4.4.1.1.
Alarms
This menu displays the notification of existing faults. After failure
elimination (see chapter 5), messages are deleted by selecting “Delete”. By
clicking on „History“ can be viewed up to 50 registered alarms.
4.4.1.2.
Detailed information
All temperature sensor readings, functioning of separate air handling unit
elements and other detailed information is available in this menu.
4.4.2.
Scheduling
Menu for planning of the air handling unit operation
according to the weekly program.
Three events can be set up for every week day. One
of three modes can be assigned to each event. Every
event has a timing, when the selected mode should
be active. The timing is set by tapping “Start” and
“Stop”. When the mode “Standby” is selected, the
fans are stopped and the unit is inactive until the
next event.
Example:
Monday:
07:30 – 11:00 Away mode is active
11:30 – 16:00 Home mode is active
16:00 – 17:00 Boost mode is active
The rest of the day the unit operates in Standby mode.
Every event start and end time is set from 0:00 to 24:00 h. The events should be set consistently
from the first one at the top of the window.