background image

 

Mechanically installing the 2-Stage Station 

 
After all electrical connections have been made, install the 2-Stage Station IAM into a electrical box (not 
supplied) behind the Manual Station using Figure 4 as a reference.  Refer to the 2099-Series Non-Coded 
Fire Alarm Stations Installation and Operating Instructions (574-656) for information on other mounting 
configurations.  Mount the 2-Stage Station IAM to the electrical box as follows: 

 

For surface mounting, use a 2975-9178 red steel back box or a 2975-9022 aluminum back box.  Do not 
substitute a box with a depth less than 2-3/16 inches (5.55 centimeters). 
 
For semi-flush mounting, use a standard 4-inch (10.16 centimeters) square back box with a minimum depth 
of 2-1/8 inches (5.39 centimeters).  Fit the back box with a 3/4 inch (1.9 centimeters) deep single gang 
switch cover set flush (DO NOT RECESS) or protruding 1/16 inch (.16 centimeter) from the wall surface. 

 

1.  Install the 2-Stage Station IAM inside the electrical box in a position that allows the manual station 

adequate room to be mounted onto the electrical box.  The attached field wiring holds the 2-Stage 
Station IAM in place inside the electrical box. 

2.  Secure the manual station to the back box. 
 

 

 

Figure 4.  2-Stage Station IAM Back Box Installation 

4099-9801C IDNet

 2-Stage Station

 

IAM

 

Installation Instructions

 

 

 

574-179 

Rev. D 

574-179 

Rev. D 

 2000 Simplex Time Recorder Co., Westminster, MA 01441-0001 USA 

 2000 Simplex International Time Equipment Co., Ltd., Mississauga, Ontario L4V 1H3 Canada. 

All specifications and other information shown were current as of publication, and are subject to change without notice. 
IDNet

 is a trademark of Simplex Time Recorder Company. 

Suffix “C” following an 8-digit Product ID number denotes ULC-listed product

.

 

IAM Assembly 

Label 

DIP Switch 

(Under Re-sealable Label)

 

Terminal 

Front View

Rear View

LED 

Note:  

The LED flashes approximately once every three 

seconds to indicate valid communications with the FACP. 

 
Cautions and Warnings 
 
DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED.

  

Upon unpacking 

your Simplex product, inspect the contents of the carton for shipping damage.  If damage is apparent, 
immediately file a claim with the carrier and notify Simplex. 

 

ELECTRICAL HAZARD

 - 

Disconnect electrical power when making any internal adjustments or repairs.  

Servicing should be performed by qualified Simplex Representatives.

 

 

STATIC HAZARD -

 

Static electricity can damage components.  Ground yourself before opening or 

installing components. 

 

 

Introduction 

 

The 4099-9801C 2-Stage Station Individual Addressable Module (IAM) provides addressability to  
pre-signal type hardwired stations.  The four device states (NORMAL, OPEN, CURRENT-LIMITED  
and SHORT) are communicated to the 4010 Fire Alarm Control Panel (FACP) via the IDNet

 channel. 

Contacts for both General Alarm and Pre-Signal Alarm are supervised by the IAM.  The IDNet channel 
provides the communication link between the IAM and the 4010 FACP and powers the entire IAM circuitry.

 

 

Installation

 

 

2-Stage Station IAM installation consists of 
the following: 
 

• 

Setting the 2-Stage Station IAMs address 

• 

Making electrical connections to the 2-Stage 
Station IAM and to the IDNet channel 

• 

Mechanically installing the 2-Stage Station IAM 

 
 
 
 

 

 
 
Figure 1.  2-Stage Station IAM

 

Installation 

 
 

firealarmresources.com

Reviews: