background image

Fire cells

The fire cell above includes two alarm points and
10 dampers. The “A” in “AP” is blinking. 

Right/Left

arrow  moves   the   cursor   between   “A”   and   “D”.
Pressing  

Up  

arrow  will   go   to   the   next   fire   cell.

Pressing  

Down  

arrow

 

will go to the previous fire

cell.   Pressing  

Enter

  will   show   a   list   of   the

predefined alarm points or dampers in the current
fire   cell   as   in   the   examples   below.   Press  

Down

arrow or  

Up

  arrow to move between the different

alarm points or dampers.

On top is shown the name of the alarm point. The
lower line shows its status. If it is a smoke detector,
a blinking “R” will be shown at the extreme right to
indicate   that   a   reset   command   can   be   sent   by
pressing 

Enter.

On   top   is   shown   the   name   of   the   damper.   The
lower line shows its status and end point indication
(“O” for open, “C” for closed). A blinking  “T” will be
shown   at   the   extreme   right   to   indicate   that   a
function test can be run by pressing 

Enter.

 

Function test all dampers

Pressing  

Enter

  will carry out a function test on all

connected damper modules. Normally the dampers
will start with a 5 seconds interval within each fire
cell.

Watchdog

 

(Service Mode)

This is  to   set   up   the  maximum  acceptable   com-
munication   interruption   time   before   a   module
enters fire alarm mode closing its local damper(s)
and   opening   its   local   alarm   relay.   Tc   is   a   value
describing  the  current  cycle  time   for  the  system.
The selected watchdog time must be higher than
Tc. The time can be set to 0 s, 30 s, 40 s, 50 s up
to 90 s in 10  s increments.  

If  damper modules

have   been   replaced   in   the   system   it   is

important   that   the   watchdog   configuration   is
repeated to initialize the new modules.

Up/Down 

arrow adjusts the value. 

Enter

 sends the

value to all modules. If the value is set to zero the
function is deactivated. This is useful during com-
missioning   to   stop   dampers   from   closing   unex-
pectedly due to disruptions in the execution of the
MIDI   SMOKE   2   controller.  A  cyclically   displayed
warning   text  

“WATCHDOG   INACTIVE”

  will   be

shown in the main menu (not if  

Service Mode  

  is

active)  to indicate this condition.  

At a convenient

point during the commissioning the watchdog
should   be   properly   set   so   that   dampers   will
close if the communication breaks down.

Functional test setup

 

(Service Mode)

To   configure   the   functional   test   setup,   press   the

Enter

 key.

The 

lower line

  shows which days to run a test of

the dampers in the current fire cell and the time of
day. Use the  

Left/Right

  arrows to change the day

position and also to enter the hours/minutes field.
Use the  

Up/Down  

arrows to pull the day letters to

the upper or lower line and to increase/decrease
the time.  If no weekdays are selected for damper
test the modules will be configured to do function
tests   on   their   own   at   48   hours   interval   (time
counting starts when they are powered up). If the
“I”   alternative   is   selected   and   no   weekdays   are
selected it means that the 48 hours interval in the
modules are inhibited. This choice is typically used
if the exercise should only be controlled by digital
inputs or thru Modbus TCP.

Press 

Enter

 when ready or “

C”

 to exit without modi-

fications.

If there are more fire cells to configure the next one
will   be   shown   in   the   order   they   appear   in   the
configuration file.

Default   time   for   functional   test   is   monday   06.00
hrs.

Profcon AB

Page 8

www.smokecontrol.net

FIRE CELL 1                

2  AP   10 DAMPERS   

DAMPER ST2_1          

  OK       O              T       

ALARM POINT 1        

    OK                        R       

 FUNC. TEST ALL
 DAMPERS? <ENTER>

WATCHDOG SETUP

  Tc = 3s                      

WATCHDOG              

30 s (ENT=SAVE)       

     M T  T F S S I   FC1          

            O                06:00          

FUNC.TEST              
SETTINGS       

Summary of Contents for MIDI SMOKE 2

Page 1: ...10 Change PIN code 11 Change IP address 11 Change IP gateway address 11 Change subnet mask 11 Change port number for TCP IP 11 Set exercise start delay 12 Show digital input status 12 Show digital out...

Page 2: ...oad the configuration file 15 Step 3 System test 15 Step 4 Set RTC 15 Step 5 Change Pin Code 15 Step 6 Activate watchdog 16 Step 7 Set time for automatic exit from Service Mode 16 Step 8 Switch the sy...

Page 3: ...ommand Digital I O MIDI SMOKE 2 includes four digital inputs to be connected to external open close contacts DI1 terminals 1 2 is the External Fire Input When the contact opens it will indicate Fire A...

Page 4: ...RATION OF WATCHDOG Tc 5 s WATCHDOG 30 s ENT SAVE FUNC TEST SETTINGS T W T F S S I FC1 M 06 00 SETTINGS OF CLOCK DATE 2012 02 10 16 30 FRIDAY SETUP RUN IND OPEN AT FUNC TEST MODULE ADDRESSING ENTER STA...

Page 5: ...STATUS FIRE RESET DI2 OPEN STATUS NIGHT MODE DI3 OPEN Only in Service Mode Not when using SmokeEdit From previous page Only in Service Mode Only in Service Mode Only in Service Mode Only in Service M...

Page 6: ...DO4 CLOSED SET SERVICE MODE TIMEOUT SET SIOX REPEATS EX2 VERSION EX2 v1 61 From previous page Only in Service Mode Only in Service Mode Only in Service Mode Only in Service Mode Only in Service Mode O...

Page 7: ...are version 1 61 it is also required that the communication watchdog be set for the OK LED to be lit To enter Service Mode press F2 and the following text on the display is shown Numbers in the pin co...

Page 8: ...ow adjusts the value Enter sends the value to all modules If the value is set to zero the function is deactivated This is useful during com missioning to stop dampers from closing unex pectedly due to...

Page 9: ...is being performed Module addressing Service Mode This setup menu is used for addressing damper control modules Every module in the system requires a unique address The address consists of a Group ad...

Page 10: ...les Then run the Simple system setup once again When the check passes the text OK CONFIGURATION FOR nn MODULES is displayed The next menu Module configuration will be entered Module configuration Serv...

Page 11: ...change the IP address for the PC or the MIDI SMOKE 2 Change IP gateway address Service Mode Introduced in firmware 1 40 If the unit will be connected to Ethernet the IP gateway address can be changed...

Page 12: ...ange Show digital input status Service Mode For each of the four digital inputs DI1 DI4 there is a menu showing current status to aid in fault tracing Show digital output status Service Mode For each...

Page 13: ...loaded with a configuration file MIDISMOKE_02 cfg intended for simpler systems where the key pad is used for setup These systems support up to a maximum of 59 damper modules addressed from 1 59 in a s...

Page 14: ...a mix of sum alarm night mode functional test and fire alarm If the Run indication relay output DO4 will be used it has to be configured for the desired combination of events otherwise go to the next...

Page 15: ...address set correctly Do this by clicking on the Modules tab and then right click on the Midi Smoke symbol and select Properties Check the watchdog time by clicking on the Modules tab and then right...

Page 16: ...n is approximately 3 5 W Connection of AC power The secondary transformer winding should be connected between terminals 13 G and 14 G0 Connection of DC power Connect the negative supply wire to termin...

Page 17: ...be connected to open close switches See page 1 for a functional description Digital Outputs There are four relay outputs on the MIDI SMOKE 2 Their breaking capacity is 1 A at 30 V AC DC They are norm...

Page 18: ...MidiSmoke2_ProdDescr_12en odt 2018 05 30 YE Profcon AB Page 18 www smokecontrol net...

Reviews: