Setting up date/time

 

(Service Mode)

The value to change is blinking.  

Right/Left

  arrows

moves the cursor between year,  month, day etc.

Up/Down

  arrows  increases/decreases   the   value.

Press  

Enter

  when   done.   Press   “

C”

  key   to   exit

without modifications.

Run   indication   relay  output/Operational   mode

(Service Mode)

There   are   15   possible   functions   for   the   run
indication   relay   output   DO4.   Change   mode   with

Right / Left 

arrow

:

OPEN AT FUNC.TEST – relay opens as long as at
least one module is performing a function test.
OPEN AT NIGHT – relay opens if system is in night
mode.
NIGHT+FUNC.TEST – relay opens if system is in
night mode or a function test is performed.
OPEN AT SUM ALARM – relay opens if there is
any   damper   error   or   communication   error   in   the
system.
SFUNCTEST – relay opens if there is
any   damper   error   or   communication   error   in   the
system or a function test is performed.
SNIGHT - relay opens if there is any
damper error or communication error or if system
is in night mode.
SUM+NIGHT+F.TEST – relay opens if there is any
damper or communication error, or if the system is
in night mode or a function test is being performed.
OPEN AT FIRE – relay opens in case of fire alarm.
FIRE+FUNC.TEST – relay opens in case of a fire
alarm or a function test is being performed.
FIRE+NIGHT – relay opens if case of a fire alarm
or if system is in night mode.
FIRE+NIGHT+F.TEST - relay opens in case of a
fire alarm, or if the system is in night mode or a
function test is being performed.
FIRE+SUMALARM - relay opens if there is a fire
alarm, a damper error or a communication error in
the system.
FIRE+SUM+F.TEST -  relay opens in case of a fire
alarm   or   if   there   is   a   damper   or   communication
error in the system or a function test is being per-
formed.
FIRE+SUM+NIGHT - relay opens in case of a fire
alarm,   a   damper   or   communication   error   in   the
system or if the system is in night mode.
FIRE+SUM+NIGHT+FT - relay opens in case of a
fire alarm, a damper or communication error in the
system, or if system is in night mode or a function
test is being performed.

Module addressing

 

(Service Mode)

This  setup   menu  is  used   for  addressing  damper
control   modules.   Every   module   in   the   system
requires a unique address. The address consists of
a  

Group

  address   and   a  

Module

  address.   The

Group

  address   is   either   zero   which   is   used   to

address the first 1-59 damper modules or it could
be   61,   62   or   63   that   defines   three   possible
addressing subgroups  

(only available if SMOKE

EDIT is used)

. Each group can handle up to 59

damper modules (less if other modules are used
as well).

Please note that if digital I/O-modules are used, for
example   S27,   they   should   be   addressed   from
address   59   and   downwards.   This   means   that
correspondingly   fewer   damper   modules   can   be
installed on group zero.

All modules are at  

Group

  address 0 and  

Module

address 1 when they are delivered from factory.

Press 

Enter

 to select Module addressing menu.

The modules should be addressed in the interval
1-59,   that's   why   the   addressing   starts   at   1.   If
another start address is desired, just change it by
pressing the 

Up/Down

 arrows to increase/decrease

and 

Left/Right

 arrows to move between 

Group

 and

Module

 address.

When  

Enter

  is pressed the MIDI SMOKE 2 starts

to send addressing commands. All damper control
modules LEDs will start to flash (3 fast on/off). By
pressing the test button on a module it accepts the
address sent by MIDI SMOKE 2. The address in
the   display   now   increments   to   the   next   address
and the next module in order can be addressed.
Note that no automatic wrap occurs to next 

Group

address   when  

Module

  address   59   has   been

passed. It will stay at address 59. If sub-buses are
used,   restart   the   command   and   increase   the

Group

  address to the desired  

Group

  address (61,

62, 63). Please note that pressing 

Down

 arrow is a

quick   way   to   reach   the   high  

Group

  address

numbers   (0->63->62->61).   Adjust   the  

Module

address   to   the   desired   start   address   before
pressing  

Enter

  to   start   the   transmission   of   the

addressing commands.

Apply a distinct press on the buttons to avoid
double-activations   which  otherwise   will   result
in an address increment and a wrong address

Profcon AB

Page 9

www.smokecontrol.net

2018-02-20  16:30        

  WEDNESDAY               

SETUP RUN IND.

OPEN ON ERROR

ENTER = START          

GROUP:0    ADDR:1     

MODULE ADDRESSING

Summary of Contents for MIDI SMOKE 2

Page 1: ...10 Change PIN code 11 Change IP address 11 Change IP gateway address 11 Change subnet mask 11 Change port number for TCP IP 11 Set exercise start delay 12 Show digital input status 12 Show digital out...

Page 2: ...oad the configuration file 15 Step 3 System test 15 Step 4 Set RTC 15 Step 5 Change Pin Code 15 Step 6 Activate watchdog 16 Step 7 Set time for automatic exit from Service Mode 16 Step 8 Switch the sy...

Page 3: ...ommand Digital I O MIDI SMOKE 2 includes four digital inputs to be connected to external open close contacts DI1 terminals 1 2 is the External Fire Input When the contact opens it will indicate Fire A...

Page 4: ...RATION OF WATCHDOG Tc 5 s WATCHDOG 30 s ENT SAVE FUNC TEST SETTINGS T W T F S S I FC1 M 06 00 SETTINGS OF CLOCK DATE 2012 02 10 16 30 FRIDAY SETUP RUN IND OPEN AT FUNC TEST MODULE ADDRESSING ENTER STA...

Page 5: ...STATUS FIRE RESET DI2 OPEN STATUS NIGHT MODE DI3 OPEN Only in Service Mode Not when using SmokeEdit From previous page Only in Service Mode Only in Service Mode Only in Service Mode Only in Service M...

Page 6: ...DO4 CLOSED SET SERVICE MODE TIMEOUT SET SIOX REPEATS EX2 VERSION EX2 v1 61 From previous page Only in Service Mode Only in Service Mode Only in Service Mode Only in Service Mode Only in Service Mode O...

Page 7: ...are version 1 61 it is also required that the communication watchdog be set for the OK LED to be lit To enter Service Mode press F2 and the following text on the display is shown Numbers in the pin co...

Page 8: ...ow adjusts the value Enter sends the value to all modules If the value is set to zero the function is deactivated This is useful during com missioning to stop dampers from closing unex pectedly due to...

Page 9: ...is being performed Module addressing Service Mode This setup menu is used for addressing damper control modules Every module in the system requires a unique address The address consists of a Group ad...

Page 10: ...les Then run the Simple system setup once again When the check passes the text OK CONFIGURATION FOR nn MODULES is displayed The next menu Module configuration will be entered Module configuration Serv...

Page 11: ...change the IP address for the PC or the MIDI SMOKE 2 Change IP gateway address Service Mode Introduced in firmware 1 40 If the unit will be connected to Ethernet the IP gateway address can be changed...

Page 12: ...ange Show digital input status Service Mode For each of the four digital inputs DI1 DI4 there is a menu showing current status to aid in fault tracing Show digital output status Service Mode For each...

Page 13: ...loaded with a configuration file MIDISMOKE_02 cfg intended for simpler systems where the key pad is used for setup These systems support up to a maximum of 59 damper modules addressed from 1 59 in a s...

Page 14: ...a mix of sum alarm night mode functional test and fire alarm If the Run indication relay output DO4 will be used it has to be configured for the desired combination of events otherwise go to the next...

Page 15: ...address set correctly Do this by clicking on the Modules tab and then right click on the Midi Smoke symbol and select Properties Check the watchdog time by clicking on the Modules tab and then right...

Page 16: ...n is approximately 3 5 W Connection of AC power The secondary transformer winding should be connected between terminals 13 G and 14 G0 Connection of DC power Connect the negative supply wire to termin...

Page 17: ...be connected to open close switches See page 1 for a functional description Digital Outputs There are four relay outputs on the MIDI SMOKE 2 Their breaking capacity is 1 A at 30 V AC DC They are norm...

Page 18: ...MidiSmoke2_ProdDescr_12en odt 2018 05 30 YE Profcon AB Page 18 www smokecontrol net...

Reviews: