Making Electrical Connections to the 2-Stage Station IAM
The IDNet channel connects to the 2-Stage Station IAM via terminals 1 and 2. The manual station connects
to the 2-Stage Station IAM via terminals 3 and 4. Terminal connections are illustrated in Figure 3.
CAUTION: Do not loop wire under terminals. Break wire runs to provide supervision.
6
5
4
3
2
1
IDNet
IDNet to
next device
1.8 K 1/2 W
733-984
(4081-9005)
2-STAGE
STATION
IAM
PRE-SIGNAL STATION
TYPE 2099-9107C, -9108C, -9759C
-
+
-
+
4.7 K 1/2 W
733-896
(4081-9003)
Notes:
1. When connecting two wires to one terminal, position one wire on each side of the terminal screw.
Maximum allowable run from 4010 FACP to farthest device not to exceed 2500 feet. Maximum
total wire (including all T-Taps) from 4010 FACP is 10000 feet. IDNet wiring is supervised and
power-limited.
2. Maximum wire length is 500 feet, #18 AWG.
3. Refer to Field Wiring Diagram 842-073 for further information. Refer to 4010 panel label 526-444
for appropriate revision of the Field Wiring Diagram to be used.
Figure 3. 2-Stage Station IAM Connections
3
2
Setting the 2-Stage Station IAMs Address
Each 2-Stage Station IAM has a unique address (1 through 250). The address of the IAM is set by an eight
position dip switch (Figure 1), DIP switch position 1 is the least significant bit (LSB) and position 8 is the most
significant bit (MSB). Set the IAMs address using Figure 2 as reference. Use a small screwdriver or pen to set
the switches. The device address for the 2-Stage Station IAM should be written on the re-sealable label; this
information provides an aid in troubleshooting the system.
Note:
DIP switch in “1” position is “ON” while DIP switch in “0” position is “OFF”.
0000 1000 0100 1100 0010 1010 0110 1110 0001 1001 0101 1101 0011 1011 0111 1111
0000
0
16
32
48
64
80
96
112
128
144
160
176
192
208
224
240
1000
1
17
33
49
65
81
97
113
129
145
161
177
193
209
225
241
0100
2
18
34
50
66
82
98
114
130
146
162
178
194
210
226
242
1100
3
19
35
51
67
83
99
115
131
147
163
179
195
211
227
243
0010
4
20
36
52
68
84
100
116
132
148
164
180
196
212
228
244
1010
5
21
37
53
69
85
101
117
133
149
165
181
197
213
229
245
0110
6
22
38
54
70
86
102
118
134
150
166
182
198
214
230
246
1110
7
23
39
55
71
87
103
119
135
151
167
183
199
215
231
247
0001
8
24
40
56
72
88
104
120
136
152
168
184
200
216
232
248
1001
9
25
41
57
73
89
105
121
137
153
169
185
201
217
233
249
0101
10
26
42
58
74
90
106
122
138
154
170
186
202
218
234
250
1101
11
27
43
59
75
91
107
123
139
155
171
187
203
219
235
0011
12
28
44
60
76
92
108
124
140
156
172
188
204
220
236
1011
13
29
45
61
77
93
109
125
141
157
173
189
205
221
237
0111
14
30
46
62
78
94
110
126
142
158
174
190
206
222
238
15
31
47
63
79
95
111
127
143
159
175
191
207
223
239
LSB
MSB
1
2
3
4
5
6
7
8
1111
DIP SWITCHES 5 THRU 8
ON
OFF
1 = ON
0 = OFF
251
252
253
254
255
DIPSWITCH IS SHOWN SET AT ADDRESS 7.
Figure 2. 2-Stage Station IAM Address Chart
Configure the 2-Stage Station IAM to the 4010 panel using the
4010 Fire Alarm – PC Programmer Installation
and Programming Instructions (574-187)
and
4010 Fire Alarm – Front Panel Installing, Operating, and
Programming Instructions (574-052)
. Refer to 4010 panel label 526-444 for appropriate revision of the
instructions to be used.
firealarmresources.com