Jaguar Model J-390

6

2. CONDENSATE REMOVAL SYSTEM

The Jaguar boilers are equipped with a built-in conden-

sation drain and trap. The trap must be filled with water.

DO NOT operate the boiler without filling the trap with

water to prevent flue gas discharge into space. Periodic

inspection should be made of this assembly for deterio-

ration of the tubing and to insure that the trap is not

plugged. If it is plugged or appears to have excessive

sediment in it, it should be removed from the drain

assembly, straightened out to clear the obstruction,

reformed, filled with water and reinstalled as before.

(See Figure 7).

Leave the top of the condensate drain tee open, to act

as a vacuum breaker. Do not allow any part of the 

condensate removal system to be exposed to freezing

temperatures, or any other conditions that could cause

blockage.

If a neutralizing system is installed, the filter medium

will require periodic changing, to ensure it’s effective-

ness. Refer to the neutralizing unit’s manufacturers

instructions, if available, or change the medium on an

annual basis.

3. PIPING INSPECTION

Look at all water piping. There should be no leaks or

signs of leaks at any pipe joints or around the boiler.

4. SYSTEM WATER PRESSURE INSPECTION

The boiler water pressure is indicated on the pressure

gauge (See Figure 1 for location). The boiler water out-

let temperature is normally indicated on the tempera-

ture display (See Figure 1 for location and Figure 9 for

digits illustration). For most installations, it should

indicate about 83 to 103 kPa (12 to 15 psi) pressure

when temperature is about 21° to 38°C (70° to 100°F)

and from 103 to 172 kPa (15 psi to 25 psi) when tem-

perature is up to 91°C (195°F). FOR YOUR SYSTEM,

there is one correct pressure for each temperature.

ASK YOUR INSTALLER OR SERVICEPERSON TO

EXPLAIN AND SHOW YOU. Learn what normal pres-

sure to look for. If pressure increases from normal, the

relief valve will open to relieve the pressure. Call your

service organization if pressures are higher or lower

than normal, and if the relief valve spills water. Repair or

adjustment is needed.

5. UNUSUAL NOISE

Stand near the boiler and look and listen. As the burner

starts and shuts off, there should be no unusual noise. 

6. BOILER ROOM AIR SUPPLY

Ample boiler room fresh air is required for combustion

(non-direct vent installation) and ventilation (direct-vent

installation). 

Check air vents for continuous positive supply of air as

required. Air needs are greatest in cold weather if boiler

installation is non-direct vent method. Air vents must be

open and free of obstruction.

Warning: 

The flow of combustion and ventilating air to the

boiler should not be obstructed.

Warning: 

If you find any problem during your inspection, call

for service immediately. 

Figure 7. Condensate disposal system

NEUTRALIZING UNIT (IF REQUIRED)

CONDENSATE PUMP (IF REQUIRED)

DRAIN INSIDE BUILDING

PLASTIC TUBING

DRAIN VACUUM BREAKER, LEAVE OPEN

Summary of Contents for J-390

Page 1: ...nity of this or any other appliance __ WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any electrical switch DO NOT use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas suppli er s instructions If you cannot reach your gas supplier call the fire department __ Installation and service must be performed by a qualified ins...

Page 2: ...s boiler if any part has been underwater Immediately call a qualified service technician to inspect the boiler and to replace any part of the control system and any gas control which has been underwater WARNING Should overheating occur or the gas supply fail to shut off DO NOT turn off or disconnect the electric supply to the circulator pump Instead shut off the gas supply at a location EXTERNAL t...

Page 3: ... Non direct vent installation is shown on Figures 4 5 and 6 1 VENTING AND AIR INTAKE SYSTEM REGULAR INSPECTION Inspect the system regularly for condensation corrosion sagging and or physical damage A qualified professional should service the boiler annually and include such an inspection at that time The homeowner should look over the system monthly for damage water stains any signs of rust other ...

Page 4: ...Jaguar Model J 390 4 AIR INTAKE DO NOT BLOCK 4 DIA VENT PIPE VENT TERMINATION OUTSIDE WALL Figure 4 Non direct vent sidewall venting 102mm 4 DIA VENT PIPE ...

Page 5: ...RMINATION 4 DIA VENT PIPE AIR INTAKE DO NOT BLOCK Figure 6 Non direct vent utilizing an existing chimney as a chase VENT TERMINATION CHIMNEY TOP PLATE 4 DIA VENT PIPE 4 DIA VENT PIPE AIR INTAKE DO NOT BLOCK UNUSED CHIMNEY 102mm 4 DIA VENT PIPE 102mm 4 DIA VENT PIPE 102mm 4 DIA VENT PIPE ...

Page 6: ...ure is normally indicated on the tempera ture display See Figure 1 for location and Figure 9 for digits illustration For most installations it should indicate about 83 to 103 kPa 12 to 15 psi pressure when temperature is about 21 to 38 C 70 to 100 F and from 103 to 172 kPa 15 psi to 25 psi when tem perature is up to 91 C 195 F FOR YOUR SYSTEM there is one correct pressure for each temperature ASK ...

Page 7: ...uilding Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your hand to turn the gas supply shut off valve Never use tools If the supply shut off will not turn by hand don t try to repair it call a qualified service technician Force or attempted repair may result in a fire or ex...

Page 8: ... C 90 to 185 F 2 While d is blinking boiler supply water tempera ture for DHW may be set to desired temperature The setting range is between 40 to 85 C 104 to 185 F 3 While t is blinking DHW tank temperature may be set to desired temperature if tank is equipped with sensor The setting range is between 40 to 85 C 104 to 185 F 4 View actual following temperatures on Temperature Display Press Select ...

Page 9: ...pressed to resume normal operation Error Condition Temperature display indicates the error code Warning Condition Temperature display indicates the error code Jaguar Boiler Display Board Boiler Operation Status Note Blinking dot on Mode Display indicates active heating control burner off Steady dot indicates burner is on Error must be corrected to resume boiler operation Pressing the Reset button ...

Page 10: ...Settable from 40 to 71 C 104 F to 160 F steps of 0 55 C 1 F The default valve is 60 C 140 F Press Enter button to store see note 3 Temperature display shows actual supply water temperature Temperature display shows actual return water temperature Temperature display shows actual DHW tank temperature if the water tank is equipped with sensor Temperature display shows actual flue gas temperature Tem...

Page 11: ...d once the condition returns to normal or is fixed The temperature display shows the error code Pressing the Reset button is not required C WARNING ERRORS Indicated by an H in the mode display Operation of the space heating mode is not affected and the warning is displayed intermittently Operation of the DHW mode is automatically restored once the condition is fixed The temperature display shows t...

Page 12: ... FIN LTD LTEE 6450 Northam Drive Mississauga Ontario L4V 1H9 Phone 905 677 8400 FAX 905 677 1829 Order Desk Fax 905 677 9015 www slantfin ca E mail orderdesk slantfin ca info slantfin ca Slant Fin Corp 2008 ...

Reviews: