Additional cabling or slack that remains with the shorter distance runs can be coiled  
and secured with Zip Ties. 

 
Wiring Methods: 

1.  For 1 to 8 units:  Wire directly to inverter & charge controller equipment. 
2.  For 6 to 20 units: Use a DC combiner or panelboard. 
3.  For 20+ units: Connect the PHI 2.7 Battery terminals directly to a common bus. 

4.2 – Torque Values 

For the DC terminals on the PHI 2.7 Battery, torque to 160 in-lb (13.3 ft-lb). 

 

4.3 – Battery Wiring Methods 

4.3.1 – Connecting Cable Leads to the PHI 2.7 Batteries 

 

Before connecting the cable leads to the PHI 2.7 Battery, please be aware of the following 
information concerning power cabling, considerations for power cable terminations as well as 
installation environments. 

 

CAUTION: 

Spark may be present when connecting wires to PHI 2.7 terminals. 

 

CAUTION: 

Do not reverse polarity. It will void the Warranty. Use a volt meter to check polarity before 

connecting terminals. A brief small spark is often present when connecting the second of two leads 
to a PHI 2.7 Battery. Example: If the Positive has been connected, a small spark will likely be 
present when connecting the Negative lead. 

This is a normal occurrence

. Complete all 

connections in a clean, ventilated, well-lit area. To avoid any spark or electrical event when 
connecting the terminal leads on the PHI 2.7 Battery, turn the circuit breaker “ON/OFF” switch to 
“OFF” position.

 

 

Power Cabling for the PHI 2.7 Battery is not included. Your qualified installer or application  
specifications will determine the wire gauge for your system. Connection to the PHI 2.7 Battery 
terminal should only be made using appropriately sized ring terminals for your PHI 2.7 Battery 
cables. 
High amperage rated ring terminals can be found for these and other common wire gauges.  Your 
installer can source these. 

Considerations for Power Cable Terminations 

Please factor in the below information for power cable terminations: 

 

PHI 2.7 Battery Mounting Stud Size: 3/8’’ 

 

Power Cable Wire Gauge: Generally, anywhere from 6 AWG to 2/0 AWG or larger  

Protection from the Environment 

Anticorrosive compounds or epoxies are occasionally used in harsh or marine climate 
installations. Please contact your Electrician or Qualified Installer to determine if this is advisable, 
and if so, what solution best suits your application. 

4.3.2 – Final Connection of the Installation

 

Final installation and operation guidelines will be dictated by your Electrician and Installer based 
on the overall properties of and procedures for the equipment in your installation and any code 
requirements that apply to your region. SimpliPhi Power, Inc. technicians and sales staff are 
available to provide any additional information on the PHI 2.7 Battery as needed. Please contact 
SimpliPhi Power for any technical support at your convenience. SimpliPhi Power, Inc. is 
committed to providing safe, reliable energy storage and management that is maintenance free, 
non-toxic and long-lasting. This commitment extends to our customers, valued installers, 

Summary of Contents for PHI 2.7

Page 1: ...7 Battery Optimized Energy Storage Management for Residential Commercial Applications Utilizing Efficient Safe Non Toxic Energy Dense Lithium Ferrous Phosphate LFP Chemistry SIMPLIPHI POWER INC REV02...

Page 2: ...SimpliPhi helps you manage your power as a personal resource Anytime Anywhere SimpliPhi energy storage optimizes integration of any power generation source solar wind generator on or off grid and pro...

Page 3: ...nstallation 7 3 1 PHI 2 7 Battery Performance Parameters and Sizing Calculations 8 3 2 System Sizing for Your Installation 8 3 3 Mounting Hardware 8 3 4 Battery Weight 8 3 5 Battery Wall Mount Bracket...

Page 4: ...en approval Failure to adhere to installation protocol will void the Warranty 7 Verify polarity at all connections with a standard volt meter before 1 energizing the system and 2 turning the PHI 2 7 c...

Page 5: ...ndard volt meter before 1 energizing the system and 2 turning the PHI 2 7 circuit breaker ON OFF switch to the ON position Reverse polarity at the battery terminals will void the Warranty and destroy...

Page 6: ...ues specified are exceeded the protective circuitry will shut down the flow of electricity to from the PHI 2 7 Batteries In some cases this will result in the need to re initialize an inverter charger...

Page 7: ...ration of renewable and traditional sources of energy in conjunction with or independent of the grid net zero peak shaving emergency back up portable and mobile 2 2 Specifications Please review Table...

Page 8: ...nual balancing processes CAUTION Do not combine PHI 2 7 Batteries with other brands or chemistries This will void the Warranty CAUTION Do not mix PHI 2 7 Batteries from different installations clients...

Page 9: ...without the SimpliPhi Power Mounting Bracket as well as a diagram that provides guidance on Mounting Bracket assembly Table 2 0 Specifications PHI 2 7 Battery v PHI 2 7 Battery w Mounting Bracket PHI...

Page 10: ...installer should understand this and must adhere to the industry standard and published electrical guidelines For all installations Maintain identical wire lengths from each PHI 2 7 Battery terminal...

Page 11: ...ecial attention should be paid for parallel installations Correct wiring is essential to insure optimum performance and system longevity All wire runs should utilize identical wiring gauge and identic...

Page 12: ...rcuit breaker ON OFF switch to OFF position Power Cabling for the PHI 2 7 Battery is not included Your qualified installer or application specifications will determine the wire gauge for your system C...

Page 13: ...main online and in standby for at least 24 hours 10 at top of charge and 10 at bottom of charge This allows a system to stay online until at least one full day of sun can recharge the PHI 2 7 Battery...

Page 14: ...all connections before energizing system Reverse polarity at the PHI 2 7 Battery terminals will void the Warranty and destroy the PHI 2 7 Batteries CAUTION Before commissioning the system the appropr...

Page 15: ...a Manufactured Article and is not subject to the regulations of the Hazardous Products Act A 3 Hazards Identification Table 5 0 Common Chemical Name CAS Percent of Content Classification Hazard Label...

Page 16: ...use severe irritation to the eye Medical Conditions Aggravated by Exposure Not Available A 4 First Aid Measures Skin Contact Wash affected area with lukewarm water for at least 30 minutes If irritatio...

Page 17: ...ric acid because PHI 2 7 Batteries do not have caustic electrolytes Thermal runaway is not an issue with PHI products due to the basic nature of Lithium Ferro Phosphate cell chemistry utilized in all...

Page 18: ...er cardboard and recyclable plastic Lithium Ferrous Phosphate LFP materials can also be recycled through established battery centers if desired B 2 6 Lithium Ferrous Phosphate Batteries and the Enviro...

Reviews: