Table 4.0 – Operating Limitations
Notes / Operating Limitations for
PHI 2.7 Batteries
1
Limitations by Model
24V
48V
Continuous Discharge Rate (A)
45
26
Continuous Charge Rate (A)
45
26
2
60A Discharge/Charge Rate (10 minutes maximum)
3
Levels are typically @ 25
°
C and may need adjusting at temperature extremes.
4
When performing rapid deep charge/discharge cycles, the PHI 2.7 Battery should be
allowed to "rest" 15 mins in between.
CAUTION:
Verify polarity at all connections before energizing system. Reverse polarity at the PHI 2.7 Battery
terminals will void the Warranty and destroy the PHI 2.7 Batteries.
CAUTION:
Before commissioning the system, the appropriate controller and inverter settings must be
programmed per the manufacturer’s recommendations. Consult the manufacturer’s manuals and/or
access technical support (Schneider, SMA, Magnum, Outback, etc.). The following Charge Controller
Integration tables are for general reference only.
CAUTION:
All SimpliPhi Power products are designed to work exclusively in parallel. Never connect in
series to achieve higher voltages
.