background image

Disarming a triggered control panel

If "System Panic" is announced from the control panel after it has been disarmed,
that means the alarm was triggered when it was in armed mode.  Follow the
procedures below to set the control panel back to standby mode.

1. If the alarm was caused by sensor(s), there will be flashing LEDs and

beeping indicating which sensor(s) triggered the alarm.  You may want to
check the condition of the triggered sensor(s), the sensor(s) may be damaged
if there were break-ins.

2. You need to reset the sensor manually by triggering it twice, i.e. open and

then close a door / window sensor, or walk in front of the motion sensor. The
LED representing that sensor will stop flashing after it receives the signal
from the sensor.

3. You must now enter the password again on the control panel or press the

disarm button on the keychain remote, as an acknowledgement of the alarm
event.  This will set the control panel back to standby mode.

Disarming under Duress

If you are forcibly compelled to disarm the control panel, you may enter the Duress
Password.  Entering the duress password will terminate the entry delay, i.e. no
more entry delay beeping. But the control panel will silently call the emergency
phone numbers for help.  The called party will hear the voice announcement
“System Panic”.

Note:

- The default duress password is [3838].

19

Note:

- The control panel can also be disarmed remotely when nobody is home, with a

touch tone phone.  Please refer to “Remote Operation by Telephone” on page 24

.

- If 3 consecutive incorrect passwords are entered, alarm will sound immediately,

the control panel will be in panic mode, and start calling the emergency phone
numbers.

OPERATION

2. You must enter a valid password, either the Master Password, or Secondary

Password to disarm the system before entry delay expires.  The system can
also be disarmed by pressing button 3 on the keychain remote.

3. When a valid password is entered, you will hear “System Disarmed” and the

entry delay beeping will stop, the ARM LED will be off.

ADVANCED PROGRAMMING

Learn Sensors

You can program up to 10 sensors to the control panel.  There are 5 zones on
the control panel, each zone can program up to 2 sensors.  Before program-
ming a sensor, you must decide which sensor location (zone number and
sensor number) you would like to program the sensor to.  It is strongly recom-
mended that you refer to “Sensor Location Selection Guide” before deciding
which sensor location you would like to program the new sensors to.  Some
features you may need to consider are: 1) Beep/Alarm setting, 2) auto mute, 3)
alert zone , 4) event trigger.   Explanation for each feature can be found in the
following pages in Advanced Programming:

1. Beep/Alarm Setting - Page 26

2. Auto Mute - Page 29

3. Alert Zone - Page 30

4. Event Trigger - Page 42

Sensor Location Selection Guide

You can program up to 10 sensors to the control panel.  There are 5 zones and
maximum 2 sesnors per zone.  The 4 features mentioned above are Zone
dependent features meaning both sensors in that zone will operate based on
the setting for that zone.  So if you program 2 sensors into one zone, those 2
sensors will react in the same manner for those zone dependent features.  For
example, if you enable the Auto-Mute feature for zone 1, both zone 1 sensor 1,
and zone 1 sensor 2 will have this feature enabled.  It is not possible to enable a
zone dependent feature for sensor 1 only, but not sensor 2.

Therefore, the followings are some suggestions of how you should select the
sensor location.

1. Check all the zone dependent features, and determine if you would like to

enable any one of them.

2. If you decide not to enable any zone dependent features and keep the

factory default setting, you can simply program the sensor to any sensor
location based on your own preference.  Omit the following steps and
proceed to "Learn Sensor - Continue".

3. If you decide to enable some of the zone dependent features, check Table C

below.  Circle the zone dependent feature selections.  If there are features
that you would like to enable for more than 2 sensors, you need to select
more than one zone for those features.

34

Summary of Contents for AM-100

Page 1: ... 2005 PATENTED 2005 SKYLINK GROUP Home Smart Center www skylinkhome com CUSTOMER SERVICE 17 Sheard Avenue Brampton Ontario Canada L6Y 1J3 Tel 905 456 8883 Fax 905 456 7819 Email support skylinkhome com MODEL AM 100 TM ...

Page 2: ...Home Smart Center USER S INSTRUCTIONS English ...

Page 3: ... 5 Plug the adaptor to the socket outlet that near the equipment and shall be easily accessible SAVE THESE INSTRUCTIONS 1 Declaration of Conformity Application of Council Directive s Radio Equipment and Telecommunication Terminal Equipment Directive 1999 5 EC R TTE Standard s to which Conformity is Declared EMC EN 55022 1998 A1 2000 EN 610000 3 2 2000 EN 61000 3 3 1995 A1 2001 EN 55024 1998 A1 200...

Page 4: ...an as appropriate The Ringer Equivalence Number is an indication of the maximum number of terminals allowed to be connected to a telephone inter face The termination on an interface may consist of any combination of devices subject only to the requirement that the sum of the Ringer Equivalence Numbers of all the devices does not exceed five g Should you experience trouble with this equipment pleas...

Page 5: ...used to connect this equipment to the premises wiring and telephone network must comply with the applicable FCC Part 68 rules and requirements adopted by the ACTA A compliant telephone cord and modular plug is provided with this product It is designed to be connected to a compatible modular jack that is also compliant See installation instructions for details d The REN is used to determine the num...

Page 6: ...s closely you should find it very easy to set up the system In the package you should find the following items One Control Panel One Motion Sensor Two Door Window Sensors One Keychain Remote Alert When Home System Not Armed Beep Beep Alarm Not Home System Armed Alarm Automation Communicator T M AM 001 PS 101 WD 101 4B 101 Master Password ____________________ Secondary Password ____________________...

Page 7: ...nsors WD 101 5 Install Motion Sensor PS 101 9V Mounting Plate Ball head joint Screws Pack Control Module SW 100 US and Canada To turn home appliances lights on off Max rating 960W Resistive Control Module SW 101U UK SW 101F French SW 101G German 3 models for 3 countries Emergency Dialer AD 433S External dialer with user programmable voice message Calls up to 9 phone numbers One personal voice reco...

Page 8: ...e detector CO detector so when these detectors are triggered the control panel will be triggered Remote Control 4B 101 Additional keychain remotes for other family members To arm disarm or trigger the panic alarm with this remote Keypad Control KP 434 External keypad control To arm disarm or trigger the the panic alarm with this remote Ideal mounting locations include upper floor backdoor or garag...

Page 9: ...atteries the LO BATT LED should be off 3 Connect the phone line from the telephone jack to the back of the control panel where it marks LINE PWR will stay on and PROG LED will stop flashing 4 OPTIONAL If you have another telephone that will be using the same telephone jack you may connect this telephone to PHONE outlet of the the control panel by a phone cord not provided 5 Rotate the antenna to t...

Page 10: ...times it does and if a motion is then detected that is the First Motion So if you continue to walk in front of the motion sensor it will only pick up the first motion Unless you wait for 20 seconds then walk again the control panel will respond Otherwise the control will only respond to the first motion TROUBLE SHOOTING 45 When a sensor is triggered the Make sure the battery in the sensor is contr...

Page 11: ...d to disarm the system again by sensor is triggered and the ARM LED either entering the password or disarm by is off keychain remote Although the ARM LED is off but the system is not completely disarmed after an alarm was triggered Refer to page 19 on how to completely disarm a control panel after an alarm has been triggered Why the ARM LED keeps flashing That means you have not programmed any eme...

Page 12: ...hone memory 1 has higher priority You will hear Enter phone memory You will hear Phone Accepted indicating the phone number and its settings have been programmed successfully Repeat is the number of times that voice emergency message will be played from 1 to 9 times It is recommended to set up the repeat time to 5 or more Redial is the number of times that phone number will be called Each phone nu...

Page 13: ... how to react to an emergency call The password is treated as a confirmation of the emergency message Once a valid password is entered the control panel will not call that number again it will proceed to the next number If any one of the called parties disarms the control panel the control panel will not continue to dial the remaining phone numbers After calling all the programmed phone numbers th...

Page 14: ...it is recommended to screw the mounting plate to the frame then apply double sided tape After mounting the sensor if the AAA logo is inverted remove the front cover and rotate it so the AAA logo is in the upright position INSTALLATION Installing Door Window Sensors Transmitter Magnet Double sided foam tape Mounting plate and screws optional Sensor Sensor Sensor Magnet Magnet Red Marking Red Markin...

Page 15: ...ng a control module which involves 2 parts 1 Erase the memory of the control panel 2 Erase the memory of the control module Part 1 Erase the memory of the Control Panel 1 2 3 PROG MPIN Enter Programming mode Enter master password to programmingmode 3 beeps for valid password 1 long beep for invalid password 0 Select erase control module programming After 0 is entered some zone LEDs will flash or s...

Page 16: ...etween 2 activations INSTALLATION You may now close the battery cover and re insert the screw Mount the ball head joint on the wall with screws provided Slide the back of the sensor into the ball head joint The mounting angle can be adjusted For outdoor monitoring please refer to page 30 to program the motion sensor to Alert Zone M 0 1 2 3 4 5 6 7 8 9 10 11 12 13 2 4 6 8 10 12 14 DETECTING AREA Un...

Page 17: ...1 Triggered 2 Beep___Beep___ Beep___Beep Zone 1 Sensor 1 door open Zone 3 Sensor 2 window open Part 1 Learn signal from Control Module to Control Panel HOME AUTOMATION ZONE LED DESCRIPTION Off Zone is not occupied by any control module Flashes once This zone is occupied by another control module Programming another remote to this zone will overwrite the previous control module Flashes twice This z...

Page 18: ...l can be used to control lights and home applicances with a Control Module Control Module is sold separately Garage door opener can be controlled with a Garage Door Receive sold separately The Control Panel can control up to 5 Control Modules Garage Door Receivers There are 3 ways to control these modules receivers 1 Using the keypad on the control panel to operate these modules receivers manually...

Page 19: ...us 17 OPERATION OR 1 Press Arm on the control panel or keychain remote 2 Leave the premises within 45 seconds 3 After 45 seconds System will be armed Beep Beep Exit delay 45 seconds 45 seconds later ARM LED on System Armed ADVANCED PROGRAMMING Zone 1 SENSOR 1 Button 1 SENSOR 2 Zone 2 Zone 3 Zone 4 Zone 5 Button 2 Button 3 Button 4 Button 5 Button 6 Button 7 Button 8 Button 9 Button 0 This row Butt...

Page 20: ...should look something like this Youmayrefertoeach column representing the zone dependent feature to program each zone with the selected feature For example Auto Mute featureis only enabled for zone 3 when you are in the auto mute programming you should enable this feature for zone 3 only the rest of the zones should have this feature disabled Repeat this step for all 4 zone dependent features duri...

Page 21: ...d and the entry delay beeping will stop the ARM LED will be off ADVANCED PROGRAMMING Learn Sensors You can program up to 10 sensors to the control panel There are 5 zones on the control panel each zone can program up to 2 sensors Before program ming a sensor you must decide which sensor location zone number and sensor number you would like to program the sensor to It is strongly recom mended that ...

Page 22: ...you should contact your local phone company PANIC ARM DISARM AUX Control other Skylink receiver such as Garage Door Receiver Model 18R ADVANCED PROGRAMMING Erase Keychain Keypad Remotes 1 2 3 PROG MPIN Enter Programming mode Enter master password to pro gramming mode 3 beeps for valid password 1 long beep for invalid password 0 Select erase remote programming After 0 is entered some zone LEDs will...

Page 23: ...e announcement zone X sensor Y failure will be played ADVANCED PROGRAMMING ZONE LED DESCRIPTION Off Zone is not occupied by any remote Flashes twice This zone is occupied by another remote Programming another remote to this zone will overwrite the previous remote Flashes once This zone is occupied by a control module Optional You can still program a remote to this zone and it will not overwrite th...

Page 24: ...ensor Y low battery where X and Y represent the zone and sensor number Please replace the battery of that sensor ADVANCED PROGRAMMING To enable alert zone feature follow the instructions below 1 2 3 4 Enter Program ming mode Enter master password to programming mode 3 beeps for valid password 1 long beep for invalid password Refer to the diagram below to select the appropriate setting PROG when fi...

Page 25: ... the next section Remote Operation by Telephone Zone 1 Sensor 1 Triggered Enter Password Arm Disarm Check status Control lighting etc Disconnect COMMUNICATION 23 Zone 1 DISABLE AUTO MUTE Button 1 ENABLE AUTO MUTE Zone 2 Zone 3 Zone 4 Zone 5 Button 2 Button 3 Button 4 Button 5 Button 6 Button 7 Button 8 Button 9 Button 0 This row Buttons to Disable Auto Mute Zone LED Flash This row Buttons to Enabl...

Page 26: ...ted either beep or alarm For example if a door is opened the beep will not stop until the door is closed If the door is open for 2 hours the beep will go on for 2 hours There are times that this is not desired With the auto mute feature enabled the beep will go on for only 20 seconds After that even if the sensor remains open the beep will stop only the zone LED will flash to indicate the sensor i...

Page 27: ... mode Enter master password to programmingmode 3 beeps for valid password 1 long beep for invalid password 5 Select Beep Alarm Setting After 5 is entered some zone LEDs will flash or stay on This indicates whether that zone is set to beep or alarm 3 Set to Beep 1 to 5 SettoAlarm 6 to 0 Select which zone you would like to Beep or Alarm Refer to the diagram below to select the appro priate setting I...

Page 28: ...f a zone is set to Alarm alarm will sound instantly when a sensor is triggered Alarm will stop when the sensor is deactivated or reaches a 3 minute time out period System Armed Alarm Mode If a zone is set to Beep the control panel will give entry exit delay If a zone is set to Alarm the siren will sound immediately without entry delay Alarm Mode System Armed If a sensor is triggered i e opening a ...

Reviews: