SECTION 6 – ACCIDENTAL RELEASE MEASURES

The material contained within the batteries or cells is only expelled under abusive conditions. Use a shovel 
and cover battery with sand or vermiculite, place in an approved container and dispose in accordance with 
section 13.

SECTION 7 – HANDLING AND STORAGE

Handling: Do not expose battery or cell to extreme temperatures or fire. Do not disassemble, crush or 
puncture battery.

Storage: Insulate positive and negative terminals to avoid short circuit. Store in a cool and well - ventilated 
area and avoid direct sunlight. Elevated temperatures can result in reduced battery life.

SECTION 8 – EXPOSURE CONTROLS AND PERSONAL PROTECTION

Respiratory Protection: Not necessary under normal use. In case of battery or cell rupture, use a self- 
contained full-face respiratory mask.

Eye Protection: Not necessary under normal use. Wear safety goggles if handling a ruptured or leaking cell 
or battery pack.

Hand Protection: Not necessary under normal use. Wear rubber gloves when if handling a ruptured or 
leaking cell or battery pack.

Skin Protection: Not necessary under normal use. Wear rubber apron and rubber gloves if handling a 
ruptured or leaking cell or battery pack.

SECTION 9 – PHYSICAL AND CHEMICAL PROPERTIES

Physical State

 Solid 

Odor Type

Odorless

Appearance

Battery 

Odor Threshold

Not Applicable

pH

Not Applicable

Evaporative Rate

(n-Butyl Acetate = 1) Not Applicable

Relative Density

Not Applicable

Auto Ignition Temperature(C°)

Not Applicable

Boiling Point

Not Applicable

Flammability Limits (%)

Not Applicable

Melting Point

Not Applicable

Vapor Pressure

(mm Hg @ 20 C°) Not Applicable

Viscosity

Not Applicable

Vapor Density

(Air = 1) Not Applicable

Oxidizing Properties

Not Applicable

Solubility in Water

Insoluble

Flash Point and Method (C°)

Not Applicable

Water/ Oil distribution coefficient

Not Applicable

Summary of Contents for PHI2.6

Page 1: ...ON MANUAL PHI2 6 SMART TECH BATTERY Optimized Energy Storage Management for Residential Commercial Applications Utilizing Efficient Safe Non Toxic Energy Dense Lithium Ferrous Phosphate LFP Chemistry...

Page 2: ...ncy SimpliPhi storage technology eliminates operating temperature constraints toxic coolants and the risk of thermal runaway and fire SimpliPhi s clean storage technology utilizes the industry s most...

Page 3: ...g for Your Installation System Configuration Basic Concepts Increasing Storage Capacity Sample Installation Requirement Mounting Hardware Weight Page 13 Key Points Page 14 Connecting PHI2 6 Smart Tech...

Page 4: ...ify polarity at all connections with a standard volt meter before 1 energizing the system and 2 turning the PHI2 6 80 Amp breaker ON OFF switch to the ON position Reverse polarity at the battery termi...

Page 5: ...ement system BMS This assures the highest grade and quality longest cycle life greatest efficiency and freedom from material impurities toxicity and hazardous risk Each PHI2 6 Smart Tech Battery conta...

Page 6: ...mining the size of the energy storage and management system under the following circumstances and conditions See specific inverter manufacturer program settings for optimizing system integration Note...

Page 7: ...THER BRANDS OR CHEMISTRIES DO NOT MIX PHI SMART TECH BATTERIES FROM DIFFERENT INSTALLATIONS CLIENTS OR JOB SITES System Configuration Basic Concepts Safe and reliable installation requires trained and...

Page 8: ...re to the industry standard and published electrical guidelines For All Installations Maintain identical wire lengths from each PHI2 6 Smart Tech Battery terminal to the common bus Use identical wire...

Page 9: ...allel arrangements whether they are 24V or 48V See Figure 1 2 Simple Parallel Arrangements Storage Capacity and total available Amperage is increased by Parallel arrangements The following illustratio...

