VisualSetup   forms   but   not   for   Modbus   TCP/IP
communications. Modbus TCP/IP communications
should use the standard Modbus TCP/IP port 502.

Please   note   that   normally   there   is   no   need   to
change the port number. Standard port number is
1024. Lower numbers should not be used. Highest
available is 65535.

The port number is changed with the arrow keys.
When   the   new   number   has   been   chosen,   press

Enter 

to confirm and store the new port number.

The module must be restarted (power off/on) to
effectuate the change.

Set exercise start delay

 

(Service Mode)

Introduced in firmware 1.60

When damper function test (exercise) is requested
either thru digital inputs, real time clock controlled
or   via   the   “FUNC.   TEST ALL  DAMPERS”   menu
then a configurable delay (0-500 seconds) can be
set   to   stop   fans   that   are   controlled   by   exercise
status   outputs  

before

  the   actual   exercise   starts.

For instance, if relay output DO4 is configured to
open   during   exercise   and   the   time   is   set   to   60
seconds then the relay output will open 60 seconds
before actual exercise starts.

Press 

Enter

 to change the time.

Up

  arrow   increases   the   time   in   10   seconds

increments. 

Down

 arrow resets the time to zero.

Press  

Enter

  to confirm or “

C”

  to exit without any

change.

Show digital input status

 

(Service Mode)

For each of the four digital inputs DI1-DI4 there is a
menu showing current status to aid in fault tracing.

Show digital output status

 

(Service Mode)

For each of the four digital outputs DO1-DO4 there
is   a   menu   showing   current   status   to   aid   in   fault
tracing. To toggle the output status press 

Left

  key

or  

Right  

key.   Please   note   that   as   long   as   these

menues are active, MIDI SMOKE 2 is not able to
control   the   output   statuses.  Also   be   aware   that
reversing the output status may affect connected
systems, i.e. a fire alarm could be generated.

Press “

C”

 or 

Enter

 to exit command.

Set service mode timeout

 

(Service Mode)

The   time   for   automatic   exit   from   Service   Mode
back to normal operation can be set between 1 -
72   hours   or   be   inactivated   (no   automatic   exit).
Factory default is no automatic exit.

If   a  unit  is  mistakenly forgotten  in  Service  Mode
then it will return back to normal operation after the
time expires. Please note that pressing any key on
the keyboard will reinit the timeout time.

Press 

Enter

 to change the timeout.

Profcon AB

Page 12

www.smokecontrol.net

STATUS EXTERNAL
ALARM DI1:CLOSED

STATUS FIRE RESET
DI2:OPEN

STATUS NIGHT MODE
DI3:OPEN

STATUS FUNC.TEST
DI4:OPEN

SUM ALARMS
OUTPUT DO1:CLOSED

FIRE ALARM
OUTPUT DO2:CLOSED

SD SERVICE
OUTPUT DO3:CLOSED

RUN INDICATOR
OUTPUT DO4:CLOSED

SET SERVICE MODE
TIMEOUT

EXERCISE START
DELAY

SET EXERCISE
DELAY 060 s

Summary of Contents for MIDI SMOKE 2

Page 1: ...10 Change PIN code 11 Change IP address 11 Change IP gateway address 11 Change subnet mask 11 Change port number for TCP IP 11 Set exercise start delay 12 Show digital input status 12 Show digital out...

Page 2: ...oad the configuration file 15 Step 3 System test 15 Step 4 Set RTC 15 Step 5 Change Pin Code 15 Step 6 Activate watchdog 16 Step 7 Set time for automatic exit from Service Mode 16 Step 8 Switch the sy...

Page 3: ...ommand Digital I O MIDI SMOKE 2 includes four digital inputs to be connected to external open close contacts DI1 terminals 1 2 is the External Fire Input When the contact opens it will indicate Fire A...

Page 4: ...RATION OF WATCHDOG Tc 5 s WATCHDOG 30 s ENT SAVE FUNC TEST SETTINGS T W T F S S I FC1 M 06 00 SETTINGS OF CLOCK DATE 2012 02 10 16 30 FRIDAY SETUP RUN IND OPEN AT FUNC TEST MODULE ADDRESSING ENTER STA...

Page 5: ...STATUS FIRE RESET DI2 OPEN STATUS NIGHT MODE DI3 OPEN Only in Service Mode Not when using SmokeEdit From previous page Only in Service Mode Only in Service Mode Only in Service Mode Only in Service M...

Page 6: ...DO4 CLOSED SET SERVICE MODE TIMEOUT SET SIOX REPEATS EX2 VERSION EX2 v1 61 From previous page Only in Service Mode Only in Service Mode Only in Service Mode Only in Service Mode Only in Service Mode O...

Page 7: ...are version 1 61 it is also required that the communication watchdog be set for the OK LED to be lit To enter Service Mode press F2 and the following text on the display is shown Numbers in the pin co...

Page 8: ...ow adjusts the value Enter sends the value to all modules If the value is set to zero the function is deactivated This is useful during com missioning to stop dampers from closing unex pectedly due to...

Page 9: ...is being performed Module addressing Service Mode This setup menu is used for addressing damper control modules Every module in the system requires a unique address The address consists of a Group ad...

Page 10: ...les Then run the Simple system setup once again When the check passes the text OK CONFIGURATION FOR nn MODULES is displayed The next menu Module configuration will be entered Module configuration Serv...

Page 11: ...change the IP address for the PC or the MIDI SMOKE 2 Change IP gateway address Service Mode Introduced in firmware 1 40 If the unit will be connected to Ethernet the IP gateway address can be changed...

Page 12: ...ange Show digital input status Service Mode For each of the four digital inputs DI1 DI4 there is a menu showing current status to aid in fault tracing Show digital output status Service Mode For each...

Page 13: ...loaded with a configuration file MIDISMOKE_02 cfg intended for simpler systems where the key pad is used for setup These systems support up to a maximum of 59 damper modules addressed from 1 59 in a s...

Page 14: ...a mix of sum alarm night mode functional test and fire alarm If the Run indication relay output DO4 will be used it has to be configured for the desired combination of events otherwise go to the next...

Page 15: ...address set correctly Do this by clicking on the Modules tab and then right click on the Midi Smoke symbol and select Properties Check the watchdog time by clicking on the Modules tab and then right...

Page 16: ...n is approximately 3 5 W Connection of AC power The secondary transformer winding should be connected between terminals 13 G and 14 G0 Connection of DC power Connect the negative supply wire to termin...

Page 17: ...be connected to open close switches See page 1 for a functional description Digital Outputs There are four relay outputs on the MIDI SMOKE 2 Their breaking capacity is 1 A at 30 V AC DC They are norm...

Page 18: ...MidiSmoke2_ProdDescr_12en odt 2018 05 30 YE Profcon AB Page 18 www smokecontrol net...

Reviews: