background image

7

4.

REMOVING / INSTALLING OPTION MODULES

Shut off power before removing or installing any option module.

1. Remove module from case by inserting a screwdriver into tab slot open-

ing at top of input module (see Figure 5-1). Apply pressure to release
module from case. Repeat procedure for tab located on underside of
module and then slide module away from case.

2. Refer to appropriate sections to configure switches or jumpers for proper

operation.

!

3. Install module by carefully aligning module edges with slots in case and

pressing forward until tabs (on top and bottom) engage.

Figure 5-1. Removing Option
Module

3.2

Engineering Label Placement

If the engineering unit label needs replacing, place the tip of a ballpoint pen
into the small hole at the base of the engineering label in the bezel. Slide the
label up until it pops out. Grasp and remove. Slide the new label half the dis-
tance in, then use the ballpoint pen to slide it down into place.

18

Press RE      to choose Val-1 as the setting to be edited. Notice that the far right
digit has an alternating cursor. To change this digit, use 

S

 or 

T

. To move to the

next digit, press 

W

. When all changes to the value are complete, press

RE      to confirm the change and save it to memory.

NOTE:

 Any power loss before confirming a change will lose the edited value.

The menu will revert back to alternating between Val-1 and value. Press 

T

 to

move to the response setting.

9.1.1 Response

The display will now show 

“Rsp.” 

To edit response, press RE     , otherwise

press 

T

 to move to the next choice. When editing 

Rsp

., the display will show

Hyst, Dlay, or Ltch Flashing. Use 

S

 or 

T

 to choose the required response.

Press    RE    to confirm the choice. When choosing Hyst, the display will
alternate between Hyst and the current value.
To edit the value, press RE     .   Otherwise press 

T

 to move to the next choice.

Hysteresis will be used above and below the setpoint in equal amounts. The
value represents a percentage of the setpoint. For example: If the setpoint is
set to 100.00 with a high alarm and therhysteresis is set for 8.5%, the alarm
will not turn on until the reading on the display reaches 108.50. Once tripped,
the alarm will not turn off until the display reaches 91.50.

9.1.2 Delay

When choosing 

Dlay

, the display will alternate between 

Dlay

 and current value.

To edit the value press RE     . Otherwise press q to move to the next choice.

Dlay

 will be used above and below the setpoint in equal amounts. The value

represents the amount of delay in seconds. For example, if the setpoint is
again configured for high alarm and 

Dlay

 is set for 2.5 seconds the display

crosses the setpoint value and a timer begins to count off the 2.5 seconds
before the alarm trips. If, during those 2.5 seconds the value falls below the
setpoint, no action will be taken. When the unit successfully counts off 2.5

RESET
ENTER

RESET
ENTER

RESET
ENTER

RESET
ENTER

RESET
ENTER

RESET
ENTER

9.

MENU DETAIL

9.1

Relay Control (Sp1-Sp4)

While in menu, all other operations are suspended.
The H340 has four setpoint parameters and up to four relays associated with
those four setpoints. The setpoint LEDs on the display will light even if no relay
is present for that setpoint.
To change the setpoint value, enter the menu by pressing 

W

. If the password

allows relay control, it will be the first menu to appear. The display will show the
word 

“Sp1”

.

 

If this is the setpoint to be edited, press RE     , otherwise press 

T

to move to the next choice. When editing 

Sp1

, the display will alternate be-

tween Val-1 and a value. The “value” represents a threshold above or below
the setpoint being set to alarm.

NOTE:

 Before editing this value, be sure that the decimal point is in the proper

position. It is also recommended that any scaling or linearization be entered
before setpoints are determined.

RESET
ENTER

Summary of Contents for Hawk H340

Page 1: ...venue Lac du Flambeau WI 54538 0099 715 588 3311 FAX 715 588 3326 Printed in U S A Part No 06 117489 Edition 5 06 07 Visit us on the web at www simpsonelectric com Hawk 3 Temperature H340 4 Digit Adva...

Page 2: ...stomer Service at 715 588 3311 Internet http www simpsonelectric com Warranty and Returns SIMPSON ELECTRIC COMPANY warrants each instrument and other articles manufactured by it to be free from defect...

Page 3: ...3 NOTES 22 NOTES...

Page 4: ...1 Sp4 18 9 1 1 Response 18 9 1 2 Delay 18 9 1 3 Latch 19 9 1 4 Alarm 19 9 2 Display Control 19 9 3 Output Control 20 21 20mA When the display reaches 0 percent the analog output would be 4mA The limit...

Page 5: ...configured by default for HI 100 0 and LO 0 When the display reaches 100 volts the analog output would be 20mA When the display reaches 0 volts the analog output would be 4mA The Hawk3 is purchased as...

Page 6: ...y crosses a setpoint and the relays will revert to a normally de energized state When selecting St State from the menu the display will alternate between Stand the current setting To edit the setting...

Page 7: ...ss T to move to the next choice Hysteresis will be used above and below the setpoint in equal amounts The value represents a percentage of the setpoint For example If the setpoint is set to 100 00 wit...

Page 8: ...ces T Scrolls DOWN through menu choices RE Selects a menu or submenu to edit 5 3 In Edit Mode W Moves Edit Cursor to the left Flashing cursor shows value to edit Nu meric Values Only S Increases Numer...

Page 9: ...i g r e n E d e z i g r e n e e D t n e s e r p f i 2 y a l e R 2 t n i o P t e S 2 P S 2 l a V e u l a V 2 e s n o p s e R 2 p s R t s y H y a l D h c t L 9 9 2 o t 0 0 1 0 s d n o c e S 0 0 0 6 o t...

Page 10: ...e t a d p u 0 8 4 o t 1 e u l a V d n a B e u l a v t n e r r u c m o r f s t n u o c 9 9 o t 0 e u l a V s s e n t h g i r B t i r B S d n a T s s e n t h g i r b D E L e v o m s w o r r a y a l p s...

Page 11: ...ded for resistive circuits only Use a snubber circuit to protect the contacts from inductive loads 7 2 Frequently Asked Questions What is a Form A or Form C relay The form A relay is a 1 contact switc...

Page 12: ...r o d r o w s s a p t n e r r u c 0 0 0 NOTE If you forget your password turn power off in unit press and hold the Tkey and the RE key Turn power on and wait until the display reads noPas then press t...

Reviews: