| 36 |
Table 2.0
– Sol-Ark AccESS Battery Settings
System Setup > Battery
Setup
80% DoD
(10k cycle warranty)
90% DoD
(5k cycle warranty)
100% DoD
(3.5k cycle warranty)
> Batt Tab
Batt Capacity
1
75 Ah per PHI 3.8 battery
Max A Charge
1,2
37.5 ADC per PHI 3.8 battery (20 ADC per battery for reduced stress)
80-
150 ADC for 4 x PHI 3.8’s / 120-185 ADC for 6 x PHI 3.8’s*
*The Sol-
Ark’s maximum PV charging output is limited to 185 ADC.
Max A Discharge
1
37.5 ADC per PHI 3.8 battery
TEMPCO
0 mv/C/Cell (disabled)
Use Batt V Charged
do not check this box
Use Batt % Charged
check this box
No Battery
do not check this box
BMS Lithium Batt
do not check this box
Activate Battery
do not check this box
> Charge Tab
80% DoD
90% DoD
100% DoD
Start V
Use Start % instead of Start V when using
Batt % Charged instead of Batt V Charged (in the Batt tab)
Start %
3
21%
11%
1%
A
1,4
37.5 ADC per PHI 3.8 battery (20 ADC per battery for reduced stress)
80-
150 ADC for 4 x PHI 3.8’s / 100 ADC for 6 x PHI 3.8’s*
*The Sol-
Ark’s maximum AC power charging output is limited to 100 ADC.
Gen Charge / Grid Charge
5
Check the Gen Charge box when a generator is connected to the Gen Input breaker.
Check the Grid Charge box when a generator is connected to the Grid Input breaker,
or when a grid connection is utilized to charge the batteries.
Float V
54 V
Absorption V
6
54.4 V
54.4 V
56 V
Equalization V
7
56 V
30 days
2 hours
> Discharge Tab
80% DoD
(recommended)
90% DoD
100% DoD
Shutdown
20% (50.2 V)
10% (49.5 V)
0% (48 V)
Low Batt
30% (50.5 V)
20% (50.2 V)
10% (49.5 V)
Restart
97% (52 V)
97% (52 V)
97% (52 V)