Page 10: ...nfiguration will require 8 identical lengths of appropriately heavy gauge copper wire Alternate wiring schemes are also effective The Cross Diagonal method is perhaps less common but has been evaluate...

Page 11: ...e PHI2 6 Mounting Brackets with dimensions is provided page 12 During mechanical testing individual PHI2 6 Mounting Brackets were exposed to 200 pounds each of downward pressure along the bracket s ou...

Page 12: ...pliPhi Power Inc 420 Bryant Circle Ojai CA 93023 USA 1 805 640 6700 info simpliphipower com SimpliPhiPower com 12 Figure 1 5 PHI2 6 KWH 24V and 48V Battery Modules with Integrated Battery Management B...

Page 13: ...ge sources The PHI2 6 Smart Tech Battery alone will not protect the batteries from these extreme electrical phenomena 4 GRID TIED SYSTEMS Once the PHI2 6 Smart Tech Batteries have been installed turn...

Page 14: ...washer and nut The right hand stud resides in a red colored high temperature molded insert This connection is for the positive lead The left hand stud resides in a black colored high temperature inse...

Page 15: ...osive compounds or epoxies are occasionally used in harsh or marine climate installations Please contact your Electrician or Qualified Installer to determine if this is advisable and if so what soluti...

Page 16: ...ERATING PARAMETERS PER WARRANTY Although SimpliPhi batteries are capable of performing at very high rates and depths of discharge within a very wide temperature range in order to achieve extended life...

Page 17: ...oltage Off Off Recharge Volts 23 2V 24 5V Bulk Voltage 27V 27V Absorb Voltage 28 8V 28V Float Voltage If used on a daily weekly or monthly use case then Off Self Discharge is 1 per month Schneider Equ...

Page 18: ...A Equalized Voltage Off Off Recharge Volts 46 4V 48 9V Bulk Voltage 55V 55V Absorb Voltage 57 6V 56V Float Voltage If used on a daily weekly or monthly use case then Off Self Discharge is 1 per month...

Page 19: ...4V 102 4 Amp Hours 2621Wh 48V 51 2 Amp Hours Cell Voltage Parameters Max Charge Voltage 3 65V per Cell 28 8 Max Charge Voltage for 8s 24V 57 6 Max Charge Voltage for 16s 48V Load Disconnect 2 25V per...

Page 20: ...al runaway is not an issue with PHI products due to the basic nature of Lithium Ferro Phosphate cell chemistry utilized in all our power storage products PHI2 6 Smart Tech Battery Control and Protecti...

Page 21: ...80 percent or more of their initial capacity Disposal PHI products are non hazardous may be disposed of without damage to the ecosystem and returned to the earth while easily recombining with the ele...

Page 22: ...iMH NiCad or Lead Acid types of batteries including AGM The PHI2 6 Smart Tech Batteries contain the least amount of toxic metals and are the most eco friendly of all common battery types Lithium easil...

Page 23: ...DS should be retained and available for employees and other users of this product Canada This is not a controlled product under WHMIS This product meets the definition of a Manufactured Article and is...

Page 24: ...Contact between the battery and eye will not cause any harm Eye contact with the contents of a ruptured battery can cause severe irritation to the eye Medical Conditions Aggravated by Exposure Not Av...

Page 25: ...re use a self contained full face respiratory mask Eye Protection Not necessary under normal use Wear safety goggles if handling a ruptured or leaking cell or battery pack Hand Protection Not necessar...

Page 26: ...abused and the enclosure is compromised Neurological Effects Not Applicable Sensitization Not Applicable Teratogenicity Not Applicable Reproductive Toxicity Not Applicable Mutagenicity Genetic Effects...

Page 27: ...liPhi Support for additional documentation if required The battery cells contain no metallic lithium and pass the tests defined in UN model regulation section 38 3 Do not expose to temperatures over 4...

Page 28: ...SimpliPhi Power Inc 420 Bryant Circle Ojai CA 93023 USA 1 805 640 6700 info simpliphipower com SimpliPhiPower com 28 Power On Your Terms...

Reviews: