User manual - COUNTER SLIK-N118
“oFF”
-
AUTORESET
function is inactive.
“on Pr1”
- counter is zeroed after result reaches relay R1
threshold.
After zeroing,
counter value is equal to
“oFFSEt”
value
“on 0”
-
counter is zeroed after result reaches value lower than 0
.
After zeroing,
counter value is equal to (
SEtP 1
+
“oFFSEt”
- 1)
value
While
AUTORESET
function is active some conditions must be fulfilled:
–
If
“ArESEt”=“on Pr1”
then
„
oFFSEt
” <
”SEtP 1”
–
If
“ArESEt”=“on 0”
then
„
oFFSEt
” +
”SEtP 1”
> 0
If these conditions will not be fulfilled then counter can work improperly or can't work
at all.
7.3.6.
“FiLtEr” parameter
This parameter enables the digital filter, which filters the contacts oscillations of switches
(mechanical detectors). Digital filter eliminates the counting errors when mechanical detectors
are used. This parameter can be set to values:
”OFF”
,
”10”
÷
”90”,
where its value express
the maximum passed frequency, if
”OFF”
is set the filter is disabled (see
DIGITAL FILTER
,
page 18).
7.3.7.
“PArUPd” parameter
This option allows to define when such parameters as
”muL”
,
”div”
,
”oFFSEt”
,
”Point”
and all relay control parameters will be updated if some changes are applied in device menu.
Possible values:
”immed”
- changed parameters are updated immediately,
”on rES”
- changed parameters will be updated after next reset
(manual or automatic) or after
next device power up.
7.3.8.
”PrESCA” menu
This menu contains parameter which configure the prescalling parameters (recalculations
of counted pulses). This menu allows the user to set individual prescalers, and to scale the
counter in desired units.
If
”PArUPd”
option is set to
”on rES”
mode, then change of parameters
”muL”
,
”div”
,
”oFFSEt”, ”Point”
and all parameters of the relays controlling (see
”rELAy”
menu), has no influence on current counting process. In this mode changed
parameters will be applied after reset (manual or automatic) or next device power
up. If
”PArUPd”
option is set to
”immEd”
mode, then all changes of these
parameters are applied immediately.
“muL”
- multiply coefficient , range -99999 do 999999, except 0,
“div”
- divide coefficient, range 1 do 999999, (this parameter defines the internal modulo
counter),
“oFFSEt”
- offset coefficient, range: -99999 do 999999 (constant value added to the result to
move the zero point of the current scale),
27