DOL 635 • DOL 639
User Manual
45
Feed line 1 feed stop sensor
defect
The alarm is a technical alarm to ensure that the stop sensor is working.
There should not be any feed outside of the sensor when
Max time to free
feed stop sensor
runs out, otherwise the alarm will be activated.
The alarm will stop when there is no more feed outside of the sensor.
The alarm can be connected and disconnected.
Feeding paused too long
The alarm is triggered when the ongoing feeding has been paused manually
longer than the set time (10 min.)
The alarm can be connected and disconnected.
Feed line 1 is not filled
The alarm is triggered when the filling of the entire section is not completed
within the designated time limit (
Feed line 1 maximum filling time
).
The alarm stops when the filling is completed within the time limit.
The alarm can be connected and disconnected.
Alarm for chain broken
Alarm for chain not running
The alarm is triggered when the controller registers that the feed chain is bro-
ken or not running properly. The alarm stops the feed program.
When the problem is solved, you can run manual feeding or wait for the feed
program’s next feeding.
A programmed filling on was
skipped
The alarm may be triggered for several reasons:
• The time between the feed program starts is not long enough in relation to
the
Minimum time to next filling
.
• A filling takes too long - for example, if it has been paused.
• A manual feeding has been started too close to a programmed feeding.
The alarm can be connected and disconnected.
Check if the animals need an extra manual feeding.
Dry feeding alarms subcircuit
Subcircuit 1 feed stop sensor
defect
The alarm is a technical alarm to ensure that the stop sensor is working.
There should not be any feed outside of the sensor when
Max time to free
feed stop sensor
runs out, otherwise the alarm will be activated.
The alarm will stop when there is no more feed outside of the sensor.
The alarm can be connected and disconnected.
Subcircuit 1 start sensor can-
not be emptied
The alarm is triggered when the start sensor does register that there is NO
feed outside of the sensor.
Subcircuit 1 start sensor can-
not be filled
The alarm is triggered when the start sensor does not register that there IS
feed outside the sensor. The subcircuit can therefore not be filled.
Feeding paused too long
The alarm is triggered when the ongoing feeding has been paused manually
longer than the set time (10 min.)
The alarm can be connected and disconnected.
Subcircuit 1 is not completed
The alarm is triggered when the filling of the feed line is completed before the
subcircuit is filled.
The alarm is triggered when the filling of the entire section is not completed
within the designated time limit (
Feed line 1 maximum filling time
).
The alarm stops when the filling is completed within the time limit.
The alarm can be connected and disconnected.
Alarm for chain broken
Alarm for chain not running
The alarm is triggered when the controller registers that the feed chain is bro-
ken or not running properly. The alarm stops the feed program.