19
SK650-2
SKOPE Gen2: Single Door Chiller
3.6 Replacement
If the SKOPE electronic controller has a suspected fault, care must
be taken to ensure accurate diagnosis. The controller has various
programmable parameters that effect operation such as time delay
and defost modes. Any suspected failure must be double checked.
Confirm all wiring and terminations are correct. Check probe resist-
ance is correct, and replace any faulty components.
Controller NTC probe resistance
Temperature
Resistance
(Ohms)*
-10°C
42.5
-5°C
34.0
0°C
27.3
5°C
22.1
10°C
18.0
20°C
12.1
30°C
8.3
40°C
5.8
50°C
4.2
* Tolerance: plus or minus
2.4%
Table 6: NTC Probe Resistance
ELECTRONIC CONTROLLER
3
Figure 3:
Controller Housing (open)
Electronic Controller
Controller
Housing
Parameter Configuration Label