Main menu

OK:   

No alarms.

OK TEST: Functional damper test is in progress.
FIRE:

One   or   more   alarm   points   detected
a   fire   alarm   or   one   or   more   alarm  
points are not answering.

B-ALARM: Service alarm from a smoke detector, 

damper error from a damper module or
that one or more damper modules are 
not answering.

NO APP:

No configuration is loaded, or halted.  
Could   happen   if   a   Smoke   Edit  
download is aborted for some reason. 
In that case just try to download again.

If  a small  “N” is displayed before  the status  text
then the system is in 

Night 

mode (dampers closed)

thru activation of DI3.

If “F1” is pressed, a text is displayed showing the
name of the configuration file. If the configuration
file is customer specified, the text displayed can be
freely chosen, e.g. to display the facility name of
the installation.

Service Mode

By pressing “F2” in the main menu it is possible to
enter   the  

Service   Mode

.

  In  

Service   Mode

outgoing fire alarms are blocked but shown in
the   display   to   facilitate   fault   tracing.

  Also,

dampers are opened and automatic or via DI4 re-
quested functional tests are suppressed. However,
functional tests (exercise) can still be requested via
the  

Function test all dampers  

menu, external DI-

modules or thru Modbus TCP

.

Unless   the  

Service   Mode

  is   entered,   only   the

Alarms 

menu

, Fire cells 

menu and 

Function test all

dampers

 menu are available.

When the work is completed it is mandatory to
remember to exit the 

Service Mode

 by pressing

key “F2” and then “C” in the main menu.

If the green OK LED is on it indicates normal
alarm free operation and that   

Service Mode

 is

not active.

From   system   software   version   1.61   it   is   also
required that the communication watchdog be
set for the OK LED to be lit.

To   enter  

Service   Mode

,   press   “F2”   and   the

following text on the display is shown:

Numbers  in the  pin  code  are  changed  using the
arrow keys.
When the correct pin code is entered press 

Enter

.

Default pin code is 5555.

Reset pin code to factory default

If the PIN code has been lost there is a recovery
method: Hold down the “

C”

 key while restarting the

module   (cycling   the   power).   When   the   question

“RESET   PIN   CODE   TO     5555?   ENTER=OK”

  is

shown, press 

Enter.

Change language

If the  

Service Mode

  is active and the  

Up

  arrow  is

pressed in the  

Main

 menu, a menu to change the

language is displayed. Press 

Right

 arrow to toggle

the alternatives Swedish and English. Confirm by
pressing 

Enter

.

Alarms

Shows current alarms. Press  

Enter

  to display the

alarm   list.   Press  

Down  

arrow  to   advance   to   the

next alarm in the list or  

Up  

arrow  to return to the

previous   alarm.   EXT.FIRE   is   the   DI1   Fire  Alarm
input on the MIDI SMOKE 2 module. DI2 must be
activated (>1,5 s) to unlatch this alarm.

Remember: ”

C”

 backs one step in the menues

and/or aborts a command.

In   system   software   version   1.62   a   check   was
introduced for a very rare error.

If the display shows “MODULE FAIL (SD)” it means
that the damper module on the address shown is
not defined as an Alarm Point but nevertheless is
in Fire status (and its dampers will be closed). The
reason   for   this   is   that   the   local   smoke   detector
input rises the alarm. Check that the resistor (2,2
kohm),   which   should   be   installed   between
terminals 4 and 5 on an SC2-module is correctly
installed   and   that   the   terminal   screws   are
tightened.

Profcon AB

Page 7

www.smokecontrol.net

ALARM FIRE:OTHERS
EXT.FIRE    1:1

2018-02-20 15:26

SYSTEM: OK      

    PIN: 5555       

C=EXIT SERV. MODE 

        MODULE FAIL (SD)            

Address G:0  A:7          

Summary of Contents for MIDI SMOKE 2

Page 1: ...10 Change PIN code 11 Change IP address 11 Change IP gateway address 11 Change subnet mask 11 Change port number for TCP IP 11 Set exercise start delay 12 Show digital input status 12 Show digital out...

Page 2: ...oad the configuration file 15 Step 3 System test 15 Step 4 Set RTC 15 Step 5 Change Pin Code 15 Step 6 Activate watchdog 16 Step 7 Set time for automatic exit from Service Mode 16 Step 8 Switch the sy...

Page 3: ...ommand Digital I O MIDI SMOKE 2 includes four digital inputs to be connected to external open close contacts DI1 terminals 1 2 is the External Fire Input When the contact opens it will indicate Fire A...

Page 4: ...RATION OF WATCHDOG Tc 5 s WATCHDOG 30 s ENT SAVE FUNC TEST SETTINGS T W T F S S I FC1 M 06 00 SETTINGS OF CLOCK DATE 2012 02 10 16 30 FRIDAY SETUP RUN IND OPEN AT FUNC TEST MODULE ADDRESSING ENTER STA...

Page 5: ...STATUS FIRE RESET DI2 OPEN STATUS NIGHT MODE DI3 OPEN Only in Service Mode Not when using SmokeEdit From previous page Only in Service Mode Only in Service Mode Only in Service Mode Only in Service M...

Page 6: ...DO4 CLOSED SET SERVICE MODE TIMEOUT SET SIOX REPEATS EX2 VERSION EX2 v1 61 From previous page Only in Service Mode Only in Service Mode Only in Service Mode Only in Service Mode Only in Service Mode O...

Page 7: ...are version 1 61 it is also required that the communication watchdog be set for the OK LED to be lit To enter Service Mode press F2 and the following text on the display is shown Numbers in the pin co...

Page 8: ...ow adjusts the value Enter sends the value to all modules If the value is set to zero the function is deactivated This is useful during com missioning to stop dampers from closing unex pectedly due to...

Page 9: ...is being performed Module addressing Service Mode This setup menu is used for addressing damper control modules Every module in the system requires a unique address The address consists of a Group ad...

Page 10: ...les Then run the Simple system setup once again When the check passes the text OK CONFIGURATION FOR nn MODULES is displayed The next menu Module configuration will be entered Module configuration Serv...

Page 11: ...change the IP address for the PC or the MIDI SMOKE 2 Change IP gateway address Service Mode Introduced in firmware 1 40 If the unit will be connected to Ethernet the IP gateway address can be changed...

Page 12: ...ange Show digital input status Service Mode For each of the four digital inputs DI1 DI4 there is a menu showing current status to aid in fault tracing Show digital output status Service Mode For each...

Page 13: ...loaded with a configuration file MIDISMOKE_02 cfg intended for simpler systems where the key pad is used for setup These systems support up to a maximum of 59 damper modules addressed from 1 59 in a s...

Page 14: ...a mix of sum alarm night mode functional test and fire alarm If the Run indication relay output DO4 will be used it has to be configured for the desired combination of events otherwise go to the next...

Page 15: ...address set correctly Do this by clicking on the Modules tab and then right click on the Midi Smoke symbol and select Properties Check the watchdog time by clicking on the Modules tab and then right...

Page 16: ...n is approximately 3 5 W Connection of AC power The secondary transformer winding should be connected between terminals 13 G and 14 G0 Connection of DC power Connect the negative supply wire to termin...

Page 17: ...be connected to open close switches See page 1 for a functional description Digital Outputs There are four relay outputs on the MIDI SMOKE 2 Their breaking capacity is 1 A at 30 V AC DC They are norm...

Page 18: ...MidiSmoke2_ProdDescr_12en odt 2018 05 30 YE Profcon AB Page 18 www smokecontrol net...

Reviews: