SJE
®
13 SP6R-X Controller User Manual
The following is a list of all accessible Modbus registers.
Access Type
Holding
Register
Number
Holding
Register
Address
Bit
Description
Unit of Measure (Other Notes)
Read
2005
42006
Input Level Reading
Tenths of Units
Read
2006
42007
Input mA
Hundredths of mA
Read
2007
42008
Output mA
Read/Write
2008
42009
Units
0=ft, 1=in, 2=m, 3=cm, 4=psi, 5=bar, 6=kPa,
7=%, 8=°C, 9=°F, 10=GPM, 11=m³/hr, 12=V,
13=A, 14=mA, 15=none
Read/Write
2009
42010
R1 Out-of-Range Behavior
0=Relay Open, 1=Relay Closed
Read/Write
2010
42011
R2 Out-of-Range Behavior
Read/Write
2011
42012
R3 Out-of-Range Behavior
Read/Write
2012
42013
R4 Out-of-Range Behavior
Read/Write
2013
42014
R5 Out-of-Range Behavior
Read/Write
2014
42015
R6 Out-of-Range Behavior
Read
2023
42024
0
Relay 1 Status
0=Relay Open, 1=Relay Closed
1
Relay 2 Status
2
Relay 3 Status
3
Relay 4 Status
4
Relay 5 Status
5
Relay 6 Status
6-15
--not used--
Read/Write
2025
42026
Analog Input (4mA)
Tenths of Units
Read/Write
2026
42027
Analog Input (20mA)
Read/Write
2027
42028
Transmitter Offset
Read/Write
2028
42029
Bar Graph Maximum
Read/Write
2029
42030
Bar Graph Maximum
Read/Write
2031
42032
Relay 1 On Setpoint
Read/Write
2032
42033
Relay 1 Off Setpoint
Read/Write
2033
42034
Relay 2 On Setpoint
Read/Write
2034
42035
Relay 2 Off Setpoint
Read/Write
2035
42036
Relay 3 On Setpoint
Read/Write
2036
42037
Relay 3 Off Setpoint
Read/Write
2037
42038
Relay 4 On Setpoint
Read/Write
2038
42039
Relay 4 Off Setpoint
Read/Write
2039
42040
Relay 5 On Setpoint
Read/Write
2040
42041
Relay 5 Off Setpoint
Read/Write
2041
42042
Relay 6 On Setpoint
Read/Write
2042
42043
Relay 6 Off Setpoint