- 15 -
Setting the T1 temperature to start defrosting
Press the
ENTER
key to enter the setting menu and use the ▼/▲ keys to select the
Defrost
menu. After opening this menu, select the
Start
menu.
Defrost
Start
After opening this menu:
Start
-xx.x
The set temperature to stop!!! defrosting is displayed. Use the ▼/▲ keys and the
ENTER
key to set the individual digits and sign.
You can set –20.0°C to +5.0°C
; the default value is
-5.0°C.
Long press the ENTER key to save the set value
; the following message briefly
appears:
Saved OK
-yy.y
Then the display returns one level back in the menu.
Setting the T1 temperature to stop defrosting
Press the
ENTER
key to enter the setting menu and use the ▼/▲ keys to select the
Defrost
menu. After opening this menu, select the
Stop
menu.
Defrost
Stop
After opening this menu:
Stop
+xx.x
The set temperature to stop defrosting is displayed. Use the ▼/▲ keys and the
ENTER
key
to set the individual digits.
You can set +3.0°C to +25.0°C
; the default value is +7.0°C.
Long
press the ENTER key to save the set value
; the following message briefly appears:
Saved OK
yy.y
Then the display returns one level back in the menu.
Summary of Contents for SCMI-01.4
Page 1: ...COMMUNICATION MODULE SCMI 01 4 USER S MANUAL EN ...