DOL 635 • DOL 639
User Manual
43
6 Alarms
Alarms only work when the status is
Active house
.
The only exceptions are alarm test and alarms for CAN communication and temperature surveil-
lance for
Empty house
.
When an alarm occurs, the house controller will register the
alarm type and the time it occurred.
The information on the type of alarm will appear in a separate
alarm window together with a short description of the alarm situ-
ation.
The alarm relay is only trigged by hard alarms.
Soft alarms generate a pop-up in the display.
Red: active alarm
Yellow: active warning
Gray: deactivated alarm (alarm state ceased)
There are two types of alarm:
Hard alarm:
Red pop-up alarm on the controller and alarm gen-
eration with the connected alarm units, e.g. a horn
Soft alarm:
Yellow pop-up alert on the controller.
In the alarm menu, it is possible to select whether some climate
and production alarms are to be hard or soft.
The controller will also activate an alarm signal, which you can
choose to maintain.
The alarm signal will thus continue to sound until you acknowl-
edge the alarm. This also applies even if the situation that trig-
gered the alarm has stopped
Alarms maintained:
YES
: The signal continues after the alarm situation has ceased.
NO
: The signal stops after the alarm situation has ceased.
The controller can remind you of an on-going alarm situation
once you have acknowledged a hard alarm. This to ensure that
the cause of the alarm is handled.
Settings for reminders:
Alarm time:
Setting how long after the alarm, the reminder is to
appear.
Repeat times:
Setting how many times the reminder is to ap-
pear.
6.1 Stopping an alarm signal
The alarm window disappears, and the alarm signal stops when you acknowledge the alarm by pressing
Ac-
knowledge
.