MultiXplo / MultiTox
Page 38 / 60
NOSP15759-Rev 10
The INH screen:
This screen is dedicated to verify the inhibition mode configuration (frozen or free). If the
access level permits it, it is possible to change this setting.
6.7.
Adjustment menu [ADJT]
This menu presents all the detector settings. All the functionalities, except alarm level
acknowledgment, request access level 2.
6.7.1.
[STAT]us sub-menu
Alarm Acknowledgement
This menu enables the acknowledgement of the memorized alarms. The alarm can be
acknowledged only if the alarm condition has disappeared.
Inhibition / End of inhibition
The inhibition (called permanent inhibition) is activated or deactivated manually using the
menu. This function is used for deactivating the detector outputs (example: during
maintenance).
The « inhibition » menu is available if the sensor is not in inhibition, maintenance inhibition
or simulation.
Selecting the inhibition mode will switch the detector in inhibition mode.
The message “End of inhibition” is displayed on the TLU.
Press on “End of inhibition” to get the detector back to normal operating mode.