background image

REV020620

 

 
 
 
 

SimpliPhi Power, Inc.  |  3100 Camino Del Sol  |  Oxnard, CA 93030, USA  |  (805) 640-6700  |  

info@simpliphipower.com

|  

SimpliPhiPower.com

 

|  11  |          

                                                    

 

 

discharge.  Over-discharging the PHI Batteries will destroy them and Void the Warranty. 

In the case where the invert

er’s AC Power Output rating exceeds the connected loads’ actual power draw 

(i.e. the inverter is rated at 5 kW but all loads amount to 3 kW of maximum instantaneous power draw), 
SimpliPhi still expects that the proper additional precautions be made to ensure that the PHI Battery bank is 
not over-discharged. This typically involves the installation of an additional overcurrent protection device 
between the PHI Battery bank and the inverter to ensure that the PHI Battery bank does not discharge 
beyond its maximum instantaneous power rating.  Failure to do so will destroy the PHI batteries and Void 
the Warranty. 

 

𝑃𝐻𝐼 𝐵𝑎𝑡𝑡𝑒𝑟𝑦 𝐵𝑎𝑛𝑘 𝑀𝐴𝑋 𝑐𝑜𝑛𝑡𝑖𝑛𝑢𝑜𝑢𝑠 𝑑𝑖𝑠𝑐ℎ𝑎𝑟𝑔𝑒 𝑟𝑎𝑡𝑒

= (𝐵𝑎𝑡𝑡𝑒𝑟𝑦 𝑞𝑢𝑎𝑛𝑡𝑖𝑡𝑦) × (𝑀𝐴𝑋 𝐶𝑜𝑛𝑡𝑖𝑛𝑢𝑜𝑢𝑠 𝐷𝑖𝑠𝑐ℎ𝑎𝑟𝑔𝑒 𝑅𝑎𝑡𝑒 𝑝𝑒𝑟 𝐵𝑎𝑡𝑡𝑒𝑟𝑦)

 

 

Example: Two PHI 3.8 kWh-51.2V

nominal

 batteries must be installed with an additional 75 ADC-rated 

breaker between the battery bank and the inverter. 

 

(𝑃𝐻𝐼 𝐵𝑎𝑡𝑡𝑒𝑟𝑦 𝐵𝑎𝑛𝑘 𝑀𝐴𝑋 𝑐𝑜𝑛𝑡𝑖𝑛𝑢𝑜𝑢𝑠 𝑑𝑖𝑠𝑐ℎ𝑎𝑟𝑔𝑒 𝑟𝑎𝑡𝑒) = 2 × 37.5𝐴𝐷𝐶 = 75𝐴𝐷𝐶

 

 

3.2.2 

 Sizing for Maximum Instantaneous Charge Rate (DC Coupled)

 

In a DC Coupled system, the solar PV array output can be mitigated using charge controllers. However, 

reducing the solar array’s power output using charge controller programming implies that the PV array’s 

output is also reduced for the entire remainder of the system, including the solar power available for 
powering loads and f

or exporting to the grid. Furthermore, greatly reducing the PV array’s output via the 

charge controllers effectively wastes the solar PV array’s power and puts strain o

n the charge controllers. 

Calculate the minimum quantity of PHI Batteries needed to prevent over-charge from the solar PV array by 

considering both the solar array size and the charge controller’s potential output. Whichever value is 

less 

should be used to 

size the PHI Battery Bank. If the solar array’s maximum potential current output is les

than the paired charge controller’s Output Amps rating, then the solar array’s maximum potential current 

output can be used to size the PHI Battery bank. If the charg

e controller’s Amp rating is less than the solar 

array’s maximum potential current output, then the charge controller’s rating is used to size the PHI Battery 

bank. 

Divide the system’s potential charging current by the MAX Continuous Charge Rate per PHI Ba

ttery (found 

in Table 1.0 or on the relevant battery’s specification sheet) to calculate

 the minimum quantity of PHI 

Batteries needed to ensure that the solar PV array does not over-charge the battery bank. 

Example A: Three PHI 3.8 kWh-51.2V

nominal

 batteries (used in a 48-Volt system) must be paired with a 

4,500-Watt solar PV array wired to an 80 Amp-rated charge controller. In this case, the 80-Amp charge 
controller is used to determine the minimum PHI Battery quantity needed to prevent over-charging from 
the solar PV. 

𝑊𝑎𝑡𝑡𝑠 = 𝐴𝑚𝑝𝑠 × 𝑉𝑜𝑙𝑡𝑠

 

4,500 𝑊𝑎𝑡𝑡 𝑆𝑜𝑙𝑎𝑟 𝑃𝑉 𝑎𝑟𝑟𝑎𝑦 = 𝐴𝑚𝑝𝑠 × 48 𝑉𝑜𝑙𝑡𝑠

 

4,500 𝑊𝑎𝑡𝑡𝑠

48 𝑉𝑜𝑙𝑡𝑠

= 𝟗𝟑. 𝟕𝟓 𝐴𝑚𝑝𝑠 = 𝑀𝐴𝑋 𝑝𝑜𝑡𝑒𝑛𝑡𝑖𝑎𝑙 𝑠𝑜𝑙𝑎𝑟 𝑃𝑉 𝑎𝑟𝑟𝑎𝑦 𝑜𝑢𝑡𝑝𝑢𝑡

 

Summary of Contents for PHI 1.4 Series

Page 1: ...SIMPLIPHI POWER INC REV020620...

Page 2: ...reduces operating temperature constraints toxic coolants and the risk of thermal runaway Safe lithium ferrous phosphate LFP No cobalt No toxic hazards SimpliPhi s battery technology utilizes the indu...

Page 3: ...4 2 Environmental Considerations 14 4 2 1 Charging at Temperatures Below Freezing 14 4 2 2 Explosive Gas Precautions 14 4 2 3 Anti Corrosion Protection 14 4 3 Mounting Hardware 14 4 4 Dimensions and...

Page 4: ...hi Technical Support at 805 640 6700 x 1 regarding the compatibility of any equipment not explicitly listed in the Integration Guides section of the Product Documentation web page https simpliphipower...

Page 5: ...impliPhi with any questions We are committed to working with you and your installation team to achieve a safe reliable storage system that will provide years of maintenance free service that is covere...

Page 6: ...breaker This breaker increases safety during shipping and installations and allows the battery to effectively be turned OFF or ON The breaker works in conjunction with the battery s built in BMS and c...

Page 7: ...4 Amps DC 358 4 W DC 28 5 Amps DC 364 8 W DC DC Voltage Range1 24 to 28 VDC 48 to 56 VDC 24 to 28 VDC 48 to 56 VDC 24 to 28 VDC 12 to 14 VDC 24 to 28 VDC 12 to 14 VDC Depth of Discharge1 up to 100 Ope...

Page 8: ...n page 4 of this Manual 2 2 Response to Emergency Situations As with any battery if the PHI Battery s cells are severely damaged due to physical abuse reverse polarity high voltage unmitigated current...

Page 9: ...y bank but also all other power related sizing parameters as outlined in Sections 3 2 1 3 2 2 or 3 2 3 and 3 2 4 Failure to do so will Void the Warranty CAUTION PHI Battery bank sizing not in accordan...

Page 10: ...ient to use the PHI 3 8 kWh 51 2Vnominal battery with 1 92 kW of maximum continuous discharge versus the PHI 3 8 kWh 25 6Vnominal battery with 1 15 kW of continuous discharge The same advantages apply...

Page 11: ...ystem including the solar power available for powering loads and for exporting to the grid Furthermore greatly reducing the PV array s output via the charge controllers effectively wastes the solar PV...

Page 12: ...arge assuming that the charge controllers full current output rating is utilized Failing to do so will destroy the PHI batteries and Void the Warranty 3 2 3 Sizing for Maximum Instantaneous Charge Rat...

Page 13: ...id the Warranty Note that this quantity of PHI Batteries is the minimum requirement to prevent over discharge and over charge from an instantaneous power perspective The system may need more PHI Batte...

Page 14: ...y confined space containing vented batteries or flammable chemicals such as natural gas NG liquid petroleum gas LPG or gasoline Benzine Petrol Do not install in a confined space with machinery powered...

Page 15: ...200 pounds each of downward pressure along the bracket s outer edge During this test a deflection of approximately 30 thousandths of an inch was measured Bracket sets are designed to hold one PHI 3 8...

Page 16: ...3 0 Specifications PHI 2 9 Battery PHI 2 9 Battery w Mounting Bracket PHI 2 9 Battery PHI 2 9 Battery w Mounting Bracket Width 11 25 13 7 15 5 with mounting flanges Height 12 75 including 1 75 termin...

Page 17: ...to form a water resistant seal around the base of the molded inserts and terminal connections CAUTION Do not attempt to loosen the large brass nut at the base of the terminals doing so will damage the...

Page 18: ...age Capacity and total available Amperage is increased incrementally with the number of units wired in Parallel For example two PHI 3 8 kWh 51 2Vnominal 75Ah Batteries wired in parallel are rated at a...

Page 19: ...n length and gauge in order to balance the load across all PHI Batteries in the installation CAUTION Identical wire lengths and identical wire gauges from each PHI Battery in a PHI Battery bank is a c...

Page 20: ...to include the 3 8 lugs that fit on the PHI Battery s threaded studs Determine the cable length for the PHI Battery terminal farthest from the common busbar or plate first Additional cabling or slack...

Page 21: ...s a washer should be placed between the current carrying terminal and the cable lug or interconnecting busbar Doing so will Void the Warranty CAUTION Spark may be present when connecting wires to PHI...

Page 22: ...ached to the batteries terminals Interconnecting busbars for paralleling either two SKU BB 2 or three SKU BB 3 PHI batteries with threaded studs are available from SimpliPhi at an additional cost CAUT...

Page 23: ...miliar with general electrical safety precautions and specific regional code requirements IfthePHIBattery s voltagehasdropped during anextended periodinstorage toa voltage belowtheinverter sminimum st...

Page 24: ...at the PHI Battery terminals will destroy the PHI batteries and Void the Warranty 7 ConfirmallloadsareturnedOFF Disconnecttheinverter sACOutputbreakerorturnoffthebreakeratthetop ofyourloads breakerpan...

Page 25: ...tery bank composed of two PHI 3 5 batteries and one PHI 3 8 battery has a total energy storage capacity for system sizing calculations of 10 5 kWh for the bank 3 X 3 5 kWh 10 5 kWh total In addition t...

Page 26: ...t 71 5 Amps DC 5 0 Programming 5 1 Operating Parameters per Warranty To maintain PHI Battery health and to comply with the Warranty adhere to the operating parameters outlined in Tables 4 0 and 5 0 be...

Page 27: ...d above the battery rests at approximately 13 3V 26 7V 53 3V Refer to Table 6 0 below for a complete Battery Voltage versus State of Charge SOC gauge Table 6 0 Battery Voltage VS State of Charge SOC a...

Page 28: ...r to turn on To measure a single battery s voltage within a battery bank only the battery being measured has its built in breaker in the ON I position all other batteries in the bank must have their b...

Page 29: ...cals contained in Lithium Ferro Phosphate cells electrolyte do not electrolyze to any appreciable extent within the PHI Battery s operating voltage range In contrast lead acid batteries which contain...

Page 30: ...Batteries are maintenance free as long as all the Installation Manual Integration Guidelines and Warranty requirements are adhered to B 2 4 Life Cycles PHI Batteries are designed for thousands of cycl...

Page 31: ...unlike NMC NCA LCO NiMH NiCad or Lead Acid types of batteries including AGM The PHI Batteries contain the least amount of toxic metals and are the most eco friendly of all common battery types Lithium...

Page 32: ...mum Battery Quantity PHI 2 9 51 2Vnom Minimum Battery Quantity Magnum MS 4448 4 4 94 4 7 3 4 Magnum MS 4048 4 94 4 3 3 3 OutBack Radian 8048A 8 93 8 6 5 6 OutBack Radian 4048A 4 93 4 3 3 3 OutBack Sky...

Page 33: ...3 3 4 8 Samlex EVO 4024 4 94 4 3 4 4 6 12 Samlex EVO 2224 2 2 93 2 4 3 3 4 7 Schneider SW 4024 4 92 4 3 4 4 6 13 Schneider SW 2524 2 5 91 5 2 7 3 3 4 8 Victron Quattro 24 5000 120 5 94 5 3 5 5 8 15 V...

Page 34: ...MidNite Solar Classic 200 24V system 78 2 2 3 6 MidNite Solar Classic 200 12V system 79 3 MidNite Solar Classic 250 48V system 55 2 2 2 2 2 4 2 2 MidNite Solar Classic 250 24V system 62 2 2 3 5 MidNi...

Page 35: ...Max Output ADC PHI 3 8 51 2V PHI 2 9 51 2V PHI 3 8 25 6V PHI 2 9 25 6V PHI 1 4 25 6V PHI 730 25 6V PHI 1 4 12 8V PHI 730 12 8V Sol Ark 12K includes dual MPPTs 185 5 7 5 5 7 14 5 7 Victron SmartSolar...

Page 36: ...ommended and available online for purchase at this link The 48V 30A for LiFePO4 LiFeYPO4 58 8V GMS charger from GWL Power is recommended and available for online purchase at this link The Smart Charge...

Page 37: ...ry Equipment 12V 24V 48V 12v 24V 48V 12V 24V 48V Absorb High Cut Off Voltage V 3 13 6 27 2 54 4 13 6 27 2 54 4 14 28 56 Absorb Time 2 Hours Absorb End Amps 2 of the PHI Battery bank s total Ah capacit...

Reviews: