User manual for universal counter with batching function SLIK-73
”diSAbL”
- programmable input is not active,
”inhibi”
- programmable input stops the counting,
”dirEct”
- active signal on the programmable input changes counting function
(counting direction) from
„A-B
”
to
„B-A
”
,
from
„A+B
”
to
„-(A+B)
”.
7.3.3.
“rESEt”
parameter
This parameter determines the counter zeroing (reset) sources, and can be set to one of
the values:
”ALL”
- this option enables both manual (using
[RESET
] button) and electronic reset.
”EL”
- this option enables external reset input
{ D }
. If an active signal is delivered to the
input
{ D }
the counter is zeroed, and the result stays zero ( or equal to offset) as
long as the signal on input
{ D }
is active. To made correct zeroing, input signal
{ D }
must be active at least by 1 ms. In this mode manual reset is disabled.
”mAn”
- manual reset only. This value enables only manual reset, which can be done by
pressing the [
RESET
] button on the front panel. This operation must to be approved
by [
ENTER
] button. After zeroing counter displays value equals to
”oFFSEt”
parameter. In this mode electronic reset is disabled.
”nonE”
- this option disables both manual and electronic reset.
Zeroing of the counter can be done via RS-485 interface (by presets of some
registers with value 0000h) independently of the
„rESEt”
parameter value. After
zeroing the counter, displayed value is equal to „
oFFSEt”
parameter. Remote
zeroing is available in all modes (
”ALL”
,
“EL”
,
“mAn”
,
„nonE”
).
7.3.4.
“ArESEt” parameter
This parameter enables the auto zeroing mode (
AUTORESET
function). If
AUTORESET
is active the counter is zeroed instantaneously after result reaches the relay R1 threshold
value (
SEtP 1
). After zeroing, counter value is equal to
“oFFSEt”
value. This parameter can be
set to:
“on”
-
AUTORESET
function is active,
“oFF”
-
AUTORESET
function is inactive.
Avoid of setting the „
oFFSEt
” parameter higher than autoreset threshold (relay R1
threshold) while
AUTORESET
function is active. In such case counter can work
improperly or can't work at all.