background image

Step 6: Activate watchdog

Enter the Watchdog menu and set the watchdog
timeout. Refer to the earlier section 

Watchdog.

See 

Watchdog 

menu description

.

Step 7: Set time for automatic exit from Service
Mode

If   desirable,   the   time   for   automatic   exit   from
Service Mode can be set. Factory default is that
automatic   exit   is   inactivated.   Time   can   be   set
between 1 – 72 hours.

See Set Service mode timeout menu description.

Step 8: Switch the system to normal operation
mode

Exit the 

Service Mode

 by pressing “

F2

” och ”

C”

 in

the   main   menu   to   let   the   system   run   in   normal
operational mode.

Fire alarms will now be distributed thru DO2 to any
external systems.

The green OK LED should be on to indicate that
the system is operating normal and error free and
that Service Mode is not active any more.

If the communication watchdog has not  been
activated   then   the   display   will   flash

WATCHDOG INACTIVE!

” in the main menu.

Introduced in software version 1.61 the green
OK   LED   will   be   off   if   the   communication
watchdog   has   not   been   activated   during
normal   operation   (unit   not   in   Service   Mode).
Also,   the   ERROR   LED   will   flash   at   the   same
rate as the warning text in the main menu.

Note that the flashing has higher priority than other
errors   that   otherwise   would   give   a   constant
activation of the ERROR LED.

Remedy   this   by   activating   the   communication
watchdog.

This concludes the setup and configuration task.

Installation

MIDI   SMOKE   2   is   intended   for   installation   on
standard 35 mm DIN-rails conforming to EN50022
(DIN46277-3). The unit should be located inside an
enclosure   prohibiting   access   by   unauthorized
personnel.

The module can be AC- or DC-powered. The AC
input voltage range is 12-24 V AC and the DC input
voltage range is 18-35 V DC. Power consumption

at normal operation is approximately 3,5 W.

Connection of AC power
The   secondary   transformer   winding   should   be
connected between terminals 13 (G) and 14 (G0).

Connection of DC power
Connect   the   negative   supply  wire   to   terminal   14
and the positive supply wire to terminal 13.

Three-wire bus

MIDI   SMOKE   2   supports   the   three-wire   concept
that is used by the Smoke Control products. The
three wires are SIOX, power (G) and ground (G0).

Terminal   10   is   used   for   the   outgoing   SIOX   bus.
Power   to   the   first   section   of   damper   modules
(before another transformer handles next section)
can be taken from terminal 11 (G) and terminal 12
(G0).

Please   note   that   screw   terminal   14   (incoming
power ground, G0) is internally connected to screw
terminal 12, as well as screw terminals 9 and 23 at
the   I/O-connectors.   Screw   terminal   13   (incoming
power, G) is internally connected to screw terminal
11.

For other types of modules, e.g. S45 and S27 that
must   be   separately   powered   by   24   V   DC,   their
SIOX   bus   connection   should   be   connected
between terminal 10 (SIOX) and terminal 12 (G0).

The   ground   wire   (G0)   should  

always

  be   routed

thru   the   whole   system,  

only   interrupted

  if   R30

Bus   Expander   Modules   are   used   that   provides
galvanic isolation between bus sections.

The third wire (G) is used to power the modules.
Depending on the size of the installation this wire is
usually divided into segments. Each segment has
its own power transformer and is powering a group
of damper modules.

Three-wire bus connection:
Screw terminal 10 is the SIOX bus.
Power to the damper modules comes out via screw
terminal 11 (G).
Screw terminal 12 is the power ground (G0).

For more information about cable selection, please
refer to:

http://www.telefrang.se/download/pdf/CableSelecti
on.pdf

Grounding
To avoid that the system will electrically “float”, the
power ground wire (G0) at terminal 12 should be
connected   to   a   grounded   point   nearby   the  MIDI
SMOKE 2 unit.

Because   the   ground   potential   between   different

Profcon AB

Page 16

www.smokecontrol.net

Summary of Contents for MIDI SMOKE 2

Page 1: ...10 Change PIN code 11 Change IP address 11 Change IP gateway address 11 Change subnet mask 11 Change port number for TCP IP 11 Set exercise start delay 12 Show digital input status 12 Show digital out...

Page 2: ...oad the configuration file 15 Step 3 System test 15 Step 4 Set RTC 15 Step 5 Change Pin Code 15 Step 6 Activate watchdog 16 Step 7 Set time for automatic exit from Service Mode 16 Step 8 Switch the sy...

Page 3: ...ommand Digital I O MIDI SMOKE 2 includes four digital inputs to be connected to external open close contacts DI1 terminals 1 2 is the External Fire Input When the contact opens it will indicate Fire A...

Page 4: ...RATION OF WATCHDOG Tc 5 s WATCHDOG 30 s ENT SAVE FUNC TEST SETTINGS T W T F S S I FC1 M 06 00 SETTINGS OF CLOCK DATE 2012 02 10 16 30 FRIDAY SETUP RUN IND OPEN AT FUNC TEST MODULE ADDRESSING ENTER STA...

Page 5: ...STATUS FIRE RESET DI2 OPEN STATUS NIGHT MODE DI3 OPEN Only in Service Mode Not when using SmokeEdit From previous page Only in Service Mode Only in Service Mode Only in Service Mode Only in Service M...

Page 6: ...DO4 CLOSED SET SERVICE MODE TIMEOUT SET SIOX REPEATS EX2 VERSION EX2 v1 61 From previous page Only in Service Mode Only in Service Mode Only in Service Mode Only in Service Mode Only in Service Mode O...

Page 7: ...are version 1 61 it is also required that the communication watchdog be set for the OK LED to be lit To enter Service Mode press F2 and the following text on the display is shown Numbers in the pin co...

Page 8: ...ow adjusts the value Enter sends the value to all modules If the value is set to zero the function is deactivated This is useful during com missioning to stop dampers from closing unex pectedly due to...

Page 9: ...is being performed Module addressing Service Mode This setup menu is used for addressing damper control modules Every module in the system requires a unique address The address consists of a Group ad...

Page 10: ...les Then run the Simple system setup once again When the check passes the text OK CONFIGURATION FOR nn MODULES is displayed The next menu Module configuration will be entered Module configuration Serv...

Page 11: ...change the IP address for the PC or the MIDI SMOKE 2 Change IP gateway address Service Mode Introduced in firmware 1 40 If the unit will be connected to Ethernet the IP gateway address can be changed...

Page 12: ...ange Show digital input status Service Mode For each of the four digital inputs DI1 DI4 there is a menu showing current status to aid in fault tracing Show digital output status Service Mode For each...

Page 13: ...loaded with a configuration file MIDISMOKE_02 cfg intended for simpler systems where the key pad is used for setup These systems support up to a maximum of 59 damper modules addressed from 1 59 in a s...

Page 14: ...a mix of sum alarm night mode functional test and fire alarm If the Run indication relay output DO4 will be used it has to be configured for the desired combination of events otherwise go to the next...

Page 15: ...address set correctly Do this by clicking on the Modules tab and then right click on the Midi Smoke symbol and select Properties Check the watchdog time by clicking on the Modules tab and then right...

Page 16: ...n is approximately 3 5 W Connection of AC power The secondary transformer winding should be connected between terminals 13 G and 14 G0 Connection of DC power Connect the negative supply wire to termin...

Page 17: ...be connected to open close switches See page 1 for a functional description Digital Outputs There are four relay outputs on the MIDI SMOKE 2 Their breaking capacity is 1 A at 30 V AC DC They are norm...

Page 18: ...MidiSmoke2_ProdDescr_12en odt 2018 05 30 YE Profcon AB Page 18 www smokecontrol net...

Reviews: