REV020918
SimpliPhi Power, Inc. | 420 Bryant Circle | Ojai, CA 93023, USA | (805) 640-6700 | info@simpliphipower.com |
SimpliPhiPower.com
| 14 |
Table 4.0 – Operating Limitations
Notes / Operating Limitations for
PHI 3.5 Batteries
1
Limitations by Model
24V
48V
Continuous Discharge Rate (A)
60
34
Continuous Charge Rate (A)
45
34
2
60A Discharge/Charge Rate (10 minutes maximum)
3
Levels are typically @ 25
°
C and may need adjusting at temperature extremes.
4
When performing rapid deep charge/discharge cycles, the battery should be allowed to "rest" 15 mins in between.
CAUTION:
Verify polarity at all connections before energizing system. Reverse polarity at the battery terminals
will void the Warranty and destroy the batteries.
CAUTION:
Before commissioning the system the appropriate controller and inverter settings must be
programmed per the manufacturer’s recommendations. Consult the manufacturer’s manuals and/or
access technical support (Schneider, SMA, Magnum, Outback, etc.). The following Charge Controller
Integration tables are for general reference only.
CAUTION:
All SimpliPhi Power products are designed to work exclusively in parallel. Never connect in
series to achieve higher voltages
.
Section 5.0 – PHI 3.5 Battery Safety & Green
Attributes, Certifications
This section covers the PHI 3.5 battery safety attributes and certifications, such as the lack of thermal
runaway and off-gassing, UN DOT certification and UL compliance. It also covers the PHI 3.5 battery’s
green attributes – from products to materials to disposal, as well as relevant environmental and ecological
considerations.
Section 5.1 – Safety Attributes and Certifications
5.1.1 – Intrinsically Safe Operation and Installation
The PHI Lithium Ferrous Phosphate (LFP) battery cell component is made with an intrinsically
safe cathode material (iron phosphate). This creates a strong molecular bond, which withstands
extreme conditions, prolongs cycle life, and maintains integrity with little or no maintenance over
extended periods of time. There is virtually no danger of Thermal Runaway, as there may be with
Lead Acid, NiCd, and Lithium Cobalt type batteries. No venting or cooling is required. No
precautions or special structural considerations are necessary when installing PHI 3.5 Batteries.