SKOPE Gen2: Single Door Chiller
4.6 Troubleshooting
Complaint
Possible Cause
Repair
6. Unit runs OK,
but short
cycles.
Overload protector.
Check compressor overload
and relay.
Thermostat: requires adjustment or
incorrectly positioned.
Adjust or relocate thermostat
probe.
7. Unit operates
long or continu-
ously.
Unsatisfactory
cabinet tem-
perature.
Short of refrigerant.
Fix leak, and add charge.
Overcharge of refrigerant.
Remove refrigerant to correct
charge.
Thermostat not reading
temperature correctly.
Check air temperature with
thermometer. Adjust offset if
required.
Evaporator has excessive load.
Establish load within limits.
Evaporator coil iced.
Defrost evaporator, check
refrigeration. Check
thermostat. Check door
closing, seals etc. Check
defrost.
Restriction in refrigeration system.
Determine location and clear
restriction. Flush with dry
nitrogen. Replace component
if blockage will not clear.
Dirty condenser.
Clean condenser. Advise client
how to regularly clean
condenser.
Inadequate air circulation.
Internal: Improve air
movement, allow airflow
around stock.
External: Remove any
restrictions to condensing
ventilation.
Compressor not pumping
efficiently.
Replace compressor.
Filter dirty (if applicable).
Clean or replace.
Faulty fan motor.
Check rotation. Replace if
necessary.
SERVICE INSTRUCTIONS
4
Table 8: Troubleshooting (continued on next page)