1.2.4
– PHI 3.8 Battery Connection Terminals
The PHI 3.8 b
atteries are equipped with two 3/8’’ threaded studs with a lock washer and nut. The red
colored high temperature molded insert connection is for the positive lead. The black colored high
temperature insert connection is for the negative lead.
CAUTION:
Do not attempt to loosen the large brass nut at the base of the terminals. This will void the Warranty.
CAUTION:
Do not reverse polarity. It will void the Warranty. Use a volt meter to check polarity before
connecting terminals.
Water Resistant Cable Boots are also included and will be in place when your units arrive. The boots are
to be placed over the cable terminations and will stretch to form a water-resistant seal around the base of
the molded inserts and terminal connections.
1.3
– Limitations of Use
The Sol-Ark equipment built into the SimpliPhi Power AccESS is not intended for use in connection with
life support systems or other medical equipment or devices.
1.4
– Explosive Gas Precautions
This equipment is not ignition protected. To prevent fire or explosion, do not install this product in
locations that require ignition-protected equipment. This includes any confined space containing vented
batteries, or flammable chemicals such as, natural gas (NG), liquid petroleum gas (LPG) or gasoline
(Benzine/Petrol).
Do not install in a confined space with machinery powered by flammable chemicals, or storage tanks,
fittings, or other connections between components of fuel or flammable chemical systems.
1.5
– Regulatory Specifications
Sol-Ark equipment has been tested and found to comply with the following:
•
Electronics certified safety by SGS labs to NEC and UL specifications: NEC 690.4B & NEC
705.4/6.
•
Grid interactivity requirements UL1741-2010/2018, IEEE1547a-2003/2014, FCC 15 class B,
UL1741SA, CA Rule 21 and HECO Rule 14H.
These standards provide regulation for acceptable output voltage ranges, acceptable output frequency
and anti-islanding performance.