermostat
0
2
2
2
0
1
1
1
0
2
1
37
Configuring input SAUX 2
0 = not used
3 = solar hot water tank sensor
4 = mix zone sensor
0
4
4
4
0
3
4
4
1
4
3
38
Configuring input SAUX 2
0 = not used
2 = preheated DHW inlet sensor
3 = solar hot water tank sensor
0
0
0
2
2
2
3
3
0
1
1
39
Configuring digital input 1
0 = not used
7 = system safety thermostat TSI (for
low temperatures)
0
0
0
0
0
0
7
7
6
6
6
40
Configuring digital input 2
0 = not used
0
0
0
0
0
0
0
0
7
7
7
45
Enabling preheating
0 = Disabled
1 = Enabled
0
0
0
1
1
1
0
0
0
0
0
46
Enabling solar function
0 = Disabled
1 = Enabled
0
0
0
0
0
1
1
1
0
0
0