REV020620
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 |
| 32 |
Appendix B
–
PHI Battery Bank Sizing Guide
PHI 3.8 -
51.2V
nom
PHI 2.9 -
51.2V
nom
PHI 3.8 -
25.6V
nom
PHI 2.9 -
25.6V
nom
PHI 1.4 -
25.6V
nom
PHI 730 -
25.6V
nom
PHI 1.4 -
12.8V
nom
PHI 730 -
12.8V
nom
Max Continuous
Dis/charge Rate
(ADC)
37.5
28.5
45
45
28.5
14
40
28.5
Max Continuous
Dis/charge Rate
(kW DC)
1.920
1.459
1.152
1.152
0.7296
0.3584
0.512
0.3648
48V Sizing for Maximum Instantaneous Discharge (Load Rate)
Inverter Make / Model
Inverter Power
Rating (kW AC)
Inverter
Efficiency
Load Rate
(kW DC)
PHI 3.8 - 51.2V
nom
Minimum Battery
Quantity
PHI 2.9 -51.2V
nom
Minimum Battery
Quantity
Magnum MS 4448
4.4
94%
4.7
3
4
Magnum MS 4048
4
94%
4.3
3
3
OutBack Radian 8048A
8
93%
8.6
5
6
OutBack Radian 4048A
4
93%
4.3
3
3
OutBack SkyBox
5
97%
5.2
3
4
OutBack VFXR 3648A
3.6
93%
3.9
3
3
OutBack FXR 3048A
3
93%
3.2
2
3
OutBack GVFX 3648 (discontinued)
3.6
93%
3.9
3
3
OutBack GTFX 3048 (discontinued)
3
93%
3.2
2
3
Schneider XW Pro
6.8
93%
7.3
4
6
Schneider XW+ 6848
6.8
92.5%
7.4
4
6
Schneider XW+ 5548
5.5
93%
5.9
4
5
Schneider SW 4048
4
94%
4.3
3
3
Selectronic SP PRO SPMC 481-AU
5
96%
5.2
3
4
Selectronic SP PRO SPMC 482-AU
7.5
96%
7.8
5
6
Sol-Ark-8K
8
96.5%
8.3
5
6
Sol-Ark-12K
12
96%
12.5
7
9
Victron Quattro 48/3000/35
3
94%
3.2
2
3
Victron Quattro 48/5000/70
5
95%
5.3
3
4
Victron Quattro 48/10000/140
10
96%
10.4
6
8
Victron Quattro 48/15000/200 (230 VAC)
15
96%
15.6
9
11