Electrical Ratings
Typical Operating Voltage Range
23 VRMS to 31 VRMS, Special Application (see below for 17 VRMS rating)
Supervisory Requirements
1 unit load
SLC Loading
Maximum of 63 addresses per SLC, 75 unit loads
Candela Setting
15 cd
30 cd
75 cd
110 cd
135 cd
185 cd
23 VRMS
Current Ratings, for typical design of
IDNAC Addressable SLCs (6 VRMS drop)
47 mA
57 mA
100 mA
132 mA
160 mA
208 mA
General Specifications
Temperature Range
32
to 122
F (0
to 50
C)
Humidity Range
10% to 93%, non-condensing @ 104° F (40° C)
IDNAC SLC Wiring Specifications
(refer to control panel installation instructions
for more information)
UTP, unshielded twisted pair recommended
Maximum wire length allowed with “T-Taps” for Class B wiring per SLC = 10,000 ft
(3048 m)
Maximum wire length to any appliance = 4000 ft (1219 m)
Maximum wiring resistance between compatible appliances = 26
Ω
Connections
Terminal blocks on mounting plate for 18 AWG to 12 AWG (0.82 mm
2
to
3.31 mm
2
); two wires per terminal for in/out wiring
Installation Instructions
579-1031
Notes:
Refer to compatibility table above for fire alarm control panel and power supply operation type.
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code
are trademarks of the National Fire Protection Association (NFPA).
Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA
S49VO-0001-3 8/2014
www.simplex-fire.com
© 2014 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Compatible Controller
Data Sheet
Reference
Controller Output
Available Strobe
Intensity
Appliance Voltage
Minimum
4100ES or 4100U with
TrueAlert Power Supply
S4100-0031
TrueAlert
Addressable SLC
15, 30, 75, and 110 cd
17 VRMS
4009 TPS, Remote
TrueAlert Power Supply
S4100-0037
TrueAlert Addressable
Controller (4009T)
S4009-0003
Electrical Ratings Reference for Retrofit Applications
Voltage Range 17 VRMS to 31 VRMS, Special Application
Candela Setting
15 cd
30 cd
75 cd
110 cd
17 VRMS
Current Ratings, use when
connected to TrueAlert Addressable SLCs per
above
62 mA
75 mA
133 mA
178 mA
Compatible Controller and additional
TrueAlert ES Appliances
Data Sheet
Reference
Controller
Output
IDNAC SLC
Output Voltage
Appliance Voltage
Design Reference
4100ES with EPS+ or EPS Power Supply
S4100-0100
IDNAC SLC
29 VRMS
(regulated)
23 VRMS
(with 6 VRMS drop)
4009 IDNAC Repeater
S4009-0004
TrueAlert ES Audible Only (Horns)
S49AO-0001
TrueAlert ES Audible/Visible
S49AV-0001
TrueAlert ES Weatherproof
Appliances
UL Listed S49WP-0001
ULC Listed S49WP-0002
TrueAlert ES Strobe Specifications
TrueAlert ES Strobe LEGACY Compatibility Reference
TrueAlert ES Appliance and IDNAC SLC Controller Compatibility Reference