background image

 

 

Making Electrical Connections to the 2-Stage Station IAM 

 

The IDNet channel connects to the 2-Stage Station IAM via terminals 1 and 2.  The manual station connects 
to the 2-Stage Station IAM via terminals 3 and 4.  Terminal connections are illustrated in Figure 3. 
 

CAUTION:  Do not loop wire under terminals.  Break wire runs to provide supervision.

 

 

6

5

4

3

2

1

IDNet

IDNet to

next device

1.8 K 1/2 W

733-984

(4081-9005)

2-STAGE
STATION

IAM

PRE-SIGNAL STATION

TYPE 2099-9107C, -9108C, -9759C

-

+

-

+

4.7 K 1/2 W

733-896

(4081-9003)

 

 

Notes:

 

 
1.  When connecting two wires to one terminal, position one wire on each side of the terminal screw.  

Maximum allowable run from 4010 FACP to farthest device not to exceed 2500 feet.  Maximum 
total wire (including all T-Taps) from 4010 FACP is 10000 feet.  IDNet wiring is supervised and 
power-limited. 

 
2.  Maximum wire length is 500 feet, #18 AWG. 
 
3.  Refer to Field Wiring Diagram 842-073 for further information.  Refer to 4010 panel label 526-444 

for appropriate revision of the Field Wiring Diagram to be used. 

 

Figure 3.  2-Stage Station IAM Connections 

 

 

3

 

2

 

 
Setting the 2-Stage Station IAMs Address

 

 
Each 2-Stage Station IAM has a unique address (1 through 250).  The address of the IAM is set by an eight 
position dip switch (Figure 1), DIP switch position 1 is the least significant bit (LSB) and position 8 is the most 
significant bit (MSB).  Set the IAMs address using Figure 2 as reference.  Use a small screwdriver or pen to set 
the switches.  The device address for the 2-Stage Station IAM should be written on the re-sealable label; this 
information provides an aid in troubleshooting the system. 

 

Note:

  DIP switch in “1” position is “ON” while DIP switch in “0” position is “OFF”. 

 

0000 1000 0100 1100 0010 1010 0110 1110 0001 1001 0101 1101 0011 1011 0111 1111

0000

0

16

32

48

64

80

96

112

128

144

160

176

192

208

224

240

1000

1

17

33

49

65

81

97

113

129

145

161

177

193

209

225

241

0100

2

18

34

50

66

82

98

114

130

146

162

178

194

210

226

242

1100

3

19

35

51

67

83

99

115

131

147

163

179

195

211

227

243

0010

4

20

36

52

68

84

100

116

132

148

164

180

196

212

228

244

1010

5

21

37

53

69

85

101

117

133

149

165

181

197

213

229

245

0110

6

22

38

54

70

86

102

118

134

150

166

182

198

214

230

246

1110

7

23

39

55

71

87

103

119

135

151

167

183

199

215

231

247

0001

8

24

40

56

72

88

104

120

136

152

168

184

200

216

232

248

1001

9

25

41

57

73

89

105

121

137

153

169

185

201

217

233

249

0101

10

26

42

58

74

90

106

122

138

154

170

186

202

218

234

250

1101

11

27

43

59

75

91

107

123

139

155

171

187

203

219

235

0011

12

28

44

60

76

92

108

124

140

156

172

188

204

220

236

1011

13

29

45

61

77

93

109

125

141

157

173

189

205

221

237

0111

14

30

46

62

78

94

110

126

142

158

174

190

206

222

238

15

31

47

63

79

95

111

127

143

159

175

191

207

223

239

LSB

MSB

1

2

3

4

5

6

7

8

1111

DIP SWITCHES 5 THRU 8

ON

OFF

1 = ON

0 = OFF

251
252
253
254
255

DIPSWITCH IS SHOWN SET AT ADDRESS 7.

 

 

Figure 2.  2-Stage Station IAM Address Chart 

 

Configure the 2-Stage Station IAM to the 4010 panel using the 

4010 Fire Alarm – PC Programmer Installation 

and Programming Instructions (574-187)

 and 

4010 Fire Alarm – Front Panel Installing, Operating, and 

Programming Instructions (574-052)

.  Refer to 4010 panel label 526-444 for appropriate revision of the 

instructions to be used. 

 

 