background image

DCN: 140-02302-01 

Page 9 

 

Installer Settings Summary 

 

Setting 

Range 

Default 

 

Display Lock 

Y or N 

Locks out front buttons 

Service Mode Submenu 

 

 

 

   Test Mode 

Y or N 

Reduces delays for testing 

System Settings Submenu 

 

 

 

Mechanical Settings Submenu 

 

 

 

   Sys Type 

Std or HP 

Std 

 

   Fan Type 

Gas or Elec 

Gas 

 

   C/O Type 

w/Heat or w/Cool 

w/Cool 

 

   2

nd

 Stage Heat 

Y or N 

 

   Aux Heat 

Y or N 

 

    2

nd

 Stage Cool 

Y or N 

 

H/C Delta 

3 – 15 deg 

 

Heat Delta Stage 1 On 

1 – 8 

 

Heat Delta Stage 1 Off 

0 – 8 

 

Heat Delta Stage 2 On 

1 – 8 

 

Heat Delta Stage 2 Off 

0 – 8 

 

Heat Delta Stage 3 On 

1 – 8 

 

Heat Delta Stage 3 Off 

0 – 8 

 

Cool Delta Stage 1 On 

1 – 8 

 

Cool Delta Stage 1 Off 

0 – 8 

 

Cool Delta Stage 2 On 

1 – 8 

 

Cool Delta Stage 2 Off 

0 – 8 

 

Max Heat SP 

40-109F (4-42C) 

90F 

 

Min Cool SP 

44-113F (6-45C) 

60F 

 

Min Run Time 

1-9 min 

 

Min Off Time 

1-9 min 

 

Temp Response 

1-6 

 

Remote Sensors Submenu 

 

 

 

   RS1 Type (curve type) 

Curve A, Type 2, Type 3 

Type 3 

 

   RS2 Type (curve type) 

Curve A, Type 2, Type 3 

Type 3 

 

   RS2 Location (Indoors or Outdoors) 

In, Out 

In 

 

 

 

 

 

Restore Defaults (factory defaults) 

Yes or No 

No 

Exit = no 

 

 

 

 

USER SETTINGS

 

 

 

 

Filter Service Submenu 

 

 

 

   Service Interval

 

Disabled, 100-4000 hrs 

300 

 

Maint Service Submenu

 

 

 

 

   Maint Interval 

Disabled, 100-4000 hrs 

3000 

 

Screen Timeout (to minimized screen) 

0, 20-120 sec 

0 = off , will not timeout  

RH Setpoint 

40-70% 

50% 

 

F/C Settings 

F or C  

 

Sensor Calibration Submenu 

Internal -7 to +7 

 

Backlite/Display Submenu 

 

 

 

   Backlight Timeout 

0, 20-120 

0 = backlite off 

   Backlight On Brightness 

0-100% 

100% 

 

   Backlight Off Brightness 

0-100% 

0% 

 

   Contrast 

0-20 

12 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DCN: 140-02302-01 

Page 10 

 

Connection to Mi-Wi Network 

This thermostat is designed to connect to the SiteSage Gateway using the Mi-Wi wireless 

protocol.  The Gateway will automatically detect a thermostat and initiate the connection. 

See the SiteSage Installation Manual for additional details. 

 

 

It is critical that the MAC address of the thermostat is mapped to the 

name of the zone served by the thermostat. The Thermostat MAC 

address can be found in the Mi-Wi Network menu option (the last 

one in the list of options shown when the Menu Button is selected. 

 

Summary of Contents for TM46

Page 1: ...re to set the change over type in the Installer Settings menu to C O Type w Heat Otherwise leave it set to w Cool DCN 140 02302 01 Page 2 Standard HVAC System G Fan W1 Heat Stage 1 Y1 Compressor Stage 1 R 24VAC Return C 24VAC Common Thermostat Connection Y2 Compressor Stage 2 W2 Heat Stage 2 Optional 24R Connection for single transformer HVAC Systems RC and RH are jumpered together on thermostat b...

Page 2: ...d Stage Cool Enable second stage cooling outputs If you have a single stage cooling system leave this set to N If you have a two stage cooling system set to Y to enable 24RC W1 24RH W2 O RS1 RS1 RSC 24C Cooling 24V Fan Cooling stage 1 Cooling stage 2 Remote Sensor 2 Remote Sensor 2 Sensor shield 24VAC Com 24V Heating Aux Heating Change Over Valve Remote Sensor 1 Remote Sensor 1 Sensor shield Remot...

Page 3: ...N these settings affect HVAC system operation and should only be changed by qualified HVAC service technicians Installer Settings Menu Items Display Lock Options Y or N Default N Y Display LOCKED N Display UNLOCKED Allows you to lock or unlock the thermostat buttons When the buttons are locked you can still access the main menu but you will not be allowed to select any menu options The Installer S...

Page 4: ... or accept setpoints higher that this maximum Options 40F to 109F 4C 43C Default 90F 32C Min Cool SP Sets the minimum cooling setpoint value Will not ramp or accept setpoints lower than this minimum Options 44F to 113F 6C 45C Default 60F 15C Min Run Time MRT Sets the minimum run time before a heating cooling cycle turns off Sets heating cooling cycle time Prevents rapid cycling Options 1 9 Minutes...

Page 5: ... 2 Type 3 Type 3 RS2 Location Indoors or Outdoors In Out In Restore Defaults factory defaults Yes or No No Exit no USER SETTINGS Filter Service Submenu Service Interval Disabled 100 4000 hrs 300 Maint Service Submenu Maint Interval Disabled 100 4000 hrs 3000 Screen Timeout to minimized screen 0 20 120 sec 0 0 off will not timeout RH Setpoint 40 70 50 F C Settings F or C F Sensor Calibration Submen...

Page 6: ...n Auto mode the mode of the last system call will be the setpoint screen displayed Setpoint Push Note that you cannot lower the cooling setpoint below the heating setpoint The thermostat will push the heating setpoint lower if you try to lower the cooling setpoint below the heating setpoint It maintains a 3 degree separation between the heating and cooling setpoint The same is true for raising the...

Page 7: ...ors Optional Fan Mode Fan Cycler If the Fan Cycler feature is enabled in the Installer Setup the additional fan mode Cycle will be shown in the Fan Mode menu This mode cycles the fan on and off continuously for fresh air ventilation according to the settings in the Installer Setup System Status Indicators When the main thermostat screen is displayed the on screen labels indicate the following Syst...

Page 8: ... menu item to load the Comfort schedule into the thermostat Confirmation screen will be displayed for Yes No entry Preset EnergyMiser This is a preset schedule with deeper setbacks Select this menu item to load the EnergyMiser schedule into the thermostat Confirmation screen will be displayed for Yes No entry Day Schedule Screen When you select the Heat and Cool Schedule menu item the day schedule...

Page 9: ...een and the current number of degrees of offset being applied typically 0 If the sensor s actual temp is 75 with 0 degrees of offset and you want it to display 76 then press to add 1 deg and it will indicate 76 in the display with 1 deg offset You can refresh the info on this screen by pressing the right hand blank button When you close this screen it may take a few seconds for the temperature dis...

Page 10: ...it does not respond immediately due to another call that has recently completed and the MOT delay timer is preventing the system from restarting The MOT delay time can be adjusted in the Installer Settings menu of the thermostat There is a minimum of 5 minutes delay to assure compressor protection Note The MOT status is shown in the thermostat System Status on screen labels DCN 140 02302 01 Page 2...

Page 11: ...quipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Any chan...

Reviews: