Although lead acid batteries are typically wired using battery-to-battery interconnecting cables, SimpliPhi
asks that PHI Batteries NOT be wired in this way.
All wire lengths from each PHI Battery to common busbars or plates should be identical in length and gauge
in order to balance the load across (all) PHI Batteries in the installation.
CAUTION: Identical wire lengths and identical wire gauges from each PHI Battery in a PHI
Battery bank is a critical feature of parallel power storage systems that must be adhered to
throughout all parallel wiring instructions. Failure to properly wire the PHI Batteries in parallel
will Void the Warranty.
Figure 5.0 depicts four PHI Batteries wired in Parallel. This configuration requires 8 identical lengths of
identical gauge copper wire.
Figure 5.0 - Four PHI Batteries in Parallel