Installing the Float Switches
The Model 112 Single Phase Simplex control panel operates with
3 float switches to activate pump STOP, START, and high-level
ALARM functions.
Mounting the Control Panel
1
2
3
CAUTION!
NOTE
Ensure all power is turned OFF
before installing floats in tank.
Failure to do so could result in
serious or fatal shock.
Label each float and cord
end with the provided pairs
of STOP, START, and ALARM
stickers.
If the distance to the control panel exceeds the length of
the float switch cords or the pump power cord, splicing
in a liquid-tight junction box will be required. For outdoor
or wet installation, we recommend an SJE Rhombus UL
Type 4X junction box.
2
Make sure hose clamp
band does not interfere
with float operation.
Do not install cord under
hose clamp.
Tighten
the
clamp.
Hose clamp is 18-8
stainless steel.
If the floats are not properly mounted and connected in the correct
order, the pumps will not function properly.
Floats require free range of motion.
They must not touch each other or any equipment in the pump chamber.
START
RED. OFF
STOP
STOP
START
RED. OFF
ALARM ALARM
Lag/Alarm
Stop
Stop
Stop
Lag/Alarm
Lead
Lead
Lead
Lag/Alarm
Operating
range
Start
Start
Alarm
Alarm
Alarm
Lag/Alarm
Stop
Stop
Stop
Lag/Alarm
Lead
Lead
Lead
Lag/Alarm
Operating
range
Start
Pipe Clamp Mounting -
Float Operation
3.5”
(9cm)