Function Type
Description
SSIG
Alarm signal, on until silenced
RSIG
Alarm signal, on until reset
TROUBLE
Trouble signal
SUPV
Supervisory signal
QALERT
SmartSync 2-wire horn/strobe control; horn on until silenced, strobe on until reset
WHEELOCK
Provides Wheelock strobe synch protocol when using only Wheelock strobes on panel, not to be mixed with
Simplex strobes
UTILITY
Utility signal, generic non-alarm
7
S4006-0001-8 8/2012
Common Fire Alarm Operations
Function Type
Relay Activates Upon
Relay Deactivates Upon
SRELAY
General Alarm
Silence
RRELAY
General Alarm
Reset
SUPV
Supervisory condition
Clear
TRBL
Trouble condition
Clear
Special Functions
Function Type
Description
UTILITY
Utility IDC in the same alarm group activates
PRIMARY
General alarm; relay is tied to Primary Elevator Recall contacts
ALTERN
General alarm; relay is tied to Alternate Elevator Recall contacts
DRESET
Relay provides 24 VDC power to 4-wire detectors; relay turns off for 5 seconds on System Reset
DHOLDER
Relay provides 24 VDC to larger door holder relay with separate power source; relay activates on general
alarm to remove power to door holder relay and close doors
Function
Details
Custom labels
Up to 20 characters per point; a built-in message library provides for commonly used words for easy front
panel programming
Message Library
For front panel label creation convenience, the following words can be selected as part of a custom label
( _designates a built-in space; typing the first letter of a word/number will select the closest word in
alphabetical/numerical sequence)
North
South
East
West
Front
Center
rear
5th
Flr_1
Flr_2
Flr_3
Flr_4
Flr_5
RM_
Basement
Floor
Garage
Hallway
HVAC_Room
Kitchen
Lobby
Office
Patient
upper
lower
main
first
2nd
3rd
4th
Boiler_RM
Classroom
Closet_
Corridor
Elect_RM
Elevator
Entrance
Restroom
Room
Stairway
Storeroom
Wing
Zone
History logs
Three separate logs: Alarm (100 entries), Supervisory (100 entries), and Trouble (300 entries); logs can be
queried separately, or as a combined log; logs can be downloaded for printing or archiving using the RS-232
service port
Autoprogram
Automatically scans system for installed option modules and configures panel programming accordingly;
modes are available to detect new modules only, recreate default programming and then add all modules
found
Alarm Groups
Up to 99 alarm groups are available, any point may be in up to 3 alarm groups; this allows NAC and relay
operation to be associated with IDC inputs according to local response requirements
WALKTEST
Allows one person to perform system testing; alarm or trouble tests are followed by automatic reset; the alarm
zone is sounded out by associated audible notification or the response is silently logged into the Alarm log
Manual Control
Allows selection of individual relays or NACs for system testing
Passcode
Protection
(4-digit number)
Level 1 = Acknowledge, Silence, System Reset, View logs, View point information, and Lamp Test
Level 2 = All Level 1 + Set Time/Date, Point Control, Enable/Disable points
Level 3 = All Level 2 + Clear logs, Clear verification tallies, Custom label editing, and WALKTEST
Level 4 = All Level 3 + Programming, Upload/Download; this is the Service access level
Relay Operation Modes
The following relay operations are selectable from either the front panel or the PC programmer.
Additional Programming Feature Details
NAC Operation Modes