Main menu
OK:
No alarms.
OK TEST: Functional damper test is in progress.
FIRE:
One or more alarm points detected
a fire alarm or one or more alarm
points are not answering.
B-ALARM: Service alarm from a smoke detector,
damper error from a damper module or
that one or more damper modules are
not answering.
NO APP:
No configuration is loaded, or halted.
Could happen if a Smoke Edit
download is aborted for some reason.
In that case just try to download again.
If a small “N” is displayed before the status text
then the system is in
Night
mode (dampers closed)
thru activation of DI3.
If “F1” is pressed, a text is displayed showing the
name of the configuration file. If the configuration
file is customer specified, the text displayed can be
freely chosen, e.g. to display the facility name of
the installation.
Service Mode
By pressing “F2” in the main menu it is possible to
enter the
Service Mode
.
In
Service Mode
outgoing fire alarms are blocked but shown in
the display to facilitate fault tracing.
Also,
dampers are opened and automatic or via DI4 re-
quested functional tests are suppressed. However,
functional tests (exercise) can still be requested via
the
Function test all dampers
menu, external DI-
modules or thru Modbus TCP
.
Unless the
Service Mode
is entered, only the
Alarms
menu
, Fire cells
menu and
Function test all
dampers
menu are available.
When the work is completed it is mandatory to
remember to exit the
Service Mode
by pressing
key “F2” and then “C” in the main menu.
If the green OK LED is on it indicates normal
alarm free operation and that
Service Mode
is
not active.
From system software version 1.61 it is also
required that the communication watchdog be
set for the OK LED to be lit.
To enter
Service Mode
, press “F2” and the
following text on the display is shown:
Numbers in the pin code are changed using the
arrow keys.
When the correct pin code is entered press
Enter
.
Default pin code is 5555.
Reset pin code to factory default
If the PIN code has been lost there is a recovery
method: Hold down the “
C”
key while restarting the
module (cycling the power). When the question
“RESET PIN CODE TO 5555? ENTER=OK”
is
shown, press
Enter.
Change language
If the
Service Mode
is active and the
Up
arrow is
pressed in the
Main
menu, a menu to change the
language is displayed. Press
Right
arrow to toggle
the alternatives Swedish and English. Confirm by
pressing
Enter
.
Alarms
Shows current alarms. Press
Enter
to display the
alarm list. Press
Down
arrow to advance to the
next alarm in the list or
Up
arrow to return to the
previous alarm. EXT.FIRE is the DI1 Fire Alarm
input on the MIDI SMOKE 2 module. DI2 must be
activated (>1,5 s) to unlatch this alarm.
Remember: ”
C”
backs one step in the menues
and/or aborts a command.
In system software version 1.62 a check was
introduced for a very rare error.
If the display shows “MODULE FAIL (SD)” it means
that the damper module on the address shown is
not defined as an Alarm Point but nevertheless is
in Fire status (and its dampers will be closed). The
reason for this is that the local smoke detector
input rises the alarm. Check that the resistor (2,2
kohm), which should be installed between
terminals 4 and 5 on an SC2-module is correctly
installed and that the terminal screws are
tightened.
Profcon AB
Page 7
www.smokecontrol.net
ALARM FIRE:OTHERS
EXT.FIRE 1:1
2018-02-20 15:26
SYSTEM: OK
PIN: 5555
C=EXIT SERV. MODE
MODULE FAIL (SD)
Address G:0 A:7