Function Type 

Description 

SSIG  

Alarm signal, on until silenced 

RSIG  

Alarm signal, on until reset 

TROUBLE  

Trouble signal 

SUPV  

Supervisory signal 

QALERT  

SmartSync 2-wire horn/strobe control; horn on until silenced, strobe on until reset 

WHEELOCK  

Provides Wheelock strobe synch protocol when using only Wheelock strobes on panel, not to be mixed with 
Simplex strobes 

UTILITY  

Utility signal, generic non-alarm 

 

S4006-0001-8  8/2012

Common Fire Alarm Operations 

Function Type 

Relay Activates Upon 

Relay Deactivates Upon 

SRELAY

 

General Alarm 

 

Silence 

RRELAY

 

General Alarm 

 

Reset 

SUPV

 

Supervisory condition

 

Clear 

TRBL

 

Trouble condition

 

Clear 

Special Functions 

Function Type 

Description 

UTILITY

 

Utility IDC in the same alarm group activates 

PRIMARY

 

General alarm; relay is tied to Primary Elevator Recall contacts 

ALTERN

 

General alarm; relay is tied to Alternate Elevator Recall contacts 

DRESET

 

Relay provides 24 VDC power to 4-wire detectors; relay turns off for 5 seconds on System Reset 

DHOLDER

 

Relay provides 24 VDC to larger door holder relay with separate power source; relay activates on general 
alarm to remove power to door holder relay and close doors 

Function 

Details 

Custom labels 

 

Up to 20 characters per point; a built-in message library provides for commonly used words for easy front 
panel programming 

Message Library

 

For front panel label creation convenience, the following words can be selected as part of a custom label  
( _designates a built-in space; typing the first letter of a word/number will select the closest word in 
alphabetical/numerical sequence) 

North 
South 
East 
West 
Front

 

Center 
rear 
5th 
Flr_1 
Flr_2

 

Flr_3 
Flr_4 
Flr_5 
RM_

 

Basement 
Floor 
Garage 
Hallway 
HVAC_Room 
Kitchen

 

Lobby 
Office 
Patient
upper 
lower

 

main 
first 
2nd 
3rd 
4th

 

Boiler_RM 
Classroom 
Closet_ 
Corridor 
Elect_RM

 

Elevator 
Entrance 
Restroom 
Room 
Stairway

 

Storeroom 
Wing 
Zone 

History logs

 

Three separate logs: Alarm (100 entries), Supervisory (100 entries), and Trouble (300 entries); logs can be 
queried separately, or as a combined log; logs can be downloaded for printing or archiving using the RS-232 
service port 

Autoprogram

 

Automatically scans system for installed option modules and configures panel programming accordingly; 
modes are available to detect new modules only, recreate default programming and then add all modules 
found 

Alarm Groups

 

Up to 99 alarm groups are available, any point may be in up to 3 alarm groups; this allows NAC and relay 
operation to be associated with IDC inputs according to local response requirements 

WALKTEST

 

Allows one person to perform system testing; alarm or trouble tests are followed by automatic reset; the alarm 
zone is sounded out by associated audible notification or the response is silently logged into the Alarm log  

Manual Control

 

Allows selection of individual relays or NACs for system testing 

Passcode 
Protection 
(4-digit number)

 

Level 1 = Acknowledge, Silence, System Reset, View logs, View point information, and Lamp Test 
Level 2 = All Level 1 + Set Time/Date, Point Control, Enable/Disable points 
Level 3 = All Level 2 + Clear logs, Clear verification tallies, Custom label editing, and WALKTEST 
Level 4 = All Level 3 + Programming, Upload/Download; this is the Service access level 

 Relay Operation Modes  

 

The following relay operations are selectable from either the front panel or the PC programmer. 

 Additional Programming Feature Details  

 NAC Operation Modes  

Summary of Contents for 4006 Series

Page 1: ... cabinet UL listed to Standard 864 Available option modules Door mounted 24 LED annunciator standard on ULC models 3 A Expansion Power Supply with two on board 2 A NACs that operate the same as standard NACs ALARM ACK SUPV ACK TROUBLE ACK ALARM SILENCE SYSTEM RESET FIRE ALARM SYSTEM SUPERVISORY SYSTEM TROUBLE ALARM SILENCED AC POWER 4006 9102 Beige Standard Control Panel ALARM ACK SUPV ACK TROUBLE...

Page 2: ...tional auxiliary power output of 500 mA Output operation is the same as on the standard power supply Expansion IDC Module Provides 5 additional Class B IDCs with operation the same as the standard IDCs Expansion Relay Module Provides 10 programmable relays jumper selectable as N O or N C Contacts are rated 2 A 30 VDC Typical application is to track status of each IDC See page 7 for relay program o...

Page 3: ...arm list SUPV ACK acknowledges system supervisory conditions logs the acknowledge silences the operator panel and all annunciator tone alerts and steps through the active Supervisory list TROUBLE ACK acknowledges system troubles logs the acknowledge silences the operator panel and all annunciator tone alerts and steps through the active Trouble list FIVE NAVIGATION KEYS MENU selects the on screen ...

Page 4: ...t 500 mA maximum 24 VDC Standard Auxiliary Relay Outputs Relay 1 Programmable operation Contacts rated 2 A 30 VDC 0 35 power factor jumper selectable as N O or N C Relay 2 Trouble operation Wiring Connections for Above Circuits and AC Input Terminals rated for 18 AWG to 12 AWG 0 82 mm2 to 3 31 mm2 Option Module Ratings Class A IDC Adapter Module Five circuits per module rated same as circuits Ten ...

Page 5: ...n Alarm 4006 9121 4006 9122 Control panel with 24 LED Annunciator 148 mA 210 mA 60 mA per IDC in Alarm 4006 9801 Expansion Power Supply 50 mA 60 mA 4006 9802 Expansion IDC Module 50 mA 50 mA 60 mA per IDC in Alarm 4006 9803 Expansion Relay Module 0 mA 10 mA per energized relay 0 mA 10 mA per energized relay 4006 9804 Five Circuit IDC Class A Adapter 0 mA normal 10 mA per IDC in trouble 0 mA normal...

Page 6: ...TROUBLE VSMOKE Verified fire alarm the abnormal current limited state causes the alarm verification cycle to start a short is an immediate alarm Normal Current Limited Short Open NORMAL VERIFY FIRE TROUBLE STYLEC Style C fire monitor Normal Current Limited Short Open NORMAL FIRE TROUBLE TROUBLE LATSUPV Latching supervisory monitor supervisory latches until system is reset Normal Current Limited Sh...

Page 7: ...West Front Center rear 5th Flr_1 Flr_2 Flr_3 Flr_4 Flr_5 RM_ Basement Floor Garage Hallway HVAC_Room Kitchen Lobby Office Patient upper lower main first 2nd 3rd 4th Boiler_RM Classroom Closet_ Corridor Elect_RM Elevator Entrance Restroom Room Stairway Storeroom Wing Zone History logs Three separate logs Alarm 100 entries Supervisory 100 entries and Trouble 300 entries logs can be queried separatel...

Page 8: ...Main board Knockouts are located on top and sides Expansion Power Supply extends under IDC Expansion Module space Display Assembly Box depth 4 3 4 121 mm 16 406 mm Door thickness 5 8 16 mm NOTE For semi flush mounting cabinet must extend 1 1 2 38 mm minimum from wall surface Tyco Fire Protection Products Westminster MA 01441 0001 USA S4006 0001 8 8 2012 www simplexgrinnell com 2012 Tyco Fire Prote...

Reviews: