background image

11

SERENE SC112N-A

Electronic Controller

Service Manual

Programming the Electronic Controller

Parameters

The parameter configuration program is set by SKOPE at the factory. A label 
on the controller box indicates the parameter configuration program number 
(e.g. the SC112N-A chiller uses program ‘102’).

The electronic controller parameters can be modified using the keypad. 
Access to the parameters is protected by a password to prevent accidental 
or unauthorised modifications. Only an authorised service agent should 
modify the parameters.

To access the parameters

1. Press and hold the 

Set (mute)

 button for 5 seconds until the display shows 

PS

’ (password)

2. Press the 

Set (mute)

 button. The display shows ‘

0

’. 

3. Use the 

ES (up)

 and 

Light (down)

 buttons to select password ‘

22

’ (default 

password). 

4. Press the 

Set (mute)

 button to confirm the password. The display shows 

PS

’.

5. Use the 

ES (up)

 and 

Light (down)

 buttons to scroll the parameter codes and 

locate the required parameter.

Parameter categories can be identified by the initial symbol or letter of the 
code, and the icon displayed on the electronic controller faceplate:

6. Press the 

Set (mute)

 button to display the value associated with the 

parameter code.

7. Use the 

ES (up)

 and 

Light (down)

 buttons to increase or decrease the value 

of the parameter.

8. Press the 

Set (mute)

 button to temporarily save the new value. The display 

shows the parameter code.

Note: 

If no buttons are pressed for 60 seconds or the power is disconnected 

before the temporarily saved values are permanently saved, the temporarily 
saved values will be cancelled and the previous setting will be restored. 

9. If necessary, repeat steps 5 - 9 to change other parameters as required.

10. Press and hold the 

Set (mute)

 button for 3 seconds to permanently save the 

parameters and exit the parameter menu.

Category

Initial

Icon

Probe parameters

/

-

Control parameters

r

-

Compressor parameters c
Defrost parameters

d

Alarm parameters

A

Fan parameters

F

Summary of Contents for Serene SC112N-A

Page 1: ...Service Manual MAN80301 Rev 1 0 Mar 2021 SC112N A SERENE Four Glass Sided Chiller Type HSC112N Z156 from SKOPE...

Page 2: ...site www skope com Trademark Infringement The SKOPE trademark on this product is infringed if the owner for the time being does any of the following Applies the trade mark to the product after their s...

Page 3: ...Cycle 9 Lighting 9 Messages and Alarms 10 Controller Display 10 Programming the Electronic Controller 11 Parameters 11 4 Wiring Model SC112N A 14 Notes 15 5 Spare Parts Cabinet Assembly 16 Parts Cabi...

Page 4: ...y 27 Refrigeration System Access 28 Refrigeration System Dismantling 29 Evaporator Fan 31 Condenser Fan 31 Power Supply and Surge Protector 32 Compressor 32 Compressor Electrics 33 Electronic Controll...

Page 5: ...00a is a natural refrigerant that has a very low environmental impact Special service requirements are needed as R600a is a flammable refrigerant Safety hazards The main R600a safety hazards are Flamm...

Page 6: ...stem Bottom mounted integral electronically controlled refrigeration system Electronic controller CAREL S4 Refrigerant R600a 40g natural refrigerant Operating temperature range 0 C to 5 C Tested clima...

Page 7: ...It uses two temperature probes within the refrigeration system to collect data and runs the chiller accordingly The electronic controller is pre programmed SKOPE does not recommend that the settings...

Page 8: ...for 3 seconds to switch the chiller between Energy Save and Normal mode 3 Set mute Press to mute the alarm Press and hold to access parameters 4 Light down Press and hold to switch the cabinet lights...

Page 9: ...s feed data to the electronic controller the control probe and the evaporator probe The control probe controls the chiller temperature provides the chiller temperature for the electronic controller to...

Page 10: ...ler is in Energy Saving mode When in Energy Saving mode the temperature inside the chiller is moderated and the cabinet lights turn off The lights can be switched on and off by pressing the light butt...

Page 11: ...up and Light down buttons to scroll the parameter codes and locate the required parameter Parameter categories can be identified by the initial symbol or letter of the code and the icon displayed on t...

Page 12: ...eters CCt 2 0 C C 0 1 20 0 Cold Climate Protection Temperature Delta CCd 30 mins C 0 199 Cold Climate Protection Delay Pull Down Mode Parameters Pt 127 C C 0 127 Pull down Mode Activation Temperature...

Page 13: ...ion A12 3 C 0 16 Number of cA alarm events to trigger manual reset CA alarm A13 24 hrs C 0 240 cA alarm counter reset delay A14 60 mins C 0 240 cA alarm reset delay A15 1 C 0 1 Lights switched OFF whe...

Page 14: ...d Surge Protector BN BU GNYE BN BN BN BK BU BU BN M BU 12Vdc Power Supply N L M BK RD BU WH 12Vdc Power Supply N L RD BU BK RD RD BK All Cabinet Lighting Evap Temp Probe Cabinet Temp Probe BU Evaporat...

Page 15: ...15 SERENE SC112N A Wiring Service Manual Notes...

Page 16: ...16 Spare Parts Service Manual SERENE SC112N A 5 Spare Parts Cabinet Assembly 1 1 2 2 3 3 4 4 5 6 6 7 8 9 10 11 12 13 14 15 16 16 17 17 18 19 20 21 5...

Page 17: ...ic controller CAREL S4 ELZ11478 102 Control probe ELZ1255 Evaporator probe ELZ7644 Door switch including cable magnet HB0074091496 9 Controller insert HB0070204937 10 Shelf clip HB0070204928 11 Wire s...

Page 18: ...18 Spare Parts Service Manual SERENE SC112N A Refrigeration System Assembly 1 2 3 4 5 6 7 8 8 8 9 10 11 11 11 12 13 14 15 16 16 16 17 19 18...

Page 19: ...12Vdc power supply HB0071800202 7 Evaporator coil HB0070700492 8 Lower outer extrusion HB0070109356A 9 PTC starter HB0074000381FJ 10 Wanbao Compressor ETA110L HB0074000910 11 Adjustable foot HB007010...

Page 20: ...ith four shelf clips which engage in the corner shelf support strips To adjust the cabinet shelves 1 Remove the shelves from the chiller 2 Remove the shelf clips from the four shelf support strips at...

Page 21: ...a the light switch on the electronic controller see page 9 before replacing LED strip lighting Interior lights The cabinet interior is lit by four vertical corner pillar LED lights Each corner pillar...

Page 22: ...ee page 17 for spare parts To replace a bottom sign light 1 Isolate the chiller from the power supply by unplugging from the wall socket 2 Remove the lower bottom panel by undoing the three fixing scr...

Page 23: ...out of shape after you fit it use a hair dryer to heat and reshape it Removing and Fitting Doors For ease of servicing the doors can be removed from the chiller To remove a door To refit a door Figur...

Page 24: ...torsion bar 1 Isolate the chiller from the power supply by unplugging from the wall socket 2 Remove door from the cabinet see page 23 3 Refit door to cabinet see page 23 adjusting the tension via the...

Page 25: ...ompressor oil Asphyxiation Refrigerant identification The cabinet rating label located in the upper inside of the cabinet states the refrigerant type In addition to this warning labels are fitted to h...

Page 26: ...ration gauge set suitable for R290 flammable refrigerant Bullet valves line piercing valves suitable for 6mm tube Service vehicle Suitable for transporting flammable gas being HC refrigeration systems...

Page 27: ...Verify basic requirements before servicing Refrigeration Unit Assembly Compressor Wanbao Compressor ETA110L Compressor capacity 250 Watts Refrigerant R600a Charge 40g Bottom sign lights cables Evapora...

Page 28: ...upply by unplugging from the wall socket 2 Remove the front and back lower bottom panels by undoing the three fixing screws and sliding them down and remove the sign panel and decal from the sign 3 Re...

Page 29: ...for a second person to hold the bottom refrigeration system while separating 1 2 3 4 Fixing screw Fixing screw Level Components and parts 1 bottom Compressor compressor electrics condensate tray cond...

Page 30: ...e Components on level two can now be accessed 6 Remove the two horizontal struts from the sides of the refrigeration system by undoing the two fixing screws from each strut 7 Detach the mains flexible...

Page 31: ...from the power supply separate the top cabinet assembly from the bottom refrigeration system and gain access to level two of the refrigeration system see page 29 2 Trace evaporator fan cable and unpl...

Page 32: ...over 220 volts Ensure the voltage does not drop at start up If the voltage does drop ensure the refrigeration system has a direct power supply not from a multi box or extension cord To access the comp...

Page 33: ...ated at the front of the chiller behind the lower bottom panel and is visible from the front of the chiller For information on operation and programming refer to the Electronic Controller section of t...

Page 34: ...wn 3 The terminals at the rear of the electronic controller can now be accessed 1 Follow the steps above to access the rear of the electronic controller 2 Unplug the terminals from the rear of the con...

Page 35: ...stem and gain access to level three of the refrigeration system see page 29 2 Gain access to the terminals at the rear of the electronic controller see page 34 3 Unclip and detach the control probe an...

Page 36: ...e electronic controller Unplug from the controller 6 Attach the new evaporator probe cable to the terminals at the rear of the electronic controller and fit the cable following the same path as the or...

Page 37: ...er faceplate Electronic controller displays Err indicating a refrigeration system error Arrange service call Failed LED light Arrange service call Product is too warm Frequent door opening Limit door...

Page 38: ...SKOPE Contacts SKOPE Industries Limited A B N 73 374 418 306 AU 1800 121 535 NZ 0800 947 5673 skope skope com www skope com...

Reviews: