background image

for the module.

To stop addressing press the “

C”

 key.

Simple system setup

  

(Service Mode)

(not available when using SMOKE EDIT,
only   used   for   simpler   systems   using   the
“MIDISMOKE_02.cfg” and keyboard setup)

The   purpose   with  this  command  is  to   learn   how
many modules that are located on the bus. Ensure
that   all   modules   have   power   and   that   they   are
connected to the bus so they can be identified. A
check   is   also   performed   that   all   modules   are
sequentially   addressed   with   no   missing   modules
inbetween.

Activate   this   setup   function   by  pressing  

Enter

.   It

will scan the SIOX bus over the address range 1-
59 and count the number of modules found.

Wait until the search is over.

This menu is useful to ensure that all modules are
communicating. Also, the type of module is shown. 

FOUND – total number of found modules.
A – current address.
SC2 – module type (example).

If the number of modules found matches what
is expected, press 

Enter

.

Now a check is performed that the modules found
are   sequentially   addressed   from   address   1   and
upwards with no missing modules between the first
and the last one. If the check fails, the command is
still active so the fault could be tracked down.

Press the 

Up/Down 

arrow to increment/decrement

the   address.   If   no   module   is   answering   on   an
address, “ERR” is displayed. “DBL” is displayed if
at least two modules are on the same address. In
this   case   there   should   be   another   address   for
which “ERR” is displayed because that module is
wrongly addressed. If a module is missing, check
the  wiring,  and  if  necessary abort  this command

with the “

C” key

  to invoke the  

Module addressing

command to readdress any missing modules. Then
run the 

Simple system setup

 once again.

When   the   check   passes,   the   text  

“OK,

CONFIGURATION   FOR   nn   MODULES”

  is

displayed.

The   next   menu  

Module   configuration

  will   be

entered.

Module configuration

 

(Service Mode)

Not available when using SMOKE EDIT,
only   used   for   simpler   systems   using   the
“MIDISMOKE_02.cfg” and keyboard setup.

Press Enter to select 

Module Configuration.

This menu shows damper control modules that are
addressed in the system. If “AP” for “Alarm Point”
is displayed then the smoke detector input is used
for triggering fire alarm. If all modules will be used
with smoke detectors then pressing 

F1

 will activate

alarm points for all modules. Pressing 

F2

 will have

the   reverse   effect   to   deactivate   all   alarm   points.
The selected number of dampers at each module
is   not   affected.   “D1”   and   “D2”   means   that   both
dampers are used.

To   manually   activate/deactivate   alarm/damper
settings use

 Up/Down

 arrow to select the address

for   each   module   to   handle.   Use  

Right

  arrow   to

cycle between the different alternatives which are:

One damper only
One  Alarm point
Two dampers
Two d Alarm point
Alarm point only

Changes are instant. Exit with 

Enter

 or “

C”

 key.

Note   that   if   a   two-damper   module   is   used   but
configured   for  one   damper,   the   damper  must   be
connected   to   channel   1.   The  

Open

  and  

Closed

inputs for damper 2 must be jumpered i.e. be in
active state. For instance, the SC2 module should
have   jumpers   between   terminals   24-25   and
terminals 26-27.

Factory default configuration: no Alarm Points,
one damper per module.

If   “COMMERR”   is   displayed   then   no   module   is
answering on that address. Unless some fault has

Profcon AB

Page 10

www.smokecontrol.net

     CONFIGURATION FOR                  
      ADDR:1  AP D1 D2

FOUND MODULES      

FOUND:2    A:1  SC2    

SIMPLE SYSTEM      
SETUP

ADDRESSING...          

GROUP:0    ADDR:1     

SEARCHING MODULES

FOUND:2    A:1  SC2    

MODULE
CONFIGURATION    
    

Summary of Contents for MIDI SMOKE 2

Page 1: ...10 Change PIN code 11 Change IP address 11 Change IP gateway address 11 Change subnet mask 11 Change port number for TCP IP 11 Set exercise start delay 12 Show digital input status 12 Show digital out...

Page 2: ...oad the configuration file 15 Step 3 System test 15 Step 4 Set RTC 15 Step 5 Change Pin Code 15 Step 6 Activate watchdog 16 Step 7 Set time for automatic exit from Service Mode 16 Step 8 Switch the sy...

Page 3: ...ommand Digital I O MIDI SMOKE 2 includes four digital inputs to be connected to external open close contacts DI1 terminals 1 2 is the External Fire Input When the contact opens it will indicate Fire A...

Page 4: ...RATION OF WATCHDOG Tc 5 s WATCHDOG 30 s ENT SAVE FUNC TEST SETTINGS T W T F S S I FC1 M 06 00 SETTINGS OF CLOCK DATE 2012 02 10 16 30 FRIDAY SETUP RUN IND OPEN AT FUNC TEST MODULE ADDRESSING ENTER STA...

Page 5: ...STATUS FIRE RESET DI2 OPEN STATUS NIGHT MODE DI3 OPEN Only in Service Mode Not when using SmokeEdit From previous page Only in Service Mode Only in Service Mode Only in Service Mode Only in Service M...

Page 6: ...DO4 CLOSED SET SERVICE MODE TIMEOUT SET SIOX REPEATS EX2 VERSION EX2 v1 61 From previous page Only in Service Mode Only in Service Mode Only in Service Mode Only in Service Mode Only in Service Mode O...

Page 7: ...are version 1 61 it is also required that the communication watchdog be set for the OK LED to be lit To enter Service Mode press F2 and the following text on the display is shown Numbers in the pin co...

Page 8: ...ow adjusts the value Enter sends the value to all modules If the value is set to zero the function is deactivated This is useful during com missioning to stop dampers from closing unex pectedly due to...

Page 9: ...is being performed Module addressing Service Mode This setup menu is used for addressing damper control modules Every module in the system requires a unique address The address consists of a Group ad...

Page 10: ...les Then run the Simple system setup once again When the check passes the text OK CONFIGURATION FOR nn MODULES is displayed The next menu Module configuration will be entered Module configuration Serv...

Page 11: ...change the IP address for the PC or the MIDI SMOKE 2 Change IP gateway address Service Mode Introduced in firmware 1 40 If the unit will be connected to Ethernet the IP gateway address can be changed...

Page 12: ...ange Show digital input status Service Mode For each of the four digital inputs DI1 DI4 there is a menu showing current status to aid in fault tracing Show digital output status Service Mode For each...

Page 13: ...loaded with a configuration file MIDISMOKE_02 cfg intended for simpler systems where the key pad is used for setup These systems support up to a maximum of 59 damper modules addressed from 1 59 in a s...

Page 14: ...a mix of sum alarm night mode functional test and fire alarm If the Run indication relay output DO4 will be used it has to be configured for the desired combination of events otherwise go to the next...

Page 15: ...address set correctly Do this by clicking on the Modules tab and then right click on the Midi Smoke symbol and select Properties Check the watchdog time by clicking on the Modules tab and then right...

Page 16: ...n is approximately 3 5 W Connection of AC power The secondary transformer winding should be connected between terminals 13 G and 14 G0 Connection of DC power Connect the negative supply wire to termin...

Page 17: ...be connected to open close switches See page 1 for a functional description Digital Outputs There are four relay outputs on the MIDI SMOKE 2 Their breaking capacity is 1 A at 30 V AC DC They are norm...

Page 18: ...MidiSmoke2_ProdDescr_12en odt 2018 05 30 YE Profcon AB Page 18 www smokecontrol net...

Reviews: