For FM80 MPPT Wiring information please refer to Outback FM80 installation manual
http://www.outbackpower.com/downloads/documents/charge_controllers/flexmax_6080/owner_manual.p
df
5.0
– Programming
5.1
– Depth of Discharge
The AccESS comes pre-programmed for 80% depth of discharge (DoD). This qualifies for the 10-year /
10,000 cycle Warranty on the PHI 3.8 Batteries.
To change the DoD to the 5,000 cycle Warranty or 3,500 cycle Warranty, modify the voltages in the Basic
Settings and Advanced Settings per the Programming section. Refer to the PHI 3.8 Battery Warranty.
If a firmware update is executed on the AccESS, please verify all PHI custom settings are still in place.
These settings can be found at the end of this manual in Section 7.0: Operating Parameters.
5.2
– Configuring the Outback Radian GS8048A
The Outback Radian is capable of many different modes of operation via configurable settings. These
settings can be modified to support the function the owner would like to achieve with the AccESS unit. To
configure the AccESS, please refer to
. Excerpts from this manual
pertaining to the inverter’s different modes of operation are outlined in Appendix A.
The Outback
Owner’s Guide contains information and procedures necessary for configuring, operating,
maintaining, and troubleshooting the Outback Radian Inverter/Charger. The guide is intended for anyone
who needs to operate, configure, and troubleshoot the inverter. Certain configuration tasks should only be
performed by qualified personnel.
Proper system configuration involves setting the
System Information
in the MATE3s’s
Settings
>
System
menu to include a basic profile of the system:
System Information
Parameter
Type
Off Grid, Grid Tied, or Backup
Nominal voltage of the battery bank
48V
Array wattage (PV)
Set to system’s PV array wattage
Battery Amp-hours
300 Ah (75Ah per PHI 3.8)
Generator kW rating
Set to generator specs, if applicable
Generator type
Max Inverter kW
8 kW
Max Charger kW
8 kW
5.3
– Operating Parameters Per Warranty
Although the PHI 3.8 Batteries within the AccESS unit are capable of performing at very high rates and
depths of discharge within a very wide temperature range, in order to achieve extended life cycles and to
comply with the Warranty, the operating parameters, indicated in Tables 3.0 and 4.0 below, must be
adhered to.
The parameters shown in Table 3.0 below must be applied based on desired Warranty/cycle
life. The AccESS comes pre-programmed for 80% depth of discharge.