CA Rule 21
check this box for compliance with CA Rule 21
UL 1741SA
check this box for compliance with HECO Rule 14H and/or PREPA
GEN connect to Grid input
check this box when a generator is wired to the Grid Input
> Grid Input Tab
Grid Frequency
select 50 Hz or 60 Hz
Grid Type
select 120/240V split phase (North America),
or contact SimpliPhi to special-order 220V single phase or 120/208V 3 phase
Protect Param
leave as default values when UL 1741 & IEEE 1547 are enabled
frequency values may change when a generator is wired to the Grid Input
> FreqVolt tab
refer to the Sol-Ark Manual for Puerto Rico or Kauai-specific settings
AC Coupled
In an AC Coupled system setup, the grid-tie inverter(s) output
– string or micro-inverters – is wired to the
Sol-
Ark’s Generator Input (40A double-pole breaker) and the
For Micro inverter input
box in the
Smart
Load
tab of the
Battery Setup
menu must be checked:
Figure 22.0
– Smart Load Tab in Batt Setup Menu
The Sol-Ark-8K is limited to a maximum of 7 kW of AC Coupled solar PV, and the Sol-Ark-12K is limited to
7.6 kW of AC Coupled solar.
AC Coupled systems can operate in Grid Sell / Grid-Tied with Battery Backup, Limited to Home, Limited to
Load, or Time of Use Selling modes.
Grid Sell / Grid-Tied with Battery Backup
A net energy metering agreement with the utility company is required in order to sell energy from the solar
PV array to the grid. In this mode, the Sol-Ark prioritizes powering all loads (on both the essential loads
sub-panel and the main house breaker panel) from solar PV first (if available), then (2) grid, (3) generator,
and (4) batteries. In the event of a grid failure, the batteries will power the essential loads sub-panel only.
Take care to size the battery bank accordingly; in a grid failure scenario, the Sol-Ark does not limit the
batteries’ maximum current output. The maximum power draw (kW) on the essential loads sub-panel should