SJE®
25
VFDC-4100 Controller User Manual
Control setup
1: pvalue
R
8301
33,537
pvalue
2: ivalue
R
8302
33,538
ivalue
3: dvalue
R
8303
33,539
dvalue
4: cycle time
R
8304
33,540
cycle time
5: alternation
R
8305
33,541
shift
6: friction
R
8306
33,542
friction
7: run delay
R
8307
33,543
sec
8: stop delay
R
8308
33,544
sec
9: jockey stop delay
R
8309
33,545
sec
10: operation
R
830A
33,546
x
11: low suction TMR
R
830B
33,547
sec
12: Low suction RST
R
830C
33,548
N/A
Sensor setup
1: trans type
R
8401
33,793
trans type
2: sensor adjust
R
8402
33,794
sensor adjust
VFD setup
1: VFD stop time
R
8501
34,049
sec
2: VFD minimum rate
R
8502
34,050
%
3: VFD stop rate
R
8503
34,051
%
4: VFD display type
R
8504
34,052
%
5: VFD auto rest
R
8505
34,053
no.
Protection setup
1: freeze prevention
R
8601
34,305
0: not used , 1: used
2: fix prevention
R
8602
34,306
0: not used , 1: used
3: password use
R
8603
34,307
0: not used , 1: used
4: password
R
8604
34,308
0: not used , 1: used
Error count
high pressure alarm count
R
9002
36,866
no.
low pressure alarm count
R
9004
36,868
no.
low water alarm count
R
9006
36,870
no.
VFD1 alarm count
R
9008
36,872
no.
VFD2 alarm count
R
900A
36,874
no.
VFD3 alarm count
R
900C
36,876
no.
VFD4 alarm count
R
900E
36,878
no.
VFD1~4 all alarm count
R
9010
36,880
no.