background image

User manual - COUNTER   SLIK-N118 

Register Write

Range

Register description

18h

Yes

see descr.

“div”

 parameter in 

“PrESCA”

 menu (input divider, high word);

content of main counter is incremented by 1 every  

n

 pulses (standard 

or quadrature cycles, or one-fourths of quadrature cycle) on inputs A 
and B, where 

n

  is content of precounter registers

19h

Yes

see descr.

“div”

 parameter in 

“PrESCA”

 menu (input divider, low word);

Cumulative value of registers 18h and 19h: from 1 to 999999

1Ah

6

Yes

see descr.

“oFFSEt”

 parameter in 

“PrESCA”

 menu (high word)

1Bh

6

Yes

see descr.

“oFFSEt”

 parameter in 

“PrESCA”

 menu (low word)

Cumulative value of registers 1Ah and 1Bh: from -99999 to 999999

1Ch

Yes

0÷5

Point

 ” parameter in “

Presca

” menu (decimal point position)

0

 - “

   0

”; 

1

 - “

  0.0

”; 

2

 - “

 0.00

”; 

3

 - “

0.000

”; 

4

 - “

0.0000

”; 

5

 - “

0.00000

20h

3

Yes

0 ÷ 199

Device address

21h

No

20C5h

Device identification code (ID)

22h

4

Yes

0 ÷ 7

“bAud”

 parameter in 

“rS-485” 

menu (baud rate);

0

 - 1200 baud; 

1

 - 2400 baud; 

2

 - 4800 baud; 

3

 - 9600 baud;

4

 - 19200 baud; 

- 38400 baud; 

6

 - 57600 baud; 

7

 - 115200 baud

23h

5

Yes

0 ÷ 1

“mbAccE”

 parameter in 

“rS-485” 

menu (permission to write registers 

via RS-485 interface); 

0

 - write denied ; 

1

 - write allowed

24h

Yes

see descr.

Parameters of “

SECU

” menu (binary format (0 - „

oFF

”, 1 - „

on

”):

bit 0

 - “

A rEL1

” parameter; 

bit 1

 - “

A rEL2

” parameter

bit 2

 - “

A rEL3

” parameter; 

bit 3

 - “

A rEL4

” parameter;

bit 4

 - “

A oFFS

” parameter

25h

Yes

0 ÷ 5

“rESP”

 parameter in 

“rS-485” 

menu (additional response delay);

0

 - no additional delay;  

1

 - ”

10c

” option; 

2

 - ”

20c

” option;

3

 - ”

50c

” option;  

4

 - ”

100c

” option;  

5

 - ”

200c

” option;

27h

Yes

0 ÷ 99

“mbtimE”

 parameter in 

“rS-485” 

menu (maximum delay between 

received frames); 

0

 - no delay checking;

÷ 

99 

- maximum delay expressed in seconds

2Dh

Yes

1 ÷ 8

briGHt

” parameter (display brightness);

- the lowest brightness; 

8

 -  the highest brightness

2Fh

Yes

0 ÷ 1

Edit

” parameter (numerical parameters edit mode);

0

 - „

dig

” mode; 

1  

- „

SLid

” mode

30h

6

Yes

see descr.

“SEtP 1” 

parameter in 

“rELAy 1”

 menu (high word).

31h

6

Yes

see descr.

“SEtP 1” 

parameter in 

“rELAy 1”

 menu (low word).

Cumulative value of registers 30h and 31h: from -99999 to 999999

32h

Yes

0÷3

modE 1

” parameter in  “

rELAy 1

” menu:

0

 - “

noAct

” mode; 

1

 - “

on

” mode; 

2

 - “

oFF

” mode; 

3

 - “

modbuS

” mode

33h

Yes

0÷999

“timE 1”

 parameter in 

“rELAy 1”

 menu (

the time period  of the relay 

active state

), expressed in tenth of seconds or tenth of minutes 

(depending on 

“unit”

 parameter); 

34h

Yes

0 ÷ 1

“unit 1”

 parameter in 

“rELAy 1” 

menu:

0

 - “

SEC

” option; 

1

 - “

min

” option

37

Summary of Contents for SLIK-N118

Page 1: ...ware v 8 10 or higher Input type pulse quadrature Batching function wall mounting case IP 67 Read the user s manual carefully before starting to use the unit or software Producer reserves the right to...

Page 2: ...arameters digit change mode 23 7 2 2 Numeric parameters slide change mode 23 7 2 3 Switch parameters LIST type 23 7 3 MENU DESCRIPTION 24 7 3 1 rELAy menu 24 7 3 2 Funct parameter 25 7 3 3 Pr inP para...

Page 3: ...ions GND input of device should be connected to PE wire The unit must be properly set up according to the application Incorrect configuration can cause defective operation which can lead to unit damag...

Page 4: ...t pulse inputs or single quadrature input Additional programmable input can change basic function of counting inputs addition or subtraction of pulses from inputs change the direction of counting or t...

Page 5: ...8N2 Modbus RTU not separated Baud rate 1200 bit s 115200 bit s Display LED 6 digit 13mm height red Data memory non volatile memory EEPROM type Protection level IP 67 Housing type Housing material Hou...

Page 6: ...of the unit must be conducted correctly and according to the local regulations Read the basic safety requirements on page 3 prior to starting the installation Ensure that the power supply network volt...

Page 7: ...red The fitter is responsible for executing the installation according to this manual local safety and EMC regulations The unit is not equipped with an internal fuse or power supply circuit breaker Be...

Page 8: ...nstallations appropriate measures assuring correct operation of the unit must be applied To avoid the unit of improper indications keep recommendations listed below Avoid common parallel leading of si...

Page 9: ...lamping connectors mounted inside the housing a b Figure 4 2 Recommended dimensions of cable stripping a for big connectors 1 to 6 b for small connectors 7 to 16 Figure 4 3 Method of connecting cables...

Page 10: ...le input D reset counter input COM common terminal 10 Uo R1 R2 GND DATA DATA RS 485 option option 24V 5 10 Imax 100 mA PE D COM B A C Power supply depending on version 3 4 1 2 14 15 16 5 6 12 11 10 9...

Page 11: ...ctromagnets motors etc it is required to use additional suppression circuit typically capacitor 47nF min 250VAC in series with 100R 5W resistor connected in parallel to relay terminals or better direc...

Page 12: ...ditional intermediary circuits sensor with NPN or PNP type output for outputs of push pull type kind of connection it has no matter a b Figure 4 9 An example of pulser connection a with common earth b...

Page 13: ...symbol should not be placed in municipal waste Please check local regulations for disposal and electronic products 5 FRONT PANEL DESCRIPTION Symbols and functions of push buttons Symbol used in the m...

Page 14: ...n are showed on the display next the data stored while power supply off are restored and device goes to the selected operation mode 6 1 MEASUREMENT MODE In the counting mode normal mode the device cou...

Page 15: ...the result and can be Hi if the result is higher than 999999 Lo if the result is lower than 99999 Any time the counter can be zeroed at by pressing of the RESET push button and the confirmation of the...

Page 16: ...see rELAy menu has no influence on current counting process In this mode changed parameters will be applied after reset manual or automatic or next device power up If PArUPd option is set to immEd mo...

Page 17: ...Figure 6 2 and proposed circuit diagram in Figure 6 3 More details of this example are described on page 34 Figure 6 2 Proposed system Figure 6 3 Proposed circuit diagram 17 COM START pouring Supply 2...

Page 18: ...sitions Approve entered value pressing and holding ENTER about 2 seconds Next step is selection of decimal point position parameter Point Counter displays SetPnt message and waits for acknowledge Pres...

Page 19: ...e periods t0 t1 depend on filtered frequency When the filter is turned off time periods t0 i t1 must be longer than 50 s see Figure 6 4 and maximum counted frequency is equal 10 kHz a b Figure 6 4 The...

Page 20: ...delay of relay reaction Figure 6 5 Principle of relay outputs operation Parameter SEtP defines threshold of relay trace a While normal operation of counter relay output can change its state to active...

Page 21: ...counter value after moment when counter has reached particular threshold If parameter timE is set to 0 than relay stays in active state periods tA tC tE tG as long as counter value is equal or higher...

Page 22: ...enu being in the measurement mode operator must to press and hold at least 2 sec ESC MENU button If the user password is defined see parameter SEtCod menu SECU operator have to enter correct one befor...

Page 23: ...essed increasing slow down for a moment only if v is pressed and held while button is still pressed the increasing slow down and will be kept on lower speed To decrease edited value press or press and...

Page 24: ...warning Error will be displayed and unit returns to measurement mode Due to problem with direct displaying of m letter it is exchanged with special sign Independently in user manual letter m is used t...

Page 25: ...s set to 0 0 and the AUTORESET function is active the counter will be zeroed but relays can stay inactive or will be activated on very short time because of delays If user wants to not use particular...

Page 26: ...enables both manual using RESET button and electronic reset EL this option enables external reset input D If an active signal is delivered to the input D the counter is zeroed and the result stays zer...

Page 27: ...meters as muL div oFFSEt Point and all relay control parameters will be updated if some changes are applied in device menu Possible values immed changed parameters are updated immediately on rES chang...

Page 28: ...gain To cancel this procedure press ESC MENU Detailed description of this procedure user can find in chapter AUTOPRESCALER on page 18 7 3 9 rS 485 menu This menu is connected with RS 485 interface and...

Page 29: ...resets connected with availability of other parameters SEtCod user password 4 digits number If this parameter is set at value 0000 user password is turned off If the user do not remember his password...

Page 30: ...for viewing edition depends on device version Figure 7 1 Operation of quick view while A oFFS oFF 30 Counting mode rELPr1 Value of threshold 1 ENTER MENU ESC edition of threshold value if allowed rEL...

Page 31: ...nge the edition mode of numerical parameters dig the change to by digit mode Slid slide change mode 7 3 13 dEFS parameter This setting allows to restore the factory settings of the device To get the a...

Page 32: ...MENU ESC rESEt ENTER MENU ESC ENTER ENTER MENU ESC SEtP 1 modE 1 unit 1 Parameter edition See next page ENTER MENU ESC ENTER ENTER MENU ESC muL div oFFSEt Point Parameter edition MENU ESC FiLtEr ArESE...

Page 33: ...ESC Parameter edition ENTER MENU ESC ENTER ENTER MENU ESC Addr bAud mbAccE mbtimE rESP See previous page MENU ESC SEt 4 digit special password entering 0 _ _ _ ENTER ENTER Default settings restoring M...

Page 34: ...6 2 6 3 Data flow meter 100 pulses L main valve flow valve 1 about 10 L sec additional valve flow valve 2 about 1 L sec measurement precision up to 0 1 L valve is open while relay are closed Settings...

Page 35: ...bits 1 or 2 stop bit 2 bits are send 1 and 2 bits are accepted when receive no parity control Baud rate selectable from 1200 to 115200 bits second Transmission protocol MODBUS RTU compatible The devic...

Page 36: ...of the counter 12h Yes 0 3 rESEt option main counter clearing mode 0 mode ALL 1 mode EL reset with D input and RS 485 interface 2 mode mAn reset with RESET button and RS 485 interface 3 mode nonE rese...

Page 37: ...registers via RS 485 interface 0 write denied 1 write allowed 24h Yes see descr Parameters of SECU menu binary format 0 oFF 1 on bit 0 A rEL1 parameter bit 1 A rEL2 parameter bit 2 A rEL3 parameter b...

Page 38: ...ace The unblocking of the writes is possible from menu level only 6 numbers written to holding registers of relays thresholds are interrelated with each other auto correction For example Preset to reg...

Page 39: ...s from 1 to 2 write to reg 20h ADDR FUNC REG H L DATA H L CRC L H 01 06 00 20 00 02 09 C1 DATA H 0 DATA L new device address 2 The answer the same as the message ADDR FUNC REG H L DATA H L CRC L H 01...

Page 40: ...057h 87 displayed value 87 6 Settings of the programmable inputs parameters Pr InP inhibi ADDR FUNC REG H L DATA H L CRC L H 01 06 00 11 00 01 18 0F The answer the same as the message ADDR FUNC REG H...

Page 41: ...hod PArUPd Parameters update method immEd 27 Settings of programmable input zeroing filtering and counting mode Pr inP Programmable input function diSAbL 26 rESEt Clearing zeroing source of main count...

Page 42: ...ges of relay R1 threshold without of the user password knowledge oFF 29 A rEL2 Permission to changes of relay R2 threshold without of the user password knowledge oFF 29 Display parameters briGHt Displ...

Page 43: ...User manual COUNTER SLIK N118 43...

Page 44: ...SIMEX Sp z o o ul Wielopole 11 80 556 Gda sk Poland tel 48 58 762 07 77 fax 48 58 762 07 70 http www simex pl e mail info simex pl...

Reviews: