background image

The green OK LED should be on to indicate that
the system is operating normal and error free and
that Service Mode is not active any more.

If the communication watchdog has not  been
activated   then   the   display   will   flash

WATCHDOG INACTIVE!

” in the main menu.

Introduced in software version 1.61 the green
OK   LED   will   be   off   during   normal   operation
(unit not in Service Mode) if the communication
watchdog   has   not   been   activated.   Also,   the
ERROR LED will flash at the same rate as the
warning text in the main menu.

Note that the flashing has higher priority than other
errors   that   otherwise   would   give   a   constant
activation of the ERROR LED.

Remedy   this   by   activating   the   communication
watchdog.

This concludes the setup and configuration task.

Step-by-Step   instructions   to   commission   a
system using SMOKE EDIT

Assuming   that   the   electrical   installation   is   ready
with   all   damper   units   installed,   there   are   a   few
steps necessary to get the system up and running.

It is also assumed that a SMOKE EDIT project has
been created that can be compiled error free.

For   more   information   about   specific   menu
functions,   please   refer   to   the   corresponding
section in this document.

Step 1: Addressing the modules

Please   note:   if   a   PC   is   connected   to   the   MIDI
SMOKE   2   module,   the   PC-based   software
SioxTools   could   be   used   as   an   alternative   to
address the modules.

Enter the 

Service Mode

 and continue down to the

MODULE   ADDRESSING

  menu.   Press  

Enter

  to

start the addressing operation. Note that it starts at
Group   address=0   and   Station   address=1.   The
Station address range is 1-59 depending on how
many   modules   that   are   installed.   The   Group
Address is normally zero but for large systems it
could   also   be   61,   62   or   63.   Refer   to   relevant
project data to find out details about the planned
module addressing in the system.

See 

Module Addressing

 menu description

.

Step 2: Download the configuration file

Use SMOKE EDIT to open the project file. Check
that   the   project   file   has   the   MIDI   SMOKE   2   IP-
address   set   correctly.   Do   this   by   clicking   on   the

”Modules”

  tab   and   then   right-click   on   the  

”Midi

Smoke”

 symbol and select 

”Properties”

. Check the

watchdog   time   by   clicking   on   the  

”Modules”

  tab

and then right-click on the 

”Smoke Control”

 symbol

and select 

”Properties”

. Default time when creating

a new project is 30 seconds.

Please   note   that   the   configuration   of   the  

Run

indication relay output

 is done in SMOKE EDIT by

clicking   on   the  

”Modules”  

tab   and   then   right-

clicking   on   the  

”Midi   Smoke”

  symbol   and   select

”Properties”

.

The configuration can also  be changed  by  using
the   key   pad   on   the   MIDI   SMOKE   2,   see  

Run

indication   relay  output

  menu   description.   But   the

project file should be updated as well.

The functional test settings are handled in a similar
manner. Start by clicking on the 

”Modules” 

tab. For

each fire cell right-click on the fire cell symbol and
select  

”Properties”

. This can also be changed by

using the key pad on the MIDI SMOKE 2 but the
project file should be updated as well. To download
a corrected project file is of course the preferred
method.

Please note that an activation of DI4  

will always

request a functional test sequence unless 

Service

Mode

 is active.

Now the configuration file can be downloaded to
the MIDI SMOKE 2.

Step 3: System test

At   this   point   the   MIDI   SMOKE   2   unit   is
communicating   with   the   damper   modules   in   the
system and status will now be updated. If there are
alarms use the 

Alarm menu

 and 

Fire cells

 menu to

get information about what and where the trouble
is and correct it.

If   external   systems   are   connected   to   the   digital
inputs   and   relay   outputs   their   operation   can   be
checked now. See the earlier sections 

Show digital

input status

 and 

Show digital output status

.

Function test all dampers

 could be attempted to

check that all dampers can manage a close/open
operation.

Step 4: Set RTC

The real-time clock is used for automatic functional
test scheduling.

See 

Setting up date / time

 menu description.

Step 5: Change Pin Code

If required, change the Pin Code in order to avoid
inadvertent   access   to   the   system   setup.   Keep   a
note of the new one in a safe place.

See 

Change PIN code 

menu description

.

Profcon AB

Page 15

www.smokecontrol.net

Summary of Contents for MIDI SMOKE 2

Page 1: ...10 Change PIN code 11 Change IP address 11 Change IP gateway address 11 Change subnet mask 11 Change port number for TCP IP 11 Set exercise start delay 12 Show digital input status 12 Show digital out...

Page 2: ...oad the configuration file 15 Step 3 System test 15 Step 4 Set RTC 15 Step 5 Change Pin Code 15 Step 6 Activate watchdog 16 Step 7 Set time for automatic exit from Service Mode 16 Step 8 Switch the sy...

Page 3: ...ommand Digital I O MIDI SMOKE 2 includes four digital inputs to be connected to external open close contacts DI1 terminals 1 2 is the External Fire Input When the contact opens it will indicate Fire A...

Page 4: ...RATION OF WATCHDOG Tc 5 s WATCHDOG 30 s ENT SAVE FUNC TEST SETTINGS T W T F S S I FC1 M 06 00 SETTINGS OF CLOCK DATE 2012 02 10 16 30 FRIDAY SETUP RUN IND OPEN AT FUNC TEST MODULE ADDRESSING ENTER STA...

Page 5: ...STATUS FIRE RESET DI2 OPEN STATUS NIGHT MODE DI3 OPEN Only in Service Mode Not when using SmokeEdit From previous page Only in Service Mode Only in Service Mode Only in Service Mode Only in Service M...

Page 6: ...DO4 CLOSED SET SERVICE MODE TIMEOUT SET SIOX REPEATS EX2 VERSION EX2 v1 61 From previous page Only in Service Mode Only in Service Mode Only in Service Mode Only in Service Mode Only in Service Mode O...

Page 7: ...are version 1 61 it is also required that the communication watchdog be set for the OK LED to be lit To enter Service Mode press F2 and the following text on the display is shown Numbers in the pin co...

Page 8: ...ow adjusts the value Enter sends the value to all modules If the value is set to zero the function is deactivated This is useful during com missioning to stop dampers from closing unex pectedly due to...

Page 9: ...is being performed Module addressing Service Mode This setup menu is used for addressing damper control modules Every module in the system requires a unique address The address consists of a Group ad...

Page 10: ...les Then run the Simple system setup once again When the check passes the text OK CONFIGURATION FOR nn MODULES is displayed The next menu Module configuration will be entered Module configuration Serv...

Page 11: ...change the IP address for the PC or the MIDI SMOKE 2 Change IP gateway address Service Mode Introduced in firmware 1 40 If the unit will be connected to Ethernet the IP gateway address can be changed...

Page 12: ...ange Show digital input status Service Mode For each of the four digital inputs DI1 DI4 there is a menu showing current status to aid in fault tracing Show digital output status Service Mode For each...

Page 13: ...loaded with a configuration file MIDISMOKE_02 cfg intended for simpler systems where the key pad is used for setup These systems support up to a maximum of 59 damper modules addressed from 1 59 in a s...

Page 14: ...a mix of sum alarm night mode functional test and fire alarm If the Run indication relay output DO4 will be used it has to be configured for the desired combination of events otherwise go to the next...

Page 15: ...address set correctly Do this by clicking on the Modules tab and then right click on the Midi Smoke symbol and select Properties Check the watchdog time by clicking on the Modules tab and then right...

Page 16: ...n is approximately 3 5 W Connection of AC power The secondary transformer winding should be connected between terminals 13 G and 14 G0 Connection of DC power Connect the negative supply wire to termin...

Page 17: ...be connected to open close switches See page 1 for a functional description Digital Outputs There are four relay outputs on the MIDI SMOKE 2 Their breaking capacity is 1 A at 30 V AC DC They are norm...

Page 18: ...MidiSmoke2_ProdDescr_12en odt 2018 05 30 YE Profcon AB Page 18 www smokecontrol net...

Reviews: