Table 3.0
– Sol-Ark AccESS Battery Settings
A
B
C
D
E
# of Parallel
Batteries
DC Current Limit
ADC X VDC (48)
WDC X Discharge Efficiency (95%)
MAX Battery Output
(WAC)
4
150 ADC
7,200 WDC
6,840 WAC
6,840 WAC
6
225 ADC
10,800 WDC
10,260 WAC
10,260 WAC
Note:
Sol-
Ark’s Manual shows these
power (W)
parameters programmed to
1,000 Watts × PHI Battery
Quantity
. While there is no harm in using this approximation, the greater values outlined in the tables
above may be used.
5.3
– Configuring the Sol-Ark to a Specific Application
The Sol-Ark is capable of many different modes of operation via configurable settings (more than one
mode can be used simultaneously). This section of the Manual will outline the system programming and
setup basics for common use cases. However, refer also to the Sol-Ark Manual for all installation
requirements relevant to the application at hand.
Table 4.0
– Sol-Ark AccESS Grid Settings
System Setup > Grid Setup
80% DoD
(10k cycle warranty)
90% DoD
(5k cycle warranty)
100% DoD
(3.5k cycle warranty)
> Limiter Tab
Grid Sell
check this box when exporting solar PV power to the grid
(Net Energy Metering agreement required)
set the numerical value to the maximum number of exporting Watts
Limited Power to Home
check this box when powering both the essential loads sub-panel and
the main house breaker panel using solar and/or battery,
without exporting energy to the grid (limiter sensors required)
Limited power to load
check this box when powering the essential loads sub-panel using solar and/or
battery
Time of Use Selling
check this box when discharging the batteries during set times
(either the Grid Sell or Limited Power to Home box must also be checked)
Time
sets the time at which the batteries discharge to power both the essential loads sub-
panel and the main house breaker panel (limiter sensors required)
power (W)
sets the maximum amount of power discharged from the batteries during the set time
do not exceed the Wattage values listed in Tables 2 or 3 above
Batt
the percentage SoC to which the batteries discharge during the set time
20%
10%
0%
Grid Charge
check this box to allow for grid-to-battery charging during the set time
GEN
check this box to allow for gen-to-battery charging during the set time
> Sell Control Tab
80% DoD
90% DoD
100% DoD
General Standard
check this box when a generator is wired to the Grid Input
or to use the
Protect Param
settings listed in the
Grid Input
tab
UL 1741 & IEEE 1547
check this box for grid sell compliant functionality (default)