User manual - COUNTER SLB-94
7.
DEVICE PROGRAMMING
The device menu allow user to set all parameters connected to operation of
measurement input, control modes, critical situations behaviour, communication via RS-485
and access settings. The meaning of the particular parameters is described in paragraph
MENU DESCRIPTION
.
Some of the parameters can be accessed without menu entering (quick view mode).
After pressing
[v]
button, name of the threshold (e.g.
rELPr1
) and it's value will be displayed
on the display in alternating mode. Successive pressing of
[v]
button cause in displaying of
registers
mEmo1
÷
mEmo5
content. If
[v]
will be pressed in 5 sec again, the next
threshold or stored resets will be displayed, else the device comes back to the measurement
mode. If a thresholds values
free access
is enabled (see:
SECu menu
), user can change
the value of particular threshold pressing button
[ENTER]
(see:
PARAMETERS EDITION
).
If free access to profile changes is set, (see
Menu SECu
), then user can change profile
without knowing of main password.
If particular parameter has been changed and confirmed in quick view mode, its new
value is displayed in alternating mode with parameter name by few seconds. User
can check confirmed changes or switch viewed parameter pressing
[v]
button.
7.1.
PROGRAMMING MENU
To enter main menu (being in the measurement mode) operator must to press and hold
at least 2 sec.
[ESC/MENU]
button. If the user password is defined (see parameter
SEtCod
,
menu
SECU
), operator have to enter correct one before proceeding to menu options.
Entering of the passwords is similar to the edition of numeric parameters (see:
PARAMETERS
EDITION
)
,
however presently editing digit is showed only on the display, other digits are
replaced by - sign.
After entering of last digit of the password first menu position will be displayed (if the
password is correct) or warning
Error
in other case.
Pay attention when device parameters are being changed. If it is possible, turn off
controlled installation (machine).
Functions of the buttons while sub-menu and parameters choice:
Selection of sub-menu or parameter for editing. Name of selected item (sub-
menu or parameter) is displayed.
Operation of
[ENTER]
button depend on present menu position:
if the name of some sub-menu is displayed - enter this sub-menu; name
of the first parameter (or next level sub-menu) is displayed,
if the name of some parameter is displayed - enter the edition of this
parameter; present value of the parameter is displayed,
[ESC/MENU]
button allow user to exit present menu level and goes to upper
level menu (or measurement mode).
23
ENTER
MENU
ESC
i
!
Summary of Contents for SLB-94