SJE
®
11 SP6R-X Controller User Manual
SP6R-X I/O TABLE
J1 POWER AND COMMUNICATIONS
PIN
NAME
DESCRIPTION
1
N/C
- NO CONNECTION -
2
N/C
- NO CONNECTION -
3
0V
RETURN FOR +24 VDC SUPPLY
4
+24 VDC
19 - 28 VDC SUPPLY
5
D+
MODBUS (RS-485 NON-INVERTING)
6
D-
MODBUS (RS-485 INVERTING)
7
SHIELD
8
A OUT
4-20 mA LOOP, POWER SUPPLIED
9
AO COM
4-20 mA LOOP RETURN
10
N/C
- NO CONNECTION -
11
GND
PROTECTIVE EARTH GROUND
12
GND
PROTECTIVE EARTH GROUND
J2 RELAY OUTPUTS
PIN
NAME
DESCRIPTION
1
R1
PROGRAMMABLE RELAY #1
2
3
R2
PROGRAMMABLE RELAY #2
4
5
R3
PROGRAMMABLE RELAY #3
6
7
R4
PROGRAMMABLE RELAY #4
8
9
R5
PROGRAMMABLE RELAY #5
10
11
R6
PROGRAMMABLE RELAY #6
12
J3 DIGITAL INPUTS
PIN
NAME
DESCRIPTION
1
GND
2
RESERVED
3
RESERVED
4
RESERVED
5
RESERVED
6
RESERVED
7
RESERVED
8
RESERVED
9
RESERVED
10
RESERVED
11
RESERVED
12
RESERVED
13
SHIELD
14
AI COM
4 - 20 mA LOOP RETURN
15
A INPUT
4 - 20 mA LOOP INPUT
16
+24 VDC OUT
LEVEL TRANSMITTER SUPPLY
Note:
Pins J1-3, J1-7, J1-11, J1-12, J3-1, J3-13 and
J3-14 are all internally connected, and should
be wired to Protective Earth Ground at terminal
J1-11 or J1-12.
Use Copper Conductors, rated 60°C (140°F)
Apply Torque Value of 4.5 In-lbs to Field Wiring
Terminals.