occurred   that   prevents   a   module   to   answer,   this
means that the address is not used in the system
(and not the addresses above either). Check that
the previous address was the highest in use.

Change PIN code

 

(Service Mode)

Press 

Enter

 to change the PIN code.

Numbers   in   the   pin   code   are   changed   with   the
arrow   keys.  When   the   new   pin   code   has   been
chosen, press 

Enter 

to confirm and store the new

code.

If   the   PIN   code   is   lost,   see  

Reset   pin   code   to

factory default 

for advice.

Change IP-address

 

(Service Mode)

If   the  unit  will be  connected  to  Ethernet,   the  IP-
address may have to be changed from the default
192.168.0.234.

Press 

Enter

 to change the IP-address.

Numbers in the IP-address are changed with the
arrows. When the new address has been chosen,
press 

Enter 

to confirm and store the new address.

The module must be restarted (power off/on) to
effectuate the change.

Please   note:   if   a   direct   connection   between   the
MIDI SMOKE 2 and a PC (Windows) is desired, it
will be necessary that the IP-address for the PC
and the MIDI SMOKE 2 shares the same network
address space. Typically this means that the first
three   fields   in   the   IP-address   must   be   identical.
The last field must differ.

Either   change   the   IP-address   for   the   PC   or   the
MIDI SMOKE 2.

Change IP-gateway address

 

(Service Mode)

Introduced in firmware 1.40

If   the  unit   will  be  connected  to  Ethernet,  the  IP-
gateway   address   can   be   changed   to   match   the
current network.

Press 

Enter

 to change the IP-gateway address.

Numbers in the IP-gateway address are changed
with the arrows. When the new address has been
chosen, press 

Enter  

to confirm and store the new

address.

The module must be restarted (power off/on) to
effectuate the change.

Change subnet mask

 

(Service Mode)

Introduced in firmware 1.60

If the unit will be connected to Ethernet, the Subnet
Mask   can   be   changed   to   match   the   current
network. Factory default setting is 255.255.255.0.

Press 

Enter

 to change the Subnet Mask.

Numbers in the Subnet Mask are changed with the
arrows. When the new address has been chosen,
press 

Enter 

to confirm and store the new address.

The module must be restarted (power off/on) to
effectuate the change.

Change port number for TCP/IP

 

(Service Mode)

Press 

Enter

 to change the port number.

This   port   is   used   for   SioxNet   TCP/IP
communications   used   by   SioxTools   and

Profcon AB

Page 11

www.smokecontrol.net

CHANGE PIN CODE

NEW PIN: 5555
C=ABORT

CHANGE IP-ADDRESS

C=ABORT,ENTER=OK
192.168.000.234

CHANGE TCP/IP PORT

C=ABORT,ENTER=OK
    PORT:01024

 CHANGE IP-GATEWAY  

C=ABORT,ENTER=OK
192.168.000.001

SET SUBNET MASK 

C=ABORT,ENTER=OK
255.255.255.000

Summary of Contents for MIDI SMOKE 2

Page 1: ...10 Change PIN code 11 Change IP address 11 Change IP gateway address 11 Change subnet mask 11 Change port number for TCP IP 11 Set exercise start delay 12 Show digital input status 12 Show digital out...

Page 2: ...oad the configuration file 15 Step 3 System test 15 Step 4 Set RTC 15 Step 5 Change Pin Code 15 Step 6 Activate watchdog 16 Step 7 Set time for automatic exit from Service Mode 16 Step 8 Switch the sy...

Page 3: ...ommand Digital I O MIDI SMOKE 2 includes four digital inputs to be connected to external open close contacts DI1 terminals 1 2 is the External Fire Input When the contact opens it will indicate Fire A...

Page 4: ...RATION OF WATCHDOG Tc 5 s WATCHDOG 30 s ENT SAVE FUNC TEST SETTINGS T W T F S S I FC1 M 06 00 SETTINGS OF CLOCK DATE 2012 02 10 16 30 FRIDAY SETUP RUN IND OPEN AT FUNC TEST MODULE ADDRESSING ENTER STA...

Page 5: ...STATUS FIRE RESET DI2 OPEN STATUS NIGHT MODE DI3 OPEN Only in Service Mode Not when using SmokeEdit From previous page Only in Service Mode Only in Service Mode Only in Service Mode Only in Service M...

Page 6: ...DO4 CLOSED SET SERVICE MODE TIMEOUT SET SIOX REPEATS EX2 VERSION EX2 v1 61 From previous page Only in Service Mode Only in Service Mode Only in Service Mode Only in Service Mode Only in Service Mode O...

Page 7: ...are version 1 61 it is also required that the communication watchdog be set for the OK LED to be lit To enter Service Mode press F2 and the following text on the display is shown Numbers in the pin co...

Page 8: ...ow adjusts the value Enter sends the value to all modules If the value is set to zero the function is deactivated This is useful during com missioning to stop dampers from closing unex pectedly due to...

Page 9: ...is being performed Module addressing Service Mode This setup menu is used for addressing damper control modules Every module in the system requires a unique address The address consists of a Group ad...

Page 10: ...les Then run the Simple system setup once again When the check passes the text OK CONFIGURATION FOR nn MODULES is displayed The next menu Module configuration will be entered Module configuration Serv...

Page 11: ...change the IP address for the PC or the MIDI SMOKE 2 Change IP gateway address Service Mode Introduced in firmware 1 40 If the unit will be connected to Ethernet the IP gateway address can be changed...

Page 12: ...ange Show digital input status Service Mode For each of the four digital inputs DI1 DI4 there is a menu showing current status to aid in fault tracing Show digital output status Service Mode For each...

Page 13: ...loaded with a configuration file MIDISMOKE_02 cfg intended for simpler systems where the key pad is used for setup These systems support up to a maximum of 59 damper modules addressed from 1 59 in a s...

Page 14: ...a mix of sum alarm night mode functional test and fire alarm If the Run indication relay output DO4 will be used it has to be configured for the desired combination of events otherwise go to the next...

Page 15: ...address set correctly Do this by clicking on the Modules tab and then right click on the Midi Smoke symbol and select Properties Check the watchdog time by clicking on the Modules tab and then right...

Page 16: ...n is approximately 3 5 W Connection of AC power The secondary transformer winding should be connected between terminals 13 G and 14 G0 Connection of DC power Connect the negative supply wire to termin...

Page 17: ...be connected to open close switches See page 1 for a functional description Digital Outputs There are four relay outputs on the MIDI SMOKE 2 Their breaking capacity is 1 A at 30 V AC DC They are norm...

Page 18: ...MidiSmoke2_ProdDescr_12en odt 2018 05 30 YE Profcon AB Page 18 www smokecontrol net...

Reviews: