REV110619
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com |
SimpliPhiPower.com
| 20 |
AccESS Sol-Ark-12K-22.8 kWh model
:
1. Mount the AccESS unit on level concrete.
2.
Make sure all PHI battery module circuit breakers are in the OFF position.
Prepare the
battery modules for installation by removing all plastic terminal covers, 11/16” stainless steel hex
nuts and
3/8” lock washers from the batteries’ terminals and set aside.
CAUTION:
Do not attempt to loosen the large brass nuts at the base of the battery terminals.
3. Place three PHI 3.8 batteries in the bottom of the cabinet and arrange three PHI 3.8 batteries on
the AccESS’s internal shelf. Orient the modules so that the battery terminals point toward the
AccESS door, with the negative posts nearest the bottom of the AccESS enclosure. Refer to
Figure 11.0 below:
Figure 11.0
– Six-PHI Battery Orientation within the Sol-Ark-12K-22.8 kWh
4.
Attach interconnecting busbars onto the batteries’ terminals. Each positive busbar parallels one
set of three batteries (positive to positive to positive), and each negative busbar parallels one set
of three batteries (negative to negative to negative).
5.
Secure the busbars to the batteries’ terminals using a 11/16” wrench socket to tighten the 3/8”
lock washers and 11/16” stainless steel hex nuts (originally included on the batteries). Tighten the
nuts to 160 in-lbs.