3.1 – PHI 2.7 Battery Performance Parameters and Sizing    

         Calculations 

PHI 2.7 Batteries are designed to operate at a continuous C/2 rate across a large operating temperature 
range, as seen in Table 1.0 above. 

The PHI 2.7 Batteries need no increase in sizing and no special 

compensations when determining the size of the energy storage and management system under the 
circumstances and conditions seen in Table 1.0 above. 

See specific inverter manufacturer program 

settings for optimizing system integration. 

 

PHI 2.7 Batteries do not need to be de-rated unless running continuously at more than 90% capacity, at 
temperatures below 0 degrees Celsius, or above 49 degrees Celsius. To achieve higher, warrantied cycles 
of 10,000+, the PHI 2.7  Batteries are typically operated  at 80% maximum Depth of Discharge. Please 
contact SimpliPhi Power Technical Support if alternative settings are desired. Please also refer to operating 
temperatures and inverter settings in Programming section. 

3.2 – System Sizing for Your Installation 

The number of PHI 2.7 Batteries should be specified in terms of total storage capacity before the initial 
installation based on the goals and objectives of the project. All PHI 2.7 Batteries are balanced during 
final production and testing stages. Following proper wiring guidelines ensures that a system will not 
require any manual balancing processes.  
 

CAUTION: 

Do not combine PHI 2.7 Batteries with other brands or chemistries. This will void the Warranty. 

 

CAUTION: 

Do not mix PHI 2.7 Batteries from different installations, clients or job sites. This will void the 

Warranty.

 

 

3.3 – Mounting Hardware 

The SimpliPhi Power Mounting Brackets (sold separately) are designed to secure one PHI 2.7 Battery to 
a load bearing surface. SimpliPhi Power PHI 2.7 Batteries can be mounted in practically any orientation 
(terminals up or on any side), with no impact to the performance of the PHI 2.7 Battery. Do not install 
them upside down. The brackets can be mounted directly to a wall or can be arranged on strut channels 
for ease of positioning (mounting hardware not included). A qualified installer should be familiar with 
accomplishing this with the appropriate load bearing requirements.  

 

For ease of measuring, arranging and mounting your PHI 2.7 Battery array, a drawing of the PHI 2.7 
Battery Mounting Brackets with dimensions is provided (

Figure 2.0

). 

 
During mechanical testing, individual PHI 2.7 Mounting Brackets were exposed to 200 pounds each of 
downward pressure along the bracket’s outer edge. During this test, a deflection of approximately 30 
thousandths of an inch was measured. Bracket sets are designed to hold one PHI 2.7 Module, with a 
weight of ~60 pounds. 

3.4 – Battery Weight 

PHI 2.7 Batteries weigh 60.5 pounds. The Wall Mount Bracket Assemblies weigh 9 Pounds (with bolts). 
The SimpliPhi Power Mounting Brackets should be mounted into load bearing beams, studs or solid 
materials with appropriate fasteners. SimpliPhi Power is not liable for damage caused by inappropriate 
installation mounting of brackets. 
 
 
 
 

Summary of Contents for PHI 2.7

Page 1: ...7 Battery Optimized Energy Storage Management for Residential Commercial Applications Utilizing Efficient Safe Non Toxic Energy Dense Lithium Ferrous Phosphate LFP Chemistry SIMPLIPHI POWER INC REV02...

Page 2: ...SimpliPhi helps you manage your power as a personal resource Anytime Anywhere SimpliPhi energy storage optimizes integration of any power generation source solar wind generator on or off grid and pro...

Page 3: ...nstallation 7 3 1 PHI 2 7 Battery Performance Parameters and Sizing Calculations 8 3 2 System Sizing for Your Installation 8 3 3 Mounting Hardware 8 3 4 Battery Weight 8 3 5 Battery Wall Mount Bracket...

Page 4: ...en approval Failure to adhere to installation protocol will void the Warranty 7 Verify polarity at all connections with a standard volt meter before 1 energizing the system and 2 turning the PHI 2 7 c...

Page 5: ...ndard volt meter before 1 energizing the system and 2 turning the PHI 2 7 circuit breaker ON OFF switch to the ON position Reverse polarity at the battery terminals will void the Warranty and destroy...

Page 6: ...ues specified are exceeded the protective circuitry will shut down the flow of electricity to from the PHI 2 7 Batteries In some cases this will result in the need to re initialize an inverter charger...

Page 7: ...ration of renewable and traditional sources of energy in conjunction with or independent of the grid net zero peak shaving emergency back up portable and mobile 2 2 Specifications Please review Table...

Page 8: ...nual balancing processes CAUTION Do not combine PHI 2 7 Batteries with other brands or chemistries This will void the Warranty CAUTION Do not mix PHI 2 7 Batteries from different installations clients...

Page 9: ...without the SimpliPhi Power Mounting Bracket as well as a diagram that provides guidance on Mounting Bracket assembly Table 2 0 Specifications PHI 2 7 Battery v PHI 2 7 Battery w Mounting Bracket PHI...

Page 10: ...installer should understand this and must adhere to the industry standard and published electrical guidelines For all installations Maintain identical wire lengths from each PHI 2 7 Battery terminal...

Page 11: ...ecial attention should be paid for parallel installations Correct wiring is essential to insure optimum performance and system longevity All wire runs should utilize identical wiring gauge and identic...

Page 12: ...rcuit breaker ON OFF switch to OFF position Power Cabling for the PHI 2 7 Battery is not included Your qualified installer or application specifications will determine the wire gauge for your system C...

Page 13: ...main online and in standby for at least 24 hours 10 at top of charge and 10 at bottom of charge This allows a system to stay online until at least one full day of sun can recharge the PHI 2 7 Battery...

Page 14: ...all connections before energizing system Reverse polarity at the PHI 2 7 Battery terminals will void the Warranty and destroy the PHI 2 7 Batteries CAUTION Before commissioning the system the appropr...

Page 15: ...a Manufactured Article and is not subject to the regulations of the Hazardous Products Act A 3 Hazards Identification Table 5 0 Common Chemical Name CAS Percent of Content Classification Hazard Label...

Page 16: ...use severe irritation to the eye Medical Conditions Aggravated by Exposure Not Available A 4 First Aid Measures Skin Contact Wash affected area with lukewarm water for at least 30 minutes If irritatio...

Page 17: ...ric acid because PHI 2 7 Batteries do not have caustic electrolytes Thermal runaway is not an issue with PHI products due to the basic nature of Lithium Ferro Phosphate cell chemistry utilized in all...

Page 18: ...er cardboard and recyclable plastic Lithium Ferrous Phosphate LFP materials can also be recycled through established battery centers if desired B 2 6 Lithium Ferrous Phosphate Batteries and the Enviro...

Reviews